background image

• Cooling Mode — When the Cooling mode is selected, the

indoor fan will operate continuously at the selected speed
if the speed is high, medium, or low. If the indoor fan is
in Auto. mode, the fan will change operating speeds de-
pending on the difference between the room temperature
and the set point. The reversing valve (QNH only) will be
energized. The compressor cannot run for 3 minutes from
the time the system starts up or for 3 minutes from the
time the compressor last operated. When the temperature
of the room is equal to or greater than the selected tem-
perature, the compressor and outdoor fan will operate un-
til the room temperature is 2° F below the set point, and
then shut off. When the room temperature is less than the
selected temperature, the compressor and outdoor fan re-
main off.

• Maximum Dehumidification Mode — When the Dehu-

midification mode is selected, the indoor fan will operate
continuously at the selected speed if the speed is high, me-
dium, or low. If the indoor fan is in Auto. mode, the fan
will change operating speeds depending on the room tem-
perature. If the room temperature is below the set point,
the indoor fan will run at ultra-low speed, and the com-
pressor could run for up to 4 minutes. (Ultra-low speed is
a control-driven speed [not user configurable] used to sample
the space when the fan would normally be off.) The re-
versing valve (QNH only) will be energized. The com-
pressor cannot run for 3 minutes from the time the system
starts up or for 3 minutes from the time the compressor
last operated.

Initial Operation — When the mode is first selected, one of
the following occurs:
1. If the room temperature is above or equal to the selected

temperature, the unit will operate for 16 minutes, and the
compressor and outdoor fan will operate. The indoor fan
will operate as in the Cooling mode. After 16 minutes of
operation (or when the room reaches 2° F below set point),
the unit switches to normal dehumidification operation.

2. If the room temperature is below the selected tempera-

ture, the unit will operate for 8 minutes as follows: the
compressor and outdoor fan will operate for 3 minutes.
The indoor fan will operate in low speed, and 30 seconds
after the compressor stops, the indoor fan stops. The unit
remains off for 1 minute, and then the indoor fan starts in
ultra-low speed for 30 seconds. The unit then switches to
normal dehumidification operation.

Normal Operation — One of the following will take place:
1. When the temperature of the room is equal to or greater

than the selected temperature (by not more than 3° F), the
unit will operate for 8 minutes as follows: the compres-
sor and outdoor fan will operate for 3 minutes. The in-
door fan will operate in low speed, and 30 seconds after
the compressor stops, the indoor fan stops. The unit re-
mains off for 1 minute, and then the indoor fan starts in
ultra-low speed for 30 seconds. The normal dehumidifi-
cation operation is repeated for the newly sensed room
temperature.

2. If the room temperature is equal to or greater than the

selected temperature, but not by more than between 4° F
and 6° F, the compressor and outdoor fan operate for
4 minutes. The indoor fan will run at ultra-low speed and
will stop 30 seconds after the compressor stops. After
3 minutes, the indoor fan runs at ultra-low speed for
30 seconds. The normal dehumidification operation is re-
peated for the newly sensed room temperature.

3. When the room temperature is equal to or greater than

4° F below the selected temperature, the system operates
as follows: The compressor and outdoor fan operate for
3 minutes. The indoor fan will operate at ultra-low speed
and will stop 30 seconds after the compressor stops. Af-
ter 4 or 5 minutes, the indoor fan starts in ultra-low speed
for 30 seconds. The normal dehumidification operation is
repeated for the newly sensed room temperature. If the
room temperature is still 4° F below the selected tem-
perature, the compressor, outdoor fan, and indoor fan re-
main off. After 7

1

2

minutes, the indoor fan operates at

ultra-low speed for 30 seconds. The normal dehumidifi-
cation operation is repeated for the newly sensed room
temperature.

• Heat Pump Heating Mode (Heat Pump Systems Only) —

When the Heat Pump mode is selected, the indoor fan will
operate at the selected speed if the speed is high, medium,
or low, unless overridden by the coil temperature (to pre-
vent cold drafts). If the indoor fan is in Auto. mode, the
fan will change operating speeds depending on the differ-
ence between the room temperature, the set point, and the
coil temperature. The reversing valve will be deenergized.
The compressor cannot run for 3 minutes from the time
the system starts up or for 3 minutes from the time it last
operated. When the temperature of the room is 8° F below
the selected temperature, the unit will operate in Heat Pump
mode until the temperature is 6° F above the selected tem-
perature, or the compressor runs for 40 minutes (which-
ever comes first). If the temperature of the room is less
than 7° F below or equal to the selected temperature, the
unit operates in Heat Pump mode until the selected set point
temperature plus 2° F is reached.

• Electric Heat in Heat Pump Heating Mode — Supplemen-

tal electric heat is enabled when the outside air thermistor
located in the outdoor unit is below 40 F and the room
temperature thermistor is equal to or less than 5.4 F below
set point. Electric heat will remain on until 1.8° F above
set point, then will turn off. Fan operation will be the same
as described previously in the heat pump heating mode.
NOTE: Electric heat control cannot be overridden.

• Demand Defrost Mode (Heat Pump Systems Only) — This

unit uses a demand defrost system to remove frost from
the outdoor coil during heating operation. The indoor and
outdoor fans are shut off during Defrost mode. See
Fig. 20. For high wall heat pump units, the electric heat is
OFF during Defrost mode.

• Sleep Mode — The Sleep mode timer turns the unit off

when the timer reaches zero minutes. The durations that
can be selected are 1, 2, 3 or 7 hours. After the initial
30 minutes, the user set point shifts approximately 1° F
warmer. This sequence repeats itself every 40 minutes up
to a total of 150 minutes. When Sleep mode is enabled,
the display on the remote controller is dimmed.

• On/Off Timer Mode — The on/off timer will turn the unit

on or off at a user selectable on and off time (this is one
time event only). The unit will start in the same mode and
at the same selected temperature as when the system shut
off. If the room temperature is not within approximately
5° F of the set point 40 minutes before start-up, the unit
runs before the user selected on time is reached to achieve
the set point temperature at start-up.

16

Summary of Contents for 40QNB018

Page 1: ...Pump Systems Only TROUBLESHOOTING 20 26 START UP CHECKLIST CL 1 CL 2 SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical co...

Page 2: ...rews taped to the mounting bracket INSPECT SHIPMENT Upon receipt of shipment check unit Fig 1 for damage Forward claim papers directly to the transportation company Manufacturer is not responsible for...

Page 3: ...C HDL and BK applications A thermostatic expansion valve is used in the outdoor unit on 38HDS applications Insulate both refrigerant lines on 38HDS and BK applications 5 The 49 top and left side clear...

Page 4: ...For Remote Mounting Bracket 2 35 ft Long High Voltage Power Wiring 2 wire with ground 1 35 ft Long Low Voltage Thermistor Wiring 3 wire 1 AccuRaterT Body And Piston 018 and 024 Cooling Only Units 1 Bi...

Page 5: ...Tables 4A 4F for the correct size piping The length of refrigerant pipe de pends on the unit placement and building structure run pipes as directly as possible For piping requirements over 50 ft of to...

Page 6: ...nit Fig 10 Make sure Teflon seal on the piston faces toward the outdoor unit Use Table 5 to verify the correct piston for your sys tem has been shipped with the unit Refer to 38BK installation instruc...

Page 7: ...e OD in 3 8 3 8 Vapor Line OD in 5 8 5 8 Maximum Length ft 200 200 Maximum Lift Fan Coil Above Outdoor ft 65 65 Maximum Lift Fan Coil Below Outdoor ft 150 150 24 v and a minimum of 40 va is provided i...

Page 8: ...est system component Table 4D Physical Data 40QNB High Wall Fan Coil Units UNIT 40QNB 018 024 NOMINAL CAPACITY Tons 11 2 2 NOMINAL SIZE Btuh 18 000 24 000 OPERATING WEIGHT lb 38 5 42 9 MOISTURE REMOVA...

Page 9: ...Tube Aluminum Fin Face Area sq ft No of Coils 6 1 1 5 6 1 2 Fins in 15 15 CONTROLS High Pressure psig Cutout 320 20 Cut in 426 7 Liquid Line Low Pressure psig Cutout 7 3 Cut in 22 5 Fusible Plug 210...

Page 10: ...8 INDOOR COIL Copper Tube Aluminum Fin Face Area sq ft 2 56 2 56 No of Rows 2 3 Fins in 15 9 18 1 Circuits 2 3 FILTERS Cleanable Quantity Size in 2 111 2 x 173 4 AIRSWEEP Horizontal Manual Vertical Au...

Page 11: ...ethane or neoprene Table 5 Required Piston Sizes for AccuRater Metering Device OUTDOOR UNIT 38 INDOOR UNIT 40QN INDOOR PISTON INDOOR PISTON TYPE OUTDOOR PISTON OUTDOOR PISTON TYPE REQUIRED SYSTEM CHAR...

Page 12: ...esting only and cannot be used for power connections 4 Route the factory supplied ground and power wires from terminal block 1 TB1 to the field supplied disconnect switch According to NEC and most loc...

Page 13: ...res of 18 gage AWG American Wire Gage thermostat cable between the low voltage terminal block of the fan coil unit TB2 and the 38BK unit low voltage terminal block Connect the wires between terminals...

Page 14: ...m operation to the owner 40QN Control System The 40QN unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit with ther...

Page 15: ...Mode If auto mode is selected the system automatically switches the operating mode from heating heat pump system only to cooling or from cooling to heating heat pump system only depending on the sele...

Page 16: ...he indoor fan runs at ultra low speed for 30 seconds The normal dehumidification operation is re peated for the newly sensed room temperature 3 When the room temperature is equal to or greater than 4...

Page 17: ...up and down NOTE The unit cannot be controlled by the remote con troller until the slide switch is returned to the REMOTE position Emergency Mode This mode is only to be used if the remote controller...

Page 18: ...s in accordance with the markings on the remote controller so that the poles are correct and RST 3 Press the button using an instrument screwdriver or similar small pointed tool 4 Replace the cover se...

Page 19: ...ntil filter snaps in place If the filter has begun to break down or is torn it needs to be replaced Replacement filters are available through your Carrier distributor To Clean Indoor Unit Front Panel...

Page 20: ...oltage across the two ther mistor connections Approximate temperature is indicated in Table 10 Table 9 System Fault Codes NO OF QUICK LED FLASHES SYSTEM FAULT 2 Room Air Thermistor 3 Indoor Coil Therm...

Page 21: ...39 0 42 0 45 190 890 982 1 078 0 33 0 36 0 39 200 748 828 913 0 28 0 31 0 33 210 631 701 766 0 24 0 26 0 28 212 611 678 751 0 23 0 25 0 28 Circuit volts 5 vdc Table 11 Troubleshooting PROBLEM POTENTI...

Page 22: ...stem Design Manual 2 All wiring must comply with the applicable local and national codes 3 Liquid line need not be insulated 4 Wiring and piping shown are general points of connection guides only and...

Page 23: ...stor RA Th Return Air Thermistor RC Resistor Capacitor RCV Receiver RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay ST Start Thermistor STM Step Motor TB Terminal Block TG Time Guard TP...

Page 24: ...40QNH018 024 FAN COIL 38BK018 024 OUTDOOR SECTION Fig 26 40QNH Fan Coil Unit with 38BK Outdoor Heat Pump Unit 24...

Page 25: ...40QNB018 024 FAN COIL 38HDC018 024 OUTDOOR SECTION 38HDC018 ONLY Fig 27 40QNB Fan Coil Unit with 38HDC Cooling Only Outdoor Condensing Unit 25...

Page 26: ...door Condensing Unit Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations...

Page 27: ...ECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT IS THE LOW VOLTAGE CABLE INDOOR TO OUTDOO...

Page 28: ...AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG DISCHARGE PRESSURE PSIG CUT...

Reviews: