background image

Table 1 — System Combinations for Indoor

and Outdoor Units

SYSTEM

INDOOR UNIT

OUTDOOR UNIT

High Wall

Cooling

Only

40QNB018

38HDC,L018

40QNB024

38HDC,L024

(2) 40QNB018

38HDS024*

(4) 40QNB018

38HDS048*

40QNB024, (2) 40QNB018

38HDS048*

(2) 40QNB024

38HDS048*

High Wall

Heat Pump

40QNH018

38BK018

40QNH024

38BK024

*Multi-split systems can accommodate up to 4 fan coil units of vari-

ous types with one condensing unit. The combinations listed in
this table are those which use only high-wall units (not in combina-
tion with any other type of fan coil unit). Refer to system presale
literature or Price Pages for more details.

NOTE: Numbers in ( ) indicate quantities of more than 1. See Fig. 1
for 40QN high wall fan coil unit.

INSTALLATION

The 40QNB high wall fan coil unit is installed with either

the 38HDC,HDL condensing or 38HDS multi-split condens-
ing outdoor unit, and the 40QNH unit is installed with the
38BK heat pump outdoor unit. Refer to Table 1 to make sure
the correct indoor unit(s) is installed with the correct out-
door unit.

Installation instructions for the 40QN fan coil units are

contained in this manual. Refer to this manual for proper
installation of the complete system. Note that the 38HDC,
HDL, and BK outdoor units are shipped with installation and
service instructions for basic installation of the outdoor sec-
tion. Be sure to make the modifications in Make Connec-
tions to Outdoor Unit section on page 13 of this literature,
so that the outdoor unit will operate properly with the 40QN
control system. Be sure the unit will be operated within the
application guidelines shown in Table 2. When installing the
38HDC, HDL, HDS, or BK unit, note that for cooling op-
eration below 55 F (38HDC, HDL, BK), it is necessary to
equip the outdoor unit with the low ambient control acces-
sory. The low ambient control is standard on 38HDS units.

To install this system, you will need:

• 40QNB or QNH fan coil unit(s)* with standard wireless

remote controller

• 38HDC, HDL, HDS, or BK outdoor unit
• low-ambient (38HDC, HDL, BK) or winter start (38HDS)

kit (if required for your application)

* More than one fan coil unit may be used with the 38HDS

multi-split units. Refer to 38HDS system Price Pages for
full details.

NOTE: Refrigerant pipe, drain pipe, wire, etc., are also re-
quired to install unit and are field supplied.

Be sure you have the required parts before beginning in-

stallation. The 40QN unit utilizes a microprocessor control
system to deliver optimum levels of comfort and efficiency.
Be sure to follow these instructions carefully to obtain proper
functioning of the unit.

Step 1 — Complete Pre-Installation Checks

UNPACK UNIT — Store unit in the original packaging
until it is moved to the final site for installation. When re-
moving unit from carton, lift by its 4 corners. Also, note that
there is a plastic bag containing mounting screws taped to
the mounting bracket.

INSPECT SHIPMENT — Upon receipt of shipment check
unit (Fig. 1) for damage. Forward claim papers directly to
the transportation company. Manufacturer is not responsible
for damage incurred in transit.

Table 2 — Application Ranges

COOLING MODE

Maximum

Minimum

Indoor

Unit

Outdoor

Unit

Indoor

Unit

Outdoor

Unit

95 F DB

115 F DB

67 F DB

55 F DB*

71 F WB

57 F WB

0° F DB†

HEATING MODE (38BK Systems Only)

Maximum

Minimum

Indoor

Unit

Outdoor

Unit

Indoor

Unit

Outdoor

Unit

80 F DB

75 F DB

55 F DB

0° F DB

71 F WB

65 F WB

LEGEND

DB

— Dry Bulb

WB — Wet Bulb
*38HDC, HDL and BK systems only.
†38HDS systems only.

NOTE: Unit may be equipped with a low-ambient control (HDC, HDL,
BK) or winter start kit (HDS) that will allow operation down to −20 F.

Check all items. See Table 3. If any item is missing notify

your Carrier distributor. To prevent loss or damage, leave all
parts in original packages until installation.

Step 2 — Select Location —

Consult local building

codes and NEC for special installation requirements.

There are several ways the unit may be installed to dif-

ferent types of wall construction. These instructions do not
cover all installation methods. As a typical installation, these
instructions focus primarily on mounting the unit to wall studs
in new construction. See Fig. 2 for unit dimensions and
Fig. 3 for required clearances. Plan your installation care-
fully before you begin. Listed below are some guidelines that
should be followed when determining location for the unit.
1. Center unit (horizontally) on the wall selected.
2. Place the unit so it faces normal location of room

occupants.

3. Allow sufficient space for airflow clearance, wiring, re-

frigerant piping, and servicing unit. See Fig. 2 and 3.

4. Select walls that are:

a. Strong enough to support weight of the unit.
b. Accessible to convenient condensate drainage.
c. Free of obstacles that may block air circulation to the

fan coils.

d. Outside walls (if possible) to make piping easier.

5. Place top of fan coil unit as high on the wall as possible

making sure the unit is at least 10 in. down from ceiling
to permit proper air intake. Also, make sure that the unit
is not placed directly over anything to prevent filter re-
moval or block airflow.

6. Make sure units are easily accessible to electrical power.
7. Refrigerant piping can enter the unit through the prepunched

holes. Refrigerant piping can run up or down along the
wall, to the right or left along the wall, straight through
the wall, or into the wall (Fig. 4). Once the piping is through
the wall, it can run inside walls, in ceilings, between floors,
or straight to the outside. See Fig. 5 for maximum line
lengths.

NOTE: Run refrigerant piping as directly as possible, and
avoid any unnecessary turns or bends.

8. Condensate piping can be directed through the inside wall

to an approved drain, or directed straight outside.

NOTE: The piping hole for condensate line must be made
at a downward slope to ensure proper drainage. See Mount
Mounting Bracket on Wall Section on page 5 for details.

2

Summary of Contents for 40QNB018

Page 1: ...Pump Systems Only TROUBLESHOOTING 20 26 START UP CHECKLIST CL 1 CL 2 SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical co...

Page 2: ...rews taped to the mounting bracket INSPECT SHIPMENT Upon receipt of shipment check unit Fig 1 for damage Forward claim papers directly to the transportation company Manufacturer is not responsible for...

Page 3: ...C HDL and BK applications A thermostatic expansion valve is used in the outdoor unit on 38HDS applications Insulate both refrigerant lines on 38HDS and BK applications 5 The 49 top and left side clear...

Page 4: ...For Remote Mounting Bracket 2 35 ft Long High Voltage Power Wiring 2 wire with ground 1 35 ft Long Low Voltage Thermistor Wiring 3 wire 1 AccuRaterT Body And Piston 018 and 024 Cooling Only Units 1 Bi...

Page 5: ...Tables 4A 4F for the correct size piping The length of refrigerant pipe de pends on the unit placement and building structure run pipes as directly as possible For piping requirements over 50 ft of to...

Page 6: ...nit Fig 10 Make sure Teflon seal on the piston faces toward the outdoor unit Use Table 5 to verify the correct piston for your sys tem has been shipped with the unit Refer to 38BK installation instruc...

Page 7: ...e OD in 3 8 3 8 Vapor Line OD in 5 8 5 8 Maximum Length ft 200 200 Maximum Lift Fan Coil Above Outdoor ft 65 65 Maximum Lift Fan Coil Below Outdoor ft 150 150 24 v and a minimum of 40 va is provided i...

Page 8: ...est system component Table 4D Physical Data 40QNB High Wall Fan Coil Units UNIT 40QNB 018 024 NOMINAL CAPACITY Tons 11 2 2 NOMINAL SIZE Btuh 18 000 24 000 OPERATING WEIGHT lb 38 5 42 9 MOISTURE REMOVA...

Page 9: ...Tube Aluminum Fin Face Area sq ft No of Coils 6 1 1 5 6 1 2 Fins in 15 15 CONTROLS High Pressure psig Cutout 320 20 Cut in 426 7 Liquid Line Low Pressure psig Cutout 7 3 Cut in 22 5 Fusible Plug 210...

Page 10: ...8 INDOOR COIL Copper Tube Aluminum Fin Face Area sq ft 2 56 2 56 No of Rows 2 3 Fins in 15 9 18 1 Circuits 2 3 FILTERS Cleanable Quantity Size in 2 111 2 x 173 4 AIRSWEEP Horizontal Manual Vertical Au...

Page 11: ...ethane or neoprene Table 5 Required Piston Sizes for AccuRater Metering Device OUTDOOR UNIT 38 INDOOR UNIT 40QN INDOOR PISTON INDOOR PISTON TYPE OUTDOOR PISTON OUTDOOR PISTON TYPE REQUIRED SYSTEM CHAR...

Page 12: ...esting only and cannot be used for power connections 4 Route the factory supplied ground and power wires from terminal block 1 TB1 to the field supplied disconnect switch According to NEC and most loc...

Page 13: ...res of 18 gage AWG American Wire Gage thermostat cable between the low voltage terminal block of the fan coil unit TB2 and the 38BK unit low voltage terminal block Connect the wires between terminals...

Page 14: ...m operation to the owner 40QN Control System The 40QN unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit with ther...

Page 15: ...Mode If auto mode is selected the system automatically switches the operating mode from heating heat pump system only to cooling or from cooling to heating heat pump system only depending on the sele...

Page 16: ...he indoor fan runs at ultra low speed for 30 seconds The normal dehumidification operation is re peated for the newly sensed room temperature 3 When the room temperature is equal to or greater than 4...

Page 17: ...up and down NOTE The unit cannot be controlled by the remote con troller until the slide switch is returned to the REMOTE position Emergency Mode This mode is only to be used if the remote controller...

Page 18: ...s in accordance with the markings on the remote controller so that the poles are correct and RST 3 Press the button using an instrument screwdriver or similar small pointed tool 4 Replace the cover se...

Page 19: ...ntil filter snaps in place If the filter has begun to break down or is torn it needs to be replaced Replacement filters are available through your Carrier distributor To Clean Indoor Unit Front Panel...

Page 20: ...oltage across the two ther mistor connections Approximate temperature is indicated in Table 10 Table 9 System Fault Codes NO OF QUICK LED FLASHES SYSTEM FAULT 2 Room Air Thermistor 3 Indoor Coil Therm...

Page 21: ...39 0 42 0 45 190 890 982 1 078 0 33 0 36 0 39 200 748 828 913 0 28 0 31 0 33 210 631 701 766 0 24 0 26 0 28 212 611 678 751 0 23 0 25 0 28 Circuit volts 5 vdc Table 11 Troubleshooting PROBLEM POTENTI...

Page 22: ...stem Design Manual 2 All wiring must comply with the applicable local and national codes 3 Liquid line need not be insulated 4 Wiring and piping shown are general points of connection guides only and...

Page 23: ...stor RA Th Return Air Thermistor RC Resistor Capacitor RCV Receiver RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay ST Start Thermistor STM Step Motor TB Terminal Block TG Time Guard TP...

Page 24: ...40QNH018 024 FAN COIL 38BK018 024 OUTDOOR SECTION Fig 26 40QNH Fan Coil Unit with 38BK Outdoor Heat Pump Unit 24...

Page 25: ...40QNB018 024 FAN COIL 38HDC018 024 OUTDOOR SECTION 38HDC018 ONLY Fig 27 40QNB Fan Coil Unit with 38HDC Cooling Only Outdoor Condensing Unit 25...

Page 26: ...door Condensing Unit Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations...

Page 27: ...ECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT IS THE LOW VOLTAGE CABLE INDOOR TO OUTDOO...

Page 28: ...AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG DISCHARGE PRESSURE PSIG CUT...

Reviews: