background image

Step 3 — Mount Mounting Bracket on Wall

1. Decide how refrigerant will be piped. If necessary, knock

out the appropriate pre-punched holes (Fig. 4) on unit for
piping and electrical connections.

2. Remove bracket from fan coil unit by pulling it down

from fan coil unit bottom as shown in Fig. 6.

3. Using a carpenter’s level, fasten mounting brackets into

the studs in the wall at least 10 in. away from the ceiling
with the 8 screws provided. Always be sure to insert screws
into the top 2 holes indicated in Fig. 6. Make sure the
attached bracket will support a 200 lb vertical load. For
a masonry wall, anchor shields can be used to attach bracket
to the wall.

4. Temporarily hang unit on bracket to check location and

level.

If mounting bracket is not mounted level, the indoor sec-
tion will be mounted unevenly, and condensate drain-
age water may drip onto the floor. Also, a gap between
the bracket and the wall may result in vibration and noise
from the indoor section.

5. Mark and cut condensate and piping holes.

a. For piping through the wall, mark the wall below the

condensate connection and cut a 2

1

2

-in. hole into the

wall at either point ‘‘A’’ or point ‘‘B’’ in Fig. 7.

NOTE: The 2

1

2

-in hole must be made at a downward slope

to ensure proper condensate drainage. See Fig. 8. Slope
condensate line at a minimum pitch of

1

4

in. per foot of

line. The condensate line cannot be run up for upper pip-
ing connections − only refrigerant lines may be run up.

b. Push the wall sleeve (factory supplied with the unit)

through the 2

1

2

-in. wall opening.

Step 4 — Connect Refrigerant Piping —

Fan coil

units may be connected to the outdoor units using field-
supplied refrigerant grade piping. Refer to Tables 4A-4F for
the correct size piping. The length of refrigerant pipe de-
pends on the unit placement and building structure; run pipes
as directly as possible. For piping requirements over 50 ft of
total run, or more than 25 ft of lift, consult the long line
application guidelines available in the product presale lit-
erature, or contact your local representative. For the 38HDS024
unit, the maximum pipe length is 50 ft.

The 40QNB,QNH unit is shipped with a factory hold-
ing charge of R-22. DO NOT BURY MORE THAN
36 IN. OF REFRIGERANT PIPE IN THE GROUND.
If any section of pipe is buried, there must be a 6-in.
vertical rise to the valve connections on the outdoor unit.
If more than the recommended length is buried, refrig-
erant may migrate to the cooler, buried section during
extended periods of unit shutdown, causing refrigerant
slugging and possible compressor damage at start-up.

Use the following instructions to connect piping.
1. Install insulation. Insulate

all

refrigerant lines on heat pumps

and 38HDS systems to prevent condensation. It is ex-
tremely important that all refrigerant lines and the
AccuRater

t

metering device be insulated on heat pumps.

On 38HDC, HDL cooling only units, the liquid line may
be left uninsulated. Use any acceptable heat resistant closed-
cell foam insulation (minimum

3

8

-in. wall thickness). When

insulating piping, cap ends and slide insulation over the
piping. Insulation can also be cut and placed over piping.

2. Run liquid and gas refrigerant piping.

a. Run pipes as directly as possible, and avoid any un-

necessary turns and bends.

b. Suspend refrigerant pipes so that the insulation is not

damaged and vibrations are not transmitted to the
structure.

c. Leave slack in the refrigerant pipe between the struc-

ture and the unit to absorb vibrations.

Fig. 4 — Refrigerant Piping

*38HDC, 38BK/38HDL/38HDS systems.

Fig. 5 — Maximum Line Lengths

5

Summary of Contents for 40QNB018

Page 1: ...Pump Systems Only TROUBLESHOOTING 20 26 START UP CHECKLIST CL 1 CL 2 SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical co...

Page 2: ...rews taped to the mounting bracket INSPECT SHIPMENT Upon receipt of shipment check unit Fig 1 for damage Forward claim papers directly to the transportation company Manufacturer is not responsible for...

Page 3: ...C HDL and BK applications A thermostatic expansion valve is used in the outdoor unit on 38HDS applications Insulate both refrigerant lines on 38HDS and BK applications 5 The 49 top and left side clear...

Page 4: ...For Remote Mounting Bracket 2 35 ft Long High Voltage Power Wiring 2 wire with ground 1 35 ft Long Low Voltage Thermistor Wiring 3 wire 1 AccuRaterT Body And Piston 018 and 024 Cooling Only Units 1 Bi...

Page 5: ...Tables 4A 4F for the correct size piping The length of refrigerant pipe de pends on the unit placement and building structure run pipes as directly as possible For piping requirements over 50 ft of to...

Page 6: ...nit Fig 10 Make sure Teflon seal on the piston faces toward the outdoor unit Use Table 5 to verify the correct piston for your sys tem has been shipped with the unit Refer to 38BK installation instruc...

Page 7: ...e OD in 3 8 3 8 Vapor Line OD in 5 8 5 8 Maximum Length ft 200 200 Maximum Lift Fan Coil Above Outdoor ft 65 65 Maximum Lift Fan Coil Below Outdoor ft 150 150 24 v and a minimum of 40 va is provided i...

Page 8: ...est system component Table 4D Physical Data 40QNB High Wall Fan Coil Units UNIT 40QNB 018 024 NOMINAL CAPACITY Tons 11 2 2 NOMINAL SIZE Btuh 18 000 24 000 OPERATING WEIGHT lb 38 5 42 9 MOISTURE REMOVA...

Page 9: ...Tube Aluminum Fin Face Area sq ft No of Coils 6 1 1 5 6 1 2 Fins in 15 15 CONTROLS High Pressure psig Cutout 320 20 Cut in 426 7 Liquid Line Low Pressure psig Cutout 7 3 Cut in 22 5 Fusible Plug 210...

Page 10: ...8 INDOOR COIL Copper Tube Aluminum Fin Face Area sq ft 2 56 2 56 No of Rows 2 3 Fins in 15 9 18 1 Circuits 2 3 FILTERS Cleanable Quantity Size in 2 111 2 x 173 4 AIRSWEEP Horizontal Manual Vertical Au...

Page 11: ...ethane or neoprene Table 5 Required Piston Sizes for AccuRater Metering Device OUTDOOR UNIT 38 INDOOR UNIT 40QN INDOOR PISTON INDOOR PISTON TYPE OUTDOOR PISTON OUTDOOR PISTON TYPE REQUIRED SYSTEM CHAR...

Page 12: ...esting only and cannot be used for power connections 4 Route the factory supplied ground and power wires from terminal block 1 TB1 to the field supplied disconnect switch According to NEC and most loc...

Page 13: ...res of 18 gage AWG American Wire Gage thermostat cable between the low voltage terminal block of the fan coil unit TB2 and the 38BK unit low voltage terminal block Connect the wires between terminals...

Page 14: ...m operation to the owner 40QN Control System The 40QN unit is equipped with a microprocessor control which operates the system This control is located in the control box of the fan coil unit with ther...

Page 15: ...Mode If auto mode is selected the system automatically switches the operating mode from heating heat pump system only to cooling or from cooling to heating heat pump system only depending on the sele...

Page 16: ...he indoor fan runs at ultra low speed for 30 seconds The normal dehumidification operation is re peated for the newly sensed room temperature 3 When the room temperature is equal to or greater than 4...

Page 17: ...up and down NOTE The unit cannot be controlled by the remote con troller until the slide switch is returned to the REMOTE position Emergency Mode This mode is only to be used if the remote controller...

Page 18: ...s in accordance with the markings on the remote controller so that the poles are correct and RST 3 Press the button using an instrument screwdriver or similar small pointed tool 4 Replace the cover se...

Page 19: ...ntil filter snaps in place If the filter has begun to break down or is torn it needs to be replaced Replacement filters are available through your Carrier distributor To Clean Indoor Unit Front Panel...

Page 20: ...oltage across the two ther mistor connections Approximate temperature is indicated in Table 10 Table 9 System Fault Codes NO OF QUICK LED FLASHES SYSTEM FAULT 2 Room Air Thermistor 3 Indoor Coil Therm...

Page 21: ...39 0 42 0 45 190 890 982 1 078 0 33 0 36 0 39 200 748 828 913 0 28 0 31 0 33 210 631 701 766 0 24 0 26 0 28 212 611 678 751 0 23 0 25 0 28 Circuit volts 5 vdc Table 11 Troubleshooting PROBLEM POTENTI...

Page 22: ...stem Design Manual 2 All wiring must comply with the applicable local and national codes 3 Liquid line need not be insulated 4 Wiring and piping shown are general points of connection guides only and...

Page 23: ...stor RA Th Return Air Thermistor RC Resistor Capacitor RCV Receiver RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay ST Start Thermistor STM Step Motor TB Terminal Block TG Time Guard TP...

Page 24: ...40QNH018 024 FAN COIL 38BK018 024 OUTDOOR SECTION Fig 26 40QNH Fan Coil Unit with 38BK Outdoor Heat Pump Unit 24...

Page 25: ...40QNB018 024 FAN COIL 38HDC018 024 OUTDOOR SECTION 38HDC018 ONLY Fig 27 40QNB Fan Coil Unit with 38HDC Cooling Only Outdoor Condensing Unit 25...

Page 26: ...door Condensing Unit Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations...

Page 27: ...ECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT IS THE LOW VOLTAGE CABLE INDOOR TO OUTDOO...

Page 28: ...AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG DISCHARGE PRESSURE PSIG CUT...

Reviews: