background image

Before performing service or maintenance operations on
system, turn off main power to unit. Turn off accessory heater
power switch if applicable. Electrical shock could cause
severe injury or death.

Puron (R-410A) systems operate at higher pressures than
standard R-22 systems. Do not use R-22 service equipment or
components on Puron (R-410A) equipment. Ensure service
equipment is rated for Puron (R-410A).

INTRODUCTION

The 50JZ heat pump is fully self-contained and designed for
outdoor installation (See Fig. 1). Standard units are shipped in a
horizontal-discharge configuration for installation on a ground-
level slab. Standard units can be converted to downflow (vertical)
discharge configurations for rooftop applications.

RECEIVING AND INSTALLATION

Step 1—Check Equipment

IDENTIFY UNIT — The unit model number and serial number
are stamped on the unit identification plate. Check this information
against shipping papers.

INSPECT SHIPMENT — Inspect for shipping damage while unit
is still on shipping pallet. If unit appears to be damaged or is torn
loose from its anchorage, have it examined by transportation
inspectors before removal. Forward claim papers directly to
transportation company. Manufacturer is not responsible for any
damage incurred in transit. Check all items against shipping list.
Immediately notify the nearest Carrier Air Conditioning office if
any item is missing. To prevent loss or damage, leave all parts in
original packages until installation.

Step 2—Provide Unit Support

ROOF CURB — Install accessory roof curb in accordance with
instructions shipped with curb (See Fig. 4). Install insulation, cant
strips, roofing, and flashing. Ductwork must be attached to curb.

IMPORTANT:

The gasketing of the unit to the roof curb is critical

for a watertight seal. Install gasketing material supplied with the
roof curb. Improperly applied gasketing also can result in air leaks
and poor unit performance.

Curb should be level to within 1/4 in. (Fig. 5). This is necessary for
unit drain to function properly. Refer to accessory roof curb
installation instructions for additional information as required.

SLAB MOUNT — Place the unit on a solid, level concrete pad
that is a min of 4 in. thick with 2 in. above grade (Fig. 6). The slab
should extend approximately 2 in. beyond the casing on all 4 sides
of the unit. Do not secure the unit to the slab except when required
by local codes.

GROUND MOUNT — The unit may be installed either on a slab
or placed directly on the ground if local codes permit. Place the
unit on level ground prepared with gravel for condensate dis-
charge.

Step 3—Provide Clearances

The required minimum service clearances are shown in Fig. 2 and
3. Adequate ventilation and outdoor air must be provided. The
outdoor fan draws air through the outdoor coil and discharges it
through the top fan grill. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a
corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a normal house overhang) is 48
in. above the unit top. The maximum horizontal extension of a
partial over-hang must not exceed 48 in.

IMPORTANT:

Do not restrict outdoor airflow. An air restriction

at either the outdoor-air inlet or the fan discharge may be
detrimental to compressor life.

Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting, tile, or other combustible materials. Slab-mounted units
should be at least 4 in. above the highest expected water and runoff
levels. Do not use unit if it has been under water.

Step 4—Rig and Place Unit

Rigging and handling of this equipment can be hazardous for many
reasons due to the installation location (roofs, elevated structures,
etc.)

Only trained, qualified crane operators and ground support staff
should handle and install this equipment.

When working with this equipment, observe precautions in the
literature, on tags, stickers and labels attached to the equipment,
and any other safety precautions that might apply.

Follow all applicable safety codes. Wear safety shoes and work
gloves.

INSPECTION — Prior to initial use, and at monthly intervals, all
rigging brackets and straps should be visually inspected for any
damage, evidence of wear, structural deformation, or cracks.
Particular attention should be paid to excessive wear at hoist
hooking points and load support areas. Brackets or straps showing
any kind of wear in these areas must not be used and should be
discarded.

INSTALLATION

1. Remove unit from shipping carton. Leave top shipping skid on

the unit as a spreader bar to prevent the rigging straps from
damaging the unit. If the wood skid is not available, use a
spreader bar of sufficient length to protect unit from damage.

2. Position the lifting bracket assembly around the base of the

unit. Be sure the strap does not twist.

3. Place each of the 4 metal lifting brackets into the handholds in

the composite pan.

4. Thread lifting bracket strapping around bottom perimeter of

unit as follows:

a. Open lever of tension buckle (ratchet type).

b. Feed strapping through tension buckle as shown in Fig. 7.

c. Pull strapping through tension buckle unit taut.

d. Snap lever down to lock strap in tension buckle. To release

strapping, squeeze safety latch, lift lever, and pull webbing
outward.

5. Tighten the tension buckle until it is taut. Lifting brackets

must be secure in the handholds.

6. Attach field-supplied clevis or hook of sufficient strength to

hole in the lifting bracket (See Fig. 8).

7. Attach the 2 safety straps directly to the clevis or hook at the

4 rigging brackets. DO NOT attach the safety straps to the
lifting brackets (See Fig. 8).

8. Position lifting point directly over the unit’s center of gravity.

9. Lift unit. When unit is directly over the roof curb, remove the

2 safety straps. Lower the equipment onto the roof curb.

10. After the unit is placed on the roofcurb or mounting pad,

remove the top crating. On 50JZ060 units only, 2 wire ties
fastened to the outdoor coils and reversing valve/accumulator
assembly must be cut. Remove the left and front louver panels
and corner post to access the wire ties. The wire tie to be cut
on the left is located approximately 4 in. down the tube sheet

2

Summary of Contents for 50JZ024

Page 1: ...cautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for unbrazin...

Page 2: ...house overhang is 48 in above the unit top The maximum horizontal extension of a partial over hang must not exceed 48 in IMPORTANT Do not restrict outdoor airflow An air restriction at either the out...

Page 3: ...ENTS 36 914 UNIT TOP 48 1219 SIDE OPPOSITE DUCTS 36 914 DUCT PANEL 12 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 IN 304 8 MM FROM WALL SYSTEM THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED...

Page 4: ...IL ACCESS SIDE 36 00 914 0 POWER ENTRY SIDE 36 00 914 0 EXCEPT FOR NEC REQUIREMENTS UNIT TOP 48 00 1219 0 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LES...

Page 5: ...S 1 Roof curb must be setup for unit being installed 2 Seal strip gasket must be applied as required 3 Dimensions are in inches 4 Attach ductwork to flanges of the curb 5 R A Return Air S A Supply Air...

Page 6: ...t duct connector or sheet metal sleeve must extend 24 in from electric heater element 1 Size ductwork for cooling air quantity cfm The minimum air quantity for proper electric heater operation is list...

Page 7: ...2 0 040 2 0 038 2 0 046 2 0 052 OUTDOOR COIL Rows Fins in Face Area sq ft 2 17 8 5 2 17 10 3 2 17 10 3 2 17 13 5 2 17 13 5 2 17 15 4 OUTDOOR FAN Nominal Airflow CFM Diameter Motor HP RPM 2350 22 1 8 8...

Page 8: ...orrection of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage contained within conduit when low voltage control wires are in same conduit as high voltage wires...

Page 9: ...Fig 12 Wiring Schematics 208 230 1 60 C00097 9...

Page 10: ...Fig 13 Wiring Schematics 208 230 3 60 C00098 10...

Page 11: ...Fig 14 Wiring Schematics 460 3 60 C00099 11...

Page 12: ...50 3 57 2 72 8 83 3 95 4 109 3 40 40 40 40 60 60 80 90 100 110 208 230 3 60 187 253 15 4 88 0 0 9 4 1 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 10 4 12 0 20 8 24 1 31 3 36 1 41 6 48 0 24 3 24 3 24 3 24 3 3...

Page 13: ...percent of voltage imbalance Voltage imbalance max voltage deviation from average voltage 100 x average voltage EXAMPLE Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 452 464 455 Average Voltag...

Page 14: ...leak is detected see following Check for Refrigerant Leaks section c Inspect all field and factory wiring connections Be sure that connections are completed and tight d Inspect coil fins If damaged d...

Page 15: ...h Accurater Metering Device Arrow indicates direction of flow Metering Position Bypass Position HPS Fig 21 Typical Heat Pump Operation Heating Mode 1 Hot gas from compressor flows through the 4 way va...

Page 16: ...and temperature sensing devices are required Connect the pressure gauge to the service port on the suction line Mount the tempera ture sensing device on the suction line and insulate it so that the ou...

Page 17: ...411 394 381 Cfm 1374 1290 1205 1116 1020 916 Med Watts 523 506 490 471 449 426 Cfm 1500 1408 1301 1190 1082 977 High Watts 645 628 610 595 584 575 Cfm 1474 1369 1267 1169 1069 962 42 Low Watts 660 639...

Page 18: ...TEMP F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 50JZ500066 Fig 24 Cooling Charging Chart 50JZ 030 Units C00083 030 60 Hz COOLING CHARGING CHART For Use with Units Using R410a Refrige...

Page 19: ...oling Charging Chart 50JZ 060 Units C00087 060 60 Hz COOLING CHARGING CHART For use with units using R410a Refrigerant 80 90 100 110 120 130 140 150 160 170 180 20 30 40 50 60 70 80 SUCTION LINETEMPER...

Page 20: ...COIL INDOOR COIL AND CONDENSATE DRAIN PAN Inspect the outdoor coil indoor coil and conden sate drain pan at least once each year The coils are easily cleaned when dry therefore inspect and clean the...

Page 21: ...at 610 psig High pressure may be caused by a dirty outdoor coil failed fan motor or outdoor air recirculation To check switch 1 Turn off all power to unit 2 Disconnect leads on switch 3 Apply ohmeter...

Page 22: ...or 60 sec on 030 060 sizes or 30 sec on 024 size after thermostat is satisfied This delay enables blower to remove residual cooling in coil after compression shutdown thereby improving efficiency of s...

Page 23: ...es with 750 psig service pressure rating Leak detectors should be designed to detect HFC refrigerant Puron as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture fro...

Page 24: ...ities shown on nameplate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start cap...

Page 25: ...IST REMOVE AND STORE IN JOB FILE I PRELIMINARY INFORMATION Model No Serial No Date Technician II PRE START UP ___ Verify that all packing materials have been removed from unit ___ Remove all shipping...

Page 26: ...26...

Page 27: ...27...

Page 28: ...46231 50jz 1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 565...

Reviews: