Troubleshooting Chart (cont’d)
SYMPTOM
CAUSE
REMEDY
Suction pressure too low
(Cool) Dirty air filter
Replace filter
(Heat) Outdoor coil frosted
Move timer on control board to 30 minutes be-
tween defrost cycles
Low refrigerant charge
Check for leaks, repair and recharge
Metering device or low side restricted
Remove source of restriction
(Cool) Insufficient coil airflow
Increase air quantity
Check filter—replace if necessary
(Cool) Temperature too low in conditioned area
Reset thermostat
(Cool) Outdoor ambient below 40°F
Install low-ambient kit
Filter-drier restricted
Replace
Compressor runs but outdoor fan does not
NC (normally closed) contacts on defrost board
open
Check condition of relay on board
Replace if necessary
IFM does not run
Blower wheel not secured to shaft
Properly tighten blower wheel to shaft.
Insufficient voltage at motor
Determine cause and correct
Power connectors not properly sealed
Connectors should snap easily; do not force
IFM operation is intermittent
Water dripping into motor
Verify proper drip loops in connector wires
Connectors not firmly sealed
Gently pull wires individually to be sure they are
crimped into the housing
IFM—Indoor Fan Motor
START-UP CHECKLIST
(REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY INFORMATION
Model No...............................................................................................................................................................................................................
Serial No. ...............................................................................................................................................................................................................
Date ........................................................................................................................................................................................................................
Technician..............................................................................................................................................................................................................
II. PRE-START-UP
___ Verify that all packing materials have been removed from unit
___ Remove all shipping holddown bolts and brackets per installation instructions
___ Verify that condensate connection is installed per installation instructions
___ Check all electrical connections and terminals for tightness
___ Check that indoor (evaporator) air filter is clean and in place
___ Verify that unit installation is level
___ Check fan wheel and propeller for location in housing and setscrew tightness
III. START-UP
Supply Voltage: L1-L2 __________ L2-L3 _________ L3-L1 __________
Compressor Amps: L1 __________ L2 _________ L3 __________
Indoor Fan Amps: __________
AIR TEMPERATURE
Outdoor-Air Temperature: __________ DB
Return-Air Temperature: __________ DB __________ WB
Heat Pump Supply Air: __________
Electric Heater Supply Air: __________
REFRIGERANT PRESSURES AND TEMPERATURES
Refrigerant Suction __________ psig
Refrigerant Discharge __________ psig
Suction Line Temp*__________
Discharge Line Temp†__________
Liquid Line Temp‡__________
___ Verify refrigerant charge using charging tables
___ Verify 3-phase scroll compressor is rotating in correct direction.
* Measured at suction inlet to compressor.
† Measured at discharge outlet from compressor.
‡ Measured at liquid line leaving condenser.
25