background image

SERVICE

When servicing unit, turn off all electric power to unit
to avoid shock hazard or injury from rotating parts.

Do not vent refrigerant to atmosphere when servicing
unit. Recover refrigerant during system repair or unit
removal.

Diagnostic Codes —

This unit is equipped with a mi-

croprocessor control which continuously monitors the op-
eration of the unit. If an operational fault is detected, a fault
is indicated by the flashing of the green ‘‘UNIT ON’’ light
on the front of the fan coil unit. A red LED (light-emitting
diode) indicator light, located on the control board in the
control box of the indoor unit, will emit a flash code which
can be used to troubleshoot a system problem. The control
will continue to monitor the unit and, if the conditions which
cause the fault are cleared, the unit will return to normal
operation. If the fault code is present for 5 cycles of the unit,
the unit will be locked out and the alarm is indicated by the
flashing of the green ‘‘UNIT ON’’ light on the front of the
fan coil unit.

To access the LED indicator light, remove the front cover

of the unit by removing the 3 screws holding it in place.

If the LED indicator light continuously flashes on for one

second, then off for one second, the control is functioning
properly and no fault is present. A fast flashing LED indi-
cates that a fault has been detected. Table 9 lists the number
of quick flashes and the associated fault. If the system does
not operate, and the LED indicator does not flash, either the
power to the control board is off, or the control board has
failed.

System Tests —

System tests listed below are per-

formed continuously by the microprocessor. If a fault is
indicated, then the system allows only limited operation un-
til the problem is resolved. If the problem resolves itself,
then the code is cleared and operation resumes.

THERMISTOR TESTS — Each thermistor is tested for high
limit out of range (shorted condition) and low limit out of
range (open condition). If the thermistor is out of range, the
fault status indicator comes on and the LED flashes the ap-
propriate fault code.

THERMISTORS — Proper thermistor location and correct
temperature sensing are critical to unit operation. Good ther-
mal contact is also required. Thermistor cable assemblies are
provided with fan coil units to run between indoor and out-
door units. High-voltage and thermistor cable assemblies should
not touch each other, and cable runs may be extended up to
200 feet. With unit running, the thermistor integrity may be
checked by measuring the d.c. voltage across the two ther-
mistor connections. Approximate temperature is indicated in
Table 10.

Table 9 — System Fault Codes

NO. OF QUICK
LED FLASHES

SYSTEM FAULT

2

Room Air Thermistor

3

Indoor Coil Thermistor

4

Outdoor Coil Thermistor*

5

Compressor Malfunction

6

Reversing Valve Malfunction*

7

Outdoor Air Thermistor*

8

Indoor Fan Failure

9

Discharge Air Thermistor

LED — Light-Emitting Diode
*Heat pump systems only.

NOTE: If the LED light continuously flashes on for one second, then off for one
second, the control is functioning properly and no fault is present.

COMPRESSOR FAILURE

If the System is in Cooling or Dehumidification Mode —
After 5 minutes of operation, if the temperature of the in-
door coil is not 4° F less than at the time the call for cooling
started, then a compressor failure is indicated on the remote
controller LCD display.
If the System is in Heat Pump Heating Mode (38BK only)
— After 5 minutes of operation, if the temperature indi-
cated by the outdoor coil thermistor is not 4° F less than at
the time the call for heating started, then a compressor fail-
ure is indicated.
REVERSING VALVE FAILURE (38BK Only)

If the System is in Cooling or Dehumidification Mode — After
5 minutes of operation, if the temperature at the indoor coil
is 4° F more than at the time the call for cooling started, then
a reversing valve failure is indicated.
If the System is in Heat Pump Heating Mode — After 5 min-
utes of operation, if the temperature indicated by the out-
door coil is 4° F more than at the time the call for heating
started, then a reversing valve failure is indicated.

System Safeties and Interlocks

INDOOR FAN FAILURE — If the indoor fan rpm shows
greater than 800 rpm for 30 seconds with the fan in the off
mode, then this test indicates an indoor fan failure. Also, if
the indoor fan rpm is greater than 1700 rpm for 30 seconds,
then this test indicates an indoor fan failure.

COMPRESSOR SHORT-CYCLING PROTECTION — There
is a time delay of 3 minutes between compressor turning off
and turning back on.

INDOOR COIL FREEZE PROTECTION (Cooling or De-
humidification Mode Only) — If the indoor coil tempera-
ture is less than or equal to 32 F for 10 minutes after the
compressor has started, then the compressor and outdoor fan
are turned off. The indoor fan continues to run at the user-
selected speed until the indoor coil reaches 44 F. At that time,
the compressor and outdoor fan will restart.

INDOOR COIL HIGH-TEMPERATURE PROTECTION
(Heat Pump Systems Only) — If indoor coil temperature is
greater than or equal to 135 F, the outdoor fan shuts down.
The outdoor fan will restart automatically when the indoor
coil temperature drops to 120 F.

TROUBLESHOOTING

See Table 11 and Fig. 25-28 to assist in troubleshooting

the 40QN fan coil units.

20

Summary of Contents for 40QNB018

Page 1: ...Pump Systems Only TROUBLESHOOTING 20 26 START UP CHECKLIST CL 1 CL 2 SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical co...

Page 2: ...rews taped to the mounting bracket INSPECT SHIPMENT Upon receipt of shipment check unit Fig 1 for damage Forward claim papers directly to the transportation company Manufacturer is not responsible for...

Page 3: ...C HDL and BK applications A thermostatic expansion valve is used in the outdoor unit on 38HDS applications Insulate both refrigerant lines on 38HDS and BK applications 5 The 49 top and left side clear...

Page 4: ...For Remote Mounting Bracket 2 35 ft Long High Voltage Power Wiring 2 wire with ground 1 35 ft Long Low Voltage Thermistor Wiring 3 wire 1 AccuRaterT Body And Piston 018 and 024 Cooling Only Units 1 Bi...

Page 5: ...Tables 4A 4F for the correct size piping The length of refrigerant pipe de pends on the unit placement and building structure run pipes as directly as possible For piping requirements over 50 ft of to...

Page 6: ...nit Fig 10 Make sure Teflon seal on the piston faces toward the outdoor unit Use Table 5 to verify the correct piston for your sys tem has been shipped with the unit Refer to 38BK installation instruc...

Page 7: ...e OD in 3 8 3 8 Vapor Line OD in 5 8 5 8 Maximum Length ft 200 200 Maximum Lift Fan Coil Above Outdoor ft 65 65 Maximum Lift Fan Coil Below Outdoor ft 150 150 24 v and a minimum of 40 va is provided i...

Page 8: ...est system component Table 4D Physical Data 40QNB High Wall Fan Coil Units UNIT 40QNB 018 024 NOMINAL CAPACITY Tons 11 2 2 NOMINAL SIZE Btuh 18 000 24 000 OPERATING WEIGHT lb 38 5 42 9 MOISTURE REMOVA...

Page 9: ...Tube Aluminum Fin Face Area sq ft No of Coils 6 1 1 5 6 1 2 Fins in 15 15 CONTROLS High Pressure psig Cutout 320 20 Cut in 426 7 Liquid Line Low Pressure psig Cutout 7 3 Cut in 22 5 Fusible Plug 210...

Page 10: ...8 INDOOR COIL Copper Tube Aluminum Fin Face Area sq ft 2 56 2 56 No of Rows 2 3 Fins in 15 9 18 1 Circuits 2 3 FILTERS Cleanable Quantity Size in 2 111 2 x 173 4 AIRSWEEP Horizontal Manual Vertical Au...

Page 11: ...ethane or neoprene Table 5 Required Piston Sizes for AccuRater Metering Device OUTDOOR UNIT 38 INDOOR UNIT 40QN INDOOR PISTON INDOOR PISTON TYPE OUTDOOR PISTON OUTDOOR PISTON TYPE REQUIRED SYSTEM CHAR...

Page 12: ...esting only and cannot be used for power connections 4 Route the factory supplied ground and power wires from terminal block 1 TB1 to the field supplied disconnect switch According to NEC and most loc...

Page 13: ...res of 18 gage AWG American Wire Gage thermostat cable between the low voltage terminal block of the fan coil unit TB2 and the 38BK unit low voltage terminal block Connect the wires between terminals...

Page 14: ...m operation to the owner 40QN Control System The 40QN unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit with ther...

Page 15: ...Mode If auto mode is selected the system automatically switches the operating mode from heating heat pump system only to cooling or from cooling to heating heat pump system only depending on the sele...

Page 16: ...he indoor fan runs at ultra low speed for 30 seconds The normal dehumidification operation is re peated for the newly sensed room temperature 3 When the room temperature is equal to or greater than 4...

Page 17: ...up and down NOTE The unit cannot be controlled by the remote con troller until the slide switch is returned to the REMOTE position Emergency Mode This mode is only to be used if the remote controller...

Page 18: ...s in accordance with the markings on the remote controller so that the poles are correct and RST 3 Press the button using an instrument screwdriver or similar small pointed tool 4 Replace the cover se...

Page 19: ...ntil filter snaps in place If the filter has begun to break down or is torn it needs to be replaced Replacement filters are available through your Carrier distributor To Clean Indoor Unit Front Panel...

Page 20: ...oltage across the two ther mistor connections Approximate temperature is indicated in Table 10 Table 9 System Fault Codes NO OF QUICK LED FLASHES SYSTEM FAULT 2 Room Air Thermistor 3 Indoor Coil Therm...

Page 21: ...39 0 42 0 45 190 890 982 1 078 0 33 0 36 0 39 200 748 828 913 0 28 0 31 0 33 210 631 701 766 0 24 0 26 0 28 212 611 678 751 0 23 0 25 0 28 Circuit volts 5 vdc Table 11 Troubleshooting PROBLEM POTENTI...

Page 22: ...stem Design Manual 2 All wiring must comply with the applicable local and national codes 3 Liquid line need not be insulated 4 Wiring and piping shown are general points of connection guides only and...

Page 23: ...stor RA Th Return Air Thermistor RC Resistor Capacitor RCV Receiver RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay ST Start Thermistor STM Step Motor TB Terminal Block TG Time Guard TP...

Page 24: ...40QNH018 024 FAN COIL 38BK018 024 OUTDOOR SECTION Fig 26 40QNH Fan Coil Unit with 38BK Outdoor Heat Pump Unit 24...

Page 25: ...40QNB018 024 FAN COIL 38HDC018 024 OUTDOOR SECTION 38HDC018 ONLY Fig 27 40QNB Fan Coil Unit with 38HDC Cooling Only Outdoor Condensing Unit 25...

Page 26: ...door Condensing Unit Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations...

Page 27: ...ECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT IS THE LOW VOLTAGE CABLE INDOOR TO OUTDOO...

Page 28: ...AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG DISCHARGE PRESSURE PSIG CUT...

Reviews: