Carrier 50JZ024 Installation, Start-Up And Service Instructions Manual Download Page 22

Exposure, even if immediately cleaned up, may cause embrittle-
ment (leading to cracking) to occur in one year or more. When
performing any service that may risk exposure of compressor oil to
the roof, take appropriate precautions to protect roofing. Proce-
dures which risk oil leakage include, but are not limited to,
compressor replacement, repairing refrigerant leaks, replacing
refrigerant components such as filter drier, pressure switch, me-
tering device, coil, accumulator, or reversing valve.

SYNTHETIC ROOF PRECAUTIONARY PROCEDURE

1. Cover extended roof working area with an impermeable

polyethylene (plastic) drip cloth or tarp. Cover an approximate
10 x 10 ft. area.

2. Cover area in front of the unit service panel with a terry cloth

shop towel to absorb lubricant spills and prevent run-offs, and
protect drop cloth from tears caused by tools or components.

3. Place terry cloth shop towel inside unit immediately under

component(s) to be serviced and prevent lubricant run-offs
through the louvered openings in the base pan.

4. Perform required service.

5. Remove and dispose of any oil contaminated material per

local codes.

LIQUID LINE FILTER DRIER — The biflow filter drier is
specifically designed to operate with Puron. Use only factory-
authorized components. Filter drier must be replaced whenever the
refrigerant system is opened. When removing a filter drier, use a
tubing cutter to cut the drier from the system. Do not unsweat a
filter drier from the system. 
Heat from unsweating will release
moisture and contaminants from drier into system.

PURON (R-410A) REFRIGERANT CHARGING — Refer to unit
information plate and charging chart. Some R-410A refrigerant
cylinders contain a dip tube to allow liquid refrigerant to flow
from cylinder in upright position. 
For cylinders equipped with a
dip tube, charge Puron units with cylinder in upright position and
a commercial metering device in manifold hose. Charge refrigerant
into suction-line.

SYSTEM INFORMATION

TIME-DELAY RELAY — The Time-Delay Relay (TDR) is a
solid-state control, recycle delay timer which keeps indoor blower
operating for 60 sec on 030-060 sizes or 30 sec on 024 size after
thermostat is satisfied. This delay enables blower to remove
residual cooling in coil after compression shutdown, thereby
improving efficiency of system. The sequence of operation is that
on closure of wall thermostat and at end of a fixed on delay of 1
sec, fan relay is energized. When thermostat is satisfied, an off
delay is initiated. When fixed delay of 60

±

5 sec or 30

±

5 is

completed, fan relay is de-energized and fan motor stops. If wall
thermostat closes during this delay, TDR is reset and fan relay
remains energized. TDR is a 24v device that operates within a
range of 15v to 30v and draws about 0.5 amps. If the blower runs
continuously instead of cycling off when the fan switch is set on
AUTO, the TDR is probably defective and must be replaced.

LOSS OF CHARGE SWITCH — The loss of charge switch is a
protective device wired into control circuit (low voltage). It shuts
off the compressor if abnormally low pressures are present in the
refrigeration circuit.

NOTE:

Because these switches are attached to refrigeration

system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psi. Never open system
without breaking vacuum with dry nitrogen.

CHECK DEFROST THERMOSTAT — There is a liquid header
with a brass distributor and feeder tube going into outdoor coil. At
the end of 1 of the feeder tubes, there is a 3/8-in. OD stub tube
approximately 3 in. long (See Fig. 31). The defrost thermostat
should be located on stub tube. Note that there is only 1 stub tube
used with liquid header, and on most units it is the bottom circuit.

DEFROST THERMOSTATS — Defrost thermostat signals heat

pump that conditions are right for defrost or that conditions have
changed to terminate defrost. It is a thermally actuated switch
clamped to outdoor coil to sense its temperature. Normal tempera-
ture range is closed at 30˚ +/- 3˚F and open at 80˚ +/- 5˚F.

NOTE:

The defrost thermostat must be located on the liquid side

of the outdoor coil on the bottom circuit and as close to the coil as
possible.

Fig. 31—Defrost Thermostat

C99029

FEEDER TUBE

STUB TUBE

DEFROST
THERMOSTAT

22

Summary of Contents for 50JZ024

Page 1: ...cautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for unbrazin...

Page 2: ...house overhang is 48 in above the unit top The maximum horizontal extension of a partial over hang must not exceed 48 in IMPORTANT Do not restrict outdoor airflow An air restriction at either the out...

Page 3: ...ENTS 36 914 UNIT TOP 48 1219 SIDE OPPOSITE DUCTS 36 914 DUCT PANEL 12 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 IN 304 8 MM FROM WALL SYSTEM THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED...

Page 4: ...IL ACCESS SIDE 36 00 914 0 POWER ENTRY SIDE 36 00 914 0 EXCEPT FOR NEC REQUIREMENTS UNIT TOP 48 00 1219 0 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LES...

Page 5: ...S 1 Roof curb must be setup for unit being installed 2 Seal strip gasket must be applied as required 3 Dimensions are in inches 4 Attach ductwork to flanges of the curb 5 R A Return Air S A Supply Air...

Page 6: ...t duct connector or sheet metal sleeve must extend 24 in from electric heater element 1 Size ductwork for cooling air quantity cfm The minimum air quantity for proper electric heater operation is list...

Page 7: ...2 0 040 2 0 038 2 0 046 2 0 052 OUTDOOR COIL Rows Fins in Face Area sq ft 2 17 8 5 2 17 10 3 2 17 10 3 2 17 13 5 2 17 13 5 2 17 15 4 OUTDOOR FAN Nominal Airflow CFM Diameter Motor HP RPM 2350 22 1 8 8...

Page 8: ...orrection of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage contained within conduit when low voltage control wires are in same conduit as high voltage wires...

Page 9: ...Fig 12 Wiring Schematics 208 230 1 60 C00097 9...

Page 10: ...Fig 13 Wiring Schematics 208 230 3 60 C00098 10...

Page 11: ...Fig 14 Wiring Schematics 460 3 60 C00099 11...

Page 12: ...50 3 57 2 72 8 83 3 95 4 109 3 40 40 40 40 60 60 80 90 100 110 208 230 3 60 187 253 15 4 88 0 0 9 4 1 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 10 4 12 0 20 8 24 1 31 3 36 1 41 6 48 0 24 3 24 3 24 3 24 3 3...

Page 13: ...percent of voltage imbalance Voltage imbalance max voltage deviation from average voltage 100 x average voltage EXAMPLE Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 452 464 455 Average Voltag...

Page 14: ...leak is detected see following Check for Refrigerant Leaks section c Inspect all field and factory wiring connections Be sure that connections are completed and tight d Inspect coil fins If damaged d...

Page 15: ...h Accurater Metering Device Arrow indicates direction of flow Metering Position Bypass Position HPS Fig 21 Typical Heat Pump Operation Heating Mode 1 Hot gas from compressor flows through the 4 way va...

Page 16: ...and temperature sensing devices are required Connect the pressure gauge to the service port on the suction line Mount the tempera ture sensing device on the suction line and insulate it so that the ou...

Page 17: ...411 394 381 Cfm 1374 1290 1205 1116 1020 916 Med Watts 523 506 490 471 449 426 Cfm 1500 1408 1301 1190 1082 977 High Watts 645 628 610 595 584 575 Cfm 1474 1369 1267 1169 1069 962 42 Low Watts 660 639...

Page 18: ...TEMP F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 50JZ500066 Fig 24 Cooling Charging Chart 50JZ 030 Units C00083 030 60 Hz COOLING CHARGING CHART For Use with Units Using R410a Refrige...

Page 19: ...oling Charging Chart 50JZ 060 Units C00087 060 60 Hz COOLING CHARGING CHART For use with units using R410a Refrigerant 80 90 100 110 120 130 140 150 160 170 180 20 30 40 50 60 70 80 SUCTION LINETEMPER...

Page 20: ...COIL INDOOR COIL AND CONDENSATE DRAIN PAN Inspect the outdoor coil indoor coil and conden sate drain pan at least once each year The coils are easily cleaned when dry therefore inspect and clean the...

Page 21: ...at 610 psig High pressure may be caused by a dirty outdoor coil failed fan motor or outdoor air recirculation To check switch 1 Turn off all power to unit 2 Disconnect leads on switch 3 Apply ohmeter...

Page 22: ...or 60 sec on 030 060 sizes or 30 sec on 024 size after thermostat is satisfied This delay enables blower to remove residual cooling in coil after compression shutdown thereby improving efficiency of s...

Page 23: ...es with 750 psig service pressure rating Leak detectors should be designed to detect HFC refrigerant Puron as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture fro...

Page 24: ...ities shown on nameplate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start cap...

Page 25: ...IST REMOVE AND STORE IN JOB FILE I PRELIMINARY INFORMATION Model No Serial No Date Technician II PRE START UP ___ Verify that all packing materials have been removed from unit ___ Remove all shipping...

Page 26: ...26...

Page 27: ...27...

Page 28: ...46231 50jz 1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 565...

Reviews: