background image

START-UP

Complete the following checks and the Start-Up Check-

list on page CL-1 before system start-up. Refer to outdoor
unit installation, start-up and service instructions for system
start-up procedures and refrigerant charging methods.

1. Check condensate drainage system.

Add water to check the drainage flow. If water does not
flow regularly, check the pipe slope or see if there are
any pipe restrictions.

2. Make sure that all wiring connections are correct and

tight.

3. Make sure that all barriers, covers, and panels are in place.
4. Ensure that the filters have been installed and that the

discharge louvers are correctly positioned.

Never operate unit without a filter. Damage to the
unit or personal injury may result.

5. If the unit is equipped with a crankcase heater, energize

a minimum of 24 hours before starting the unit. To en-
ergize crankcase heater only, close indoor unit discon-
nect, then with the remote controller, set unit in off mode
and close the outdoor unit disconnect.

6. Fully backseat (open) the liquid and vapor tube service

valves.

7. Unit is shipped with valve stems frontseated and caps

factory installed. Replace stem caps after system is opened
to refrigerant flow (backseated). Replace caps finger tight.

8. With the remote controller, turn on the unit and operate

in each mode (as applicable) for 15 minutes to test for
proper operation. Do not operate in cooling mode if out-
door temperature is below 55 F (HDC, HDL, BK) or
0° F (HDS) unless unit is equipped with low ambient
control (HDC, HDL, BK) or winter start kit (HDS). Do
not operate in heating mode (heat pump systems only)
if the outdoor temperature is above 75 F.

9. Test for proper refrigerant charge using the superheat

method (HDC, HDL, BK) or subcooling method (HDS).

10. Explain basic system operation to the owner.

40QN Control System —

The 40QN unit is equipped

with a microprocessor control which operates the system.
This control is located in the control box of the fan coil unit,
with thermistors located in the fan coil inlet and on the

indoor coil. The 40QNH heat pump fan coil units also have
thermistors located on the outdoor coil and in the outdoor air
inlet. These thermistors monitor system operation and con-
trol the operating mode. To change settings or modes of op-
eration, use the factory-supplied infrared wireless remote
controller. This controller allows the fan coil unit to be op-
erated from within the same room without any wire connec-
tions to the unit.

WIRELESS REMOTE CONTROLLERS — A wireless re-
mote controller is supplied for system operation of all high
wall units. Each battery-operated wireless (infrared) remote
controller may be used to control more than one unit. The
wireless remote controller has a maximum range of 20 feet.
The fan coil unit is equipped with an emergency switch which
allows operation if the remote controller malfunctions or is
misplaced. Because the controller uses infrared communi-
cation, all of the following must be true for the controller to
work properly:
1. The power must be on to the fan coil unit.
2. The batteries in the controller must be good.
3. The controller must be within range of and pointed di-

rectly at the fan coil unit.

4. The fan coil unit’s 3-position switch must be set in the

remote position.

The remote controller includes a wall-mounted bracket.

To install the bracket, attach bracket to the wall as shown in
Fig. 17 using, double-sided tape included in remote control-
ler assembly. Install factory-supplied batteries into the re-
mote controller per To Install or Replace Remote Controller
Batteries section on page 18, and place the controller into
the bracket so that it will be ready for use.

Fig. 16 — Mounting Unit to Bracket

Fig. 17 — Mounting Remote Controller Bracket

14

Summary of Contents for 40QNB018

Page 1: ...Pump Systems Only TROUBLESHOOTING 20 26 START UP CHECKLIST CL 1 CL 2 SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical co...

Page 2: ...rews taped to the mounting bracket INSPECT SHIPMENT Upon receipt of shipment check unit Fig 1 for damage Forward claim papers directly to the transportation company Manufacturer is not responsible for...

Page 3: ...C HDL and BK applications A thermostatic expansion valve is used in the outdoor unit on 38HDS applications Insulate both refrigerant lines on 38HDS and BK applications 5 The 49 top and left side clear...

Page 4: ...For Remote Mounting Bracket 2 35 ft Long High Voltage Power Wiring 2 wire with ground 1 35 ft Long Low Voltage Thermistor Wiring 3 wire 1 AccuRaterT Body And Piston 018 and 024 Cooling Only Units 1 Bi...

Page 5: ...Tables 4A 4F for the correct size piping The length of refrigerant pipe de pends on the unit placement and building structure run pipes as directly as possible For piping requirements over 50 ft of to...

Page 6: ...nit Fig 10 Make sure Teflon seal on the piston faces toward the outdoor unit Use Table 5 to verify the correct piston for your sys tem has been shipped with the unit Refer to 38BK installation instruc...

Page 7: ...e OD in 3 8 3 8 Vapor Line OD in 5 8 5 8 Maximum Length ft 200 200 Maximum Lift Fan Coil Above Outdoor ft 65 65 Maximum Lift Fan Coil Below Outdoor ft 150 150 24 v and a minimum of 40 va is provided i...

Page 8: ...est system component Table 4D Physical Data 40QNB High Wall Fan Coil Units UNIT 40QNB 018 024 NOMINAL CAPACITY Tons 11 2 2 NOMINAL SIZE Btuh 18 000 24 000 OPERATING WEIGHT lb 38 5 42 9 MOISTURE REMOVA...

Page 9: ...Tube Aluminum Fin Face Area sq ft No of Coils 6 1 1 5 6 1 2 Fins in 15 15 CONTROLS High Pressure psig Cutout 320 20 Cut in 426 7 Liquid Line Low Pressure psig Cutout 7 3 Cut in 22 5 Fusible Plug 210...

Page 10: ...8 INDOOR COIL Copper Tube Aluminum Fin Face Area sq ft 2 56 2 56 No of Rows 2 3 Fins in 15 9 18 1 Circuits 2 3 FILTERS Cleanable Quantity Size in 2 111 2 x 173 4 AIRSWEEP Horizontal Manual Vertical Au...

Page 11: ...ethane or neoprene Table 5 Required Piston Sizes for AccuRater Metering Device OUTDOOR UNIT 38 INDOOR UNIT 40QN INDOOR PISTON INDOOR PISTON TYPE OUTDOOR PISTON OUTDOOR PISTON TYPE REQUIRED SYSTEM CHAR...

Page 12: ...esting only and cannot be used for power connections 4 Route the factory supplied ground and power wires from terminal block 1 TB1 to the field supplied disconnect switch According to NEC and most loc...

Page 13: ...res of 18 gage AWG American Wire Gage thermostat cable between the low voltage terminal block of the fan coil unit TB2 and the 38BK unit low voltage terminal block Connect the wires between terminals...

Page 14: ...m operation to the owner 40QN Control System The 40QN unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit with ther...

Page 15: ...Mode If auto mode is selected the system automatically switches the operating mode from heating heat pump system only to cooling or from cooling to heating heat pump system only depending on the sele...

Page 16: ...he indoor fan runs at ultra low speed for 30 seconds The normal dehumidification operation is re peated for the newly sensed room temperature 3 When the room temperature is equal to or greater than 4...

Page 17: ...up and down NOTE The unit cannot be controlled by the remote con troller until the slide switch is returned to the REMOTE position Emergency Mode This mode is only to be used if the remote controller...

Page 18: ...s in accordance with the markings on the remote controller so that the poles are correct and RST 3 Press the button using an instrument screwdriver or similar small pointed tool 4 Replace the cover se...

Page 19: ...ntil filter snaps in place If the filter has begun to break down or is torn it needs to be replaced Replacement filters are available through your Carrier distributor To Clean Indoor Unit Front Panel...

Page 20: ...oltage across the two ther mistor connections Approximate temperature is indicated in Table 10 Table 9 System Fault Codes NO OF QUICK LED FLASHES SYSTEM FAULT 2 Room Air Thermistor 3 Indoor Coil Therm...

Page 21: ...39 0 42 0 45 190 890 982 1 078 0 33 0 36 0 39 200 748 828 913 0 28 0 31 0 33 210 631 701 766 0 24 0 26 0 28 212 611 678 751 0 23 0 25 0 28 Circuit volts 5 vdc Table 11 Troubleshooting PROBLEM POTENTI...

Page 22: ...stem Design Manual 2 All wiring must comply with the applicable local and national codes 3 Liquid line need not be insulated 4 Wiring and piping shown are general points of connection guides only and...

Page 23: ...stor RA Th Return Air Thermistor RC Resistor Capacitor RCV Receiver RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay ST Start Thermistor STM Step Motor TB Terminal Block TG Time Guard TP...

Page 24: ...40QNH018 024 FAN COIL 38BK018 024 OUTDOOR SECTION Fig 26 40QNH Fan Coil Unit with 38BK Outdoor Heat Pump Unit 24...

Page 25: ...40QNB018 024 FAN COIL 38HDC018 024 OUTDOOR SECTION 38HDC018 ONLY Fig 27 40QNB Fan Coil Unit with 38HDC Cooling Only Outdoor Condensing Unit 25...

Page 26: ...door Condensing Unit Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations...

Page 27: ...ECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT IS THE LOW VOLTAGE CABLE INDOOR TO OUTDOO...

Page 28: ...AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG DISCHARGE PRESSURE PSIG CUT...

Reviews: