Table 4C — Physical Data — 38HDS Condensing Units

UNIT 38HDS

024

048

NOMINAL CAPACITY (Tons)

2

4

OPERATING WEIGHT (lb)

159

292

REFRIGERANT TYPE

R-22

Control (Cooling)

TXV in Condensing Unit

Factory Charge (lb)*

Circuit A

5.0

5.5

Circuit B

5.5

COMPRESSOR TYPE

Copeland

Scroll

Quantity...Model

1...ZR23K1

2...ZR49K3

Oil (Recharge) (oz)

25

53

OUTDOOR FAN

Propeller, Direct Drive

Rpm

850

850

Diameter (in.)...No. of Blades

18...3

24...3

Pitch (Degrees)

27

24

Motor Hp

1

8

1

4

Nominal Air Cfm

1720

3900

OUTDOOR COIL

Copper Tube, Aluminum Fin

Face Area (sq ft)...No. of Rows

6.1...2

12.3...2

Fins/in.

15

15

CONTROLS

High-Pressure (psig)

Cut-in

320 ± 20

Cutout

426 ± 7

Low-Pressure (psig)

Cut-in

22 ± 5

Cutout

7 ± 3

Fusible Plug

210 F

Control Voltage

24

REFRIGERANT LINES

Connection Type

Sweat

Vapor Supply Line Quantity...OD (in.)

2...

3

8

4...

3

8

Vapor Return Line Quantity...OD (in.)

2...

5

8

4...

5

8

Maximum Length (ft)

50

50

Maximum Lift Fan Coil (Above Outdoor) (ft)

30†

30†

Maximum Lift Fan Coil (Below Outdoor) (ft)

30†

30†

EXTERNAL FINISH

Alpine Mist (Beige)

LEGEND

TXV — Thermostatic Expansion Valve

*Charge is based on 25 ft of interconnecting line.

†Maximum system lift is 30 ft between lowest system component and highest system component.

Table 4D — Physical Data — 40QNB High Wall Fan Coil Units

UNIT 40QNB

018*

024*

NOMINAL CAPACITY (Tons)

1

1

2

2

NOMINAL SIZE (Btuh)

18,000

24,000

OPERATING WEIGHT (lb)

38.5

42.9

MOISTURE REMOVAL RATE (Pints/Hr)

5.6

6.3

FINISH

White

REFRIGERANT

R-22

Control (Cooling)

AccuRater

T

Metering Device

System Charge Required (lb)†

4.6

5.3

INDOOR FAN

Direct Drive Centrifugal

Rpm...Cfm High

1120...550

1470...570

Rpm...Cfm Medium

1050...500

1370...466

Rpm...Cfm Low

950...450

1270...417

Motor Watts

44

49

Blowers — No. ...Size (in.)

2...3.94 x 17.8

2...3.94 x 17.8

INDOOR COIL

Copper Tube, Aluminum Fin

Face Area (sq ft)

2.56

2.56

No. of Rows

2

3

Fins/in.

15.9

18.1

Circuits

2

3

FILTERS

Cleanable

(Quantity) Size (in.)

(3) 11

1

2

x 17

3

4

AIRSWEEP

Horizontal

Manual

Vertical

Automatic

CONTROLS

Integrated Microprocessor

Remote Controller

Wireless

Freeze Protection

Yes

Auto. Restart

Yes

Diagnostics

Yes

Timer Mode

24-Hour Startup/Shutdown Type

Test Mode

Yes

Dehumidification Mode

Yes

Fan Mode

High/Medium/Low/Auto.

Control Voltage

24 v

REFRIGERANT LINES

Connection Type

Male Flare

Liquid Line OD (in.)

3

8

3

8

Vapor Line OD (in.)

5

8

5

8

CONDENSATE DRAIN CONNECTION (in.)

5

8

OD,

7

16

ID

*Units may only be matched with 38HDC, 38HDL and 38HDS outdoor units.

†Full factory charge shipped in outdoor unit. Charge shown is for smallest system combination and is determined based on 25 ft of line.

8

Summary of Contents for 40QNB018

Page 1: ...Pump Systems Only TROUBLESHOOTING 20 26 START UP CHECKLIST CL 1 CL 2 SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical co...

Page 2: ...rews taped to the mounting bracket INSPECT SHIPMENT Upon receipt of shipment check unit Fig 1 for damage Forward claim papers directly to the transportation company Manufacturer is not responsible for...

Page 3: ...C HDL and BK applications A thermostatic expansion valve is used in the outdoor unit on 38HDS applications Insulate both refrigerant lines on 38HDS and BK applications 5 The 49 top and left side clear...

Page 4: ...For Remote Mounting Bracket 2 35 ft Long High Voltage Power Wiring 2 wire with ground 1 35 ft Long Low Voltage Thermistor Wiring 3 wire 1 AccuRaterT Body And Piston 018 and 024 Cooling Only Units 1 Bi...

Page 5: ...Tables 4A 4F for the correct size piping The length of refrigerant pipe de pends on the unit placement and building structure run pipes as directly as possible For piping requirements over 50 ft of to...

Page 6: ...nit Fig 10 Make sure Teflon seal on the piston faces toward the outdoor unit Use Table 5 to verify the correct piston for your sys tem has been shipped with the unit Refer to 38BK installation instruc...

Page 7: ...e OD in 3 8 3 8 Vapor Line OD in 5 8 5 8 Maximum Length ft 200 200 Maximum Lift Fan Coil Above Outdoor ft 65 65 Maximum Lift Fan Coil Below Outdoor ft 150 150 24 v and a minimum of 40 va is provided i...

Page 8: ...est system component Table 4D Physical Data 40QNB High Wall Fan Coil Units UNIT 40QNB 018 024 NOMINAL CAPACITY Tons 11 2 2 NOMINAL SIZE Btuh 18 000 24 000 OPERATING WEIGHT lb 38 5 42 9 MOISTURE REMOVA...

Page 9: ...Tube Aluminum Fin Face Area sq ft No of Coils 6 1 1 5 6 1 2 Fins in 15 15 CONTROLS High Pressure psig Cutout 320 20 Cut in 426 7 Liquid Line Low Pressure psig Cutout 7 3 Cut in 22 5 Fusible Plug 210...

Page 10: ...8 INDOOR COIL Copper Tube Aluminum Fin Face Area sq ft 2 56 2 56 No of Rows 2 3 Fins in 15 9 18 1 Circuits 2 3 FILTERS Cleanable Quantity Size in 2 111 2 x 173 4 AIRSWEEP Horizontal Manual Vertical Au...

Page 11: ...ethane or neoprene Table 5 Required Piston Sizes for AccuRater Metering Device OUTDOOR UNIT 38 INDOOR UNIT 40QN INDOOR PISTON INDOOR PISTON TYPE OUTDOOR PISTON OUTDOOR PISTON TYPE REQUIRED SYSTEM CHAR...

Page 12: ...esting only and cannot be used for power connections 4 Route the factory supplied ground and power wires from terminal block 1 TB1 to the field supplied disconnect switch According to NEC and most loc...

Page 13: ...res of 18 gage AWG American Wire Gage thermostat cable between the low voltage terminal block of the fan coil unit TB2 and the 38BK unit low voltage terminal block Connect the wires between terminals...

Page 14: ...m operation to the owner 40QN Control System The 40QN unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit with ther...

Page 15: ...Mode If auto mode is selected the system automatically switches the operating mode from heating heat pump system only to cooling or from cooling to heating heat pump system only depending on the sele...

Page 16: ...he indoor fan runs at ultra low speed for 30 seconds The normal dehumidification operation is re peated for the newly sensed room temperature 3 When the room temperature is equal to or greater than 4...

Page 17: ...up and down NOTE The unit cannot be controlled by the remote con troller until the slide switch is returned to the REMOTE position Emergency Mode This mode is only to be used if the remote controller...

Page 18: ...s in accordance with the markings on the remote controller so that the poles are correct and RST 3 Press the button using an instrument screwdriver or similar small pointed tool 4 Replace the cover se...

Page 19: ...ntil filter snaps in place If the filter has begun to break down or is torn it needs to be replaced Replacement filters are available through your Carrier distributor To Clean Indoor Unit Front Panel...

Page 20: ...oltage across the two ther mistor connections Approximate temperature is indicated in Table 10 Table 9 System Fault Codes NO OF QUICK LED FLASHES SYSTEM FAULT 2 Room Air Thermistor 3 Indoor Coil Therm...

Page 21: ...39 0 42 0 45 190 890 982 1 078 0 33 0 36 0 39 200 748 828 913 0 28 0 31 0 33 210 631 701 766 0 24 0 26 0 28 212 611 678 751 0 23 0 25 0 28 Circuit volts 5 vdc Table 11 Troubleshooting PROBLEM POTENTI...

Page 22: ...stem Design Manual 2 All wiring must comply with the applicable local and national codes 3 Liquid line need not be insulated 4 Wiring and piping shown are general points of connection guides only and...

Page 23: ...stor RA Th Return Air Thermistor RC Resistor Capacitor RCV Receiver RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay ST Start Thermistor STM Step Motor TB Terminal Block TG Time Guard TP...

Page 24: ...40QNH018 024 FAN COIL 38BK018 024 OUTDOOR SECTION Fig 26 40QNH Fan Coil Unit with 38BK Outdoor Heat Pump Unit 24...

Page 25: ...40QNB018 024 FAN COIL 38HDC018 024 OUTDOOR SECTION 38HDC018 ONLY Fig 27 40QNB Fan Coil Unit with 38HDC Cooling Only Outdoor Condensing Unit 25...

Page 26: ...door Condensing Unit Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations...

Page 27: ...ECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT IS THE LOW VOLTAGE CABLE INDOOR TO OUTDOO...

Page 28: ...AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG DISCHARGE PRESSURE PSIG CUT...