Carrier 50JZ024 Installation, Start-Up And Service Instructions Manual Download Page 14

SPECIAL PROCEDURES FOR 208V OPERATION

1. Be sure unit disconnect switch is open.

2. Disconnect the yellow primary lead (w110) from the trans-

former. See unit wiring label (Fig. 12 and 13).

3. Connect the yellow primary lead (w110) to the transformer

terminal labeled 200v.

Indoor blower-motor speeds may need to be changed for 208v
operation. Refer to indoor airflow and airflow adjustments section.

PRE-START-UP

Failure to observe the following warnings could result in
serious personal injury or death:
1. Follow recognized safety practices and wear protective

goggles when checking or servicing refrigerant system.

2. Do not operate compressor or provide any electric power to

unit unless compressor terminal cover is in place and
secured.

3. Do not remove compressor terminal cover until all electri-

cal sources are disconnected.

4. Relieve and recover all refrigerant from both high- and

low-pressure sides of system before touching or disturbing
anything inside terminal box if refrigerant leak is suspected
around compressor terminals.

5. Never attempt to repair soldered connection while refrig-

erant system is under pressure.

6. Do not use torch to remove any component. System

contains oil and refrigerant under pressure.
To remove a component, wear protective goggles and
proceed as follows:
a. Shut off electrical power to unit.
b. Relieve and reclaim all refrigerant from system using

both high- and low-pressure ports.

c. Cut component connecting tubing with tubing cutter and

remove component from unit.

d. Carefully unsweat remaining tubing stubs when neces-

sary. Oil can ignite when exposed to torch flame.

Use the Start-Up Checklist supplied at the end of this book and
proceed as follows to inspect and prepare the unit for initial
start-up:

1. Remove all access panels.

2. Read and follow instructions on all DANGER, WARNING,

CAUTION, and INFORMATION labels attached to, or
shipped with, unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages such as broken

lines, loose parts, disconnected wires, etc.

b. Inspect for oil at all refrigerant tubing connections and on

unit base. Detecting oil generally indicates a refrigerant
leak. Leak-test all refrigerant tubing connections using

electronic leak detector, or liquid-soap solution. If a refrig-
erant leak is detected, see following Check for Refrigerant
Leaks section.

c. Inspect all field and factory-wiring connections. Be sure

that connections are completed and tight.

d. Inspect coil fins. If damaged during shipping and handling,

carefully straighten fins with a fin comb.

4. Verify the following conditions:

a. Make sure that outdoor-fan blade is correctly positioned in

fan orifice.

b. Make sure that air filter(s) is in place.

c. Make sure that condensate drain pan and trap are filled with

water to ensure proper drainage.

d. Make sure that all tools and miscellaneous loose parts have

been removed.

5. Compressors are internally spring mounted. Do not loosen or

remove compressor hold-down bolts.

6. Each unit system has 2 Schrader-type ports, one low-side

Schrader fitting located on the suction line, and one high-side
Schrader fitting located on the compressor discharge line. Be
sure that caps on the ports are tight.

START-UP

Using the Start-Up Checklist supplied at the end of this book,
proceed as follows:

Step 1—Check for Refrigerant Leaks

Locate and repair refrigerant leaks and charge the unit as follows:

1. Use both high- and low-pressure ports to relieve system

pressure and reclaim remaining refrigerant.

2. Repair leak following accepted practices.

NOTE: Replace biflow filter drier whenever the system has
been opened for repair.

3. Check system for leaks using an approved method.

4. Evacuate refrigerant system and reclaim refrigerant if no

additional leaks are found.

5. Charge unit with R-410A refrigerant, using a volumetric-

charging cylinder or accurate scale. Refer to unit rating plate
for required charge.

Step 2—Start-Up Adjustments

Complete the required procedures given in the Pre-Start-Up
section on this page before starting the unit. Do not jumper any
safety devices when operating the unit. Do not operate the unit in
Cooling mode when the outdoor temperature is below 40°F (unless
accessory low-ambient kit is installed). Do not rapid-cycle the
compressor. Allow 5 minutes between ‘‘on’’ cycles to prevent
compressor damage.

CHECKING COOLING AND HEATING CONTROL OPERA-
TION — Start and check the unit for proper control operation as
follows:

Fig. 19—Transformer Label

C99058

TRANSFORMER CONTAINS A MANUAL
RESET OVERCURRENT PROTECTOR

IT WILL NOT AUTOMATICALLY RESET

DISCONNECT POWER PRIOR TO
SERVICING

THIS COMPARTMENT MUST BE CLOSED
EXCEPT WHEN SERVICING

Fig. 20—Fan Blade Clearance

C99009

FAN GRILLE

MOTOR

1/8" MAX BETWEEN
MOTOR AND FAN HUB

MOTOR SHAFT

14

Summary of Contents for 50JZ024

Page 1: ...cautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for unbrazin...

Page 2: ...house overhang is 48 in above the unit top The maximum horizontal extension of a partial over hang must not exceed 48 in IMPORTANT Do not restrict outdoor airflow An air restriction at either the out...

Page 3: ...ENTS 36 914 UNIT TOP 48 1219 SIDE OPPOSITE DUCTS 36 914 DUCT PANEL 12 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 IN 304 8 MM FROM WALL SYSTEM THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED...

Page 4: ...IL ACCESS SIDE 36 00 914 0 POWER ENTRY SIDE 36 00 914 0 EXCEPT FOR NEC REQUIREMENTS UNIT TOP 48 00 1219 0 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LES...

Page 5: ...S 1 Roof curb must be setup for unit being installed 2 Seal strip gasket must be applied as required 3 Dimensions are in inches 4 Attach ductwork to flanges of the curb 5 R A Return Air S A Supply Air...

Page 6: ...t duct connector or sheet metal sleeve must extend 24 in from electric heater element 1 Size ductwork for cooling air quantity cfm The minimum air quantity for proper electric heater operation is list...

Page 7: ...2 0 040 2 0 038 2 0 046 2 0 052 OUTDOOR COIL Rows Fins in Face Area sq ft 2 17 8 5 2 17 10 3 2 17 10 3 2 17 13 5 2 17 13 5 2 17 15 4 OUTDOOR FAN Nominal Airflow CFM Diameter Motor HP RPM 2350 22 1 8 8...

Page 8: ...orrection of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage contained within conduit when low voltage control wires are in same conduit as high voltage wires...

Page 9: ...Fig 12 Wiring Schematics 208 230 1 60 C00097 9...

Page 10: ...Fig 13 Wiring Schematics 208 230 3 60 C00098 10...

Page 11: ...Fig 14 Wiring Schematics 460 3 60 C00099 11...

Page 12: ...50 3 57 2 72 8 83 3 95 4 109 3 40 40 40 40 60 60 80 90 100 110 208 230 3 60 187 253 15 4 88 0 0 9 4 1 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 10 4 12 0 20 8 24 1 31 3 36 1 41 6 48 0 24 3 24 3 24 3 24 3 3...

Page 13: ...percent of voltage imbalance Voltage imbalance max voltage deviation from average voltage 100 x average voltage EXAMPLE Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 452 464 455 Average Voltag...

Page 14: ...leak is detected see following Check for Refrigerant Leaks section c Inspect all field and factory wiring connections Be sure that connections are completed and tight d Inspect coil fins If damaged d...

Page 15: ...h Accurater Metering Device Arrow indicates direction of flow Metering Position Bypass Position HPS Fig 21 Typical Heat Pump Operation Heating Mode 1 Hot gas from compressor flows through the 4 way va...

Page 16: ...and temperature sensing devices are required Connect the pressure gauge to the service port on the suction line Mount the tempera ture sensing device on the suction line and insulate it so that the ou...

Page 17: ...411 394 381 Cfm 1374 1290 1205 1116 1020 916 Med Watts 523 506 490 471 449 426 Cfm 1500 1408 1301 1190 1082 977 High Watts 645 628 610 595 584 575 Cfm 1474 1369 1267 1169 1069 962 42 Low Watts 660 639...

Page 18: ...TEMP F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 50JZ500066 Fig 24 Cooling Charging Chart 50JZ 030 Units C00083 030 60 Hz COOLING CHARGING CHART For Use with Units Using R410a Refrige...

Page 19: ...oling Charging Chart 50JZ 060 Units C00087 060 60 Hz COOLING CHARGING CHART For use with units using R410a Refrigerant 80 90 100 110 120 130 140 150 160 170 180 20 30 40 50 60 70 80 SUCTION LINETEMPER...

Page 20: ...COIL INDOOR COIL AND CONDENSATE DRAIN PAN Inspect the outdoor coil indoor coil and conden sate drain pan at least once each year The coils are easily cleaned when dry therefore inspect and clean the...

Page 21: ...at 610 psig High pressure may be caused by a dirty outdoor coil failed fan motor or outdoor air recirculation To check switch 1 Turn off all power to unit 2 Disconnect leads on switch 3 Apply ohmeter...

Page 22: ...or 60 sec on 030 060 sizes or 30 sec on 024 size after thermostat is satisfied This delay enables blower to remove residual cooling in coil after compression shutdown thereby improving efficiency of s...

Page 23: ...es with 750 psig service pressure rating Leak detectors should be designed to detect HFC refrigerant Puron as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture fro...

Page 24: ...ities shown on nameplate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start cap...

Page 25: ...IST REMOVE AND STORE IN JOB FILE I PRELIMINARY INFORMATION Model No Serial No Date Technician II PRE START UP ___ Verify that all packing materials have been removed from unit ___ Remove all shipping...

Page 26: ...26...

Page 27: ...27...

Page 28: ...46231 50jz 1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 565...

Reviews: