background image

1 sec, the fan relay is energized. When the thermostat is satisfied,
an off delay is initiated. When the fixed delay of 90

±

20 sec is

completed, the fan relay is de-energized and fan motor stops. If the
wall thermostat closes during this delay, the TDR is reset and the
fan relay remains energized. The TDR is a 24-v device that
operates within a range of 15v to 30v and draws about .5 amps.

If the blower runs continuously instead of cycling off when the fan
switch is set on AUTO, the TDR is probably defective and must be
replaced.

Step 8—Pressure Switches

The low-pressure switch used on the 38TN unit is the switch
normally used in heat pump applications. The standard air condi-
tioner low-pressure switch is NOT used.

Pressure switches are protective devices wired into control circuit
(low voltage). They shut off compressor if abnormally high or low
pressures are present in the refrigeration circuit. Depending on unit
model, you may find a low- and/or high-pressure switch in system.

LOW-PRESSURE SWITCH — The low-pressure switch is lo-
cated on suction line and protects against low suction pressures
caused by such events as loss of charge, low airflow across indoor
coil, dirty filters, etc. It opens on a pressure drop at about 7 psi. If
system pressure is above this, switch should be closed. To check
switch, turn off all power to unit, disconnect leads on switch, and
apply ohmmeter leads across switch. You should have continuity
on a good switch. Because these switches are attached to refrig-
eration system under pressure, it is not advisable to remove this
device for troubleshooting unless you are reasonably certain that a
problem exists. If switch must be removed, remove and recover all
system charge so that pressure gages read 0 psi.

Wear safety glasses and gloves when working with refriger-
ants.

Apply heat with torch to solder joint and remove switch. Wear
safety glasses when using torch. Have quenching cloth available.
Oil vapor in line may ignite when switch is removed.

Braze in 1/4-in. flare fitting and screw on replacement pressure
switch.

HIGH-PRESSURE SWITCH — The high-pressure switch is lo-
cated on liquid line, and protects against high discharge pressures
caused by such events as overcharge, condenser fan motor failure,
system restriction, etc. It opens on pressure rise at about 425 psi.
If system pressures go above this setting during abnormal condi-
tions, the switch opens. Do not attempt to simulate these system
abnormalities as high pressures pose a serious safety hazard.
High-pressure switch is also checked with an ohmmeter similar to
checking low-pressure switch. If system pressure is below 425 psi,
the switch shows continuity. It is replaced in the same manner as
low-pressure switch. Observe all safety precautions.

Step 9—Fan Motor

Fan motor rotates the fan blade that either draws or blows air
through outdoor coil to perform heat exchange. Motors are totally
enclosed to increase reliability. This also eliminates need for rain
shield. For the correct position of the fan blade assembly, see Fig.
12. The A dimension indicated in Fig. 12 equals 6-1/8 in.

Turn off all power to unit before servicing or replacing fan
motor. Be sure unit main power switch is turned off. Failure
to do so may result in electric shock, death, or injury from
rotating fan blade.

The bearings are permanently lubricated, therefore, no oil ports are

provided.

For suspected electrical failures, check for loose or faulty electrical
connections, or defective fan motor capacitor. Fan motor is
equipped with thermal overload device in motor windings which
may open under adverse operating conditions. Allow time for
motor to cool so device can reset. Further checking of motor can
be done with an ohmmeter. Set scale on R X 1 position, and check
for continuity between 3 leads. Replace motors that show an open
circuit in any of the windings. Place 1 lead of ohmmeter on each
motor lead. At same time, place other ohmmeter lead on motor
case (ground). Replace any motor that shows resistance to ground,
arcing, burning, or overheating.

Step 10—Compressor Plug

The compressor electrical plug provides a quick-tight connection
to the compressor terminals. The plug completely covers the
compressor terminals and the mating female terminals are com-
pletely encapsulated in the plug. Therefore, the terminals are
isolated from any moisture so corrosion and resultant pitted or
discolored terminals are reduced. The plug is oriented to the relief
slot in the terminal box so the cover cannot be secured if wires are
not positioned in slot, assuring correct electrical connection at the
compressor. The plug can be removed by simultaneously pulling
while "rocking" the plug. However, these plugs are specialized and
vary in terminal orientation. Therefore, plugs can be used on only
the specific compressor. Fig. 13 shows compressor plug configu-
ration for the Millennium scroll compressor. The configuration
around the fusite terminals is the outline of the terminal covers.
The slot through which the wires of the plug are routed is oriented
on the bottom and slightly to the left. The correct plug can be
connected easily to the compressor terminals and plug wires routed
easily through the slot in the terminal cover.

Step 11—Low-Voltage Terminals

The

low-voltage

terminal

designations

and

their

description/function are used on all split-system condensers.

G—Energizes indoor blower circuit.

R—Energizes 24-v power from transformer (red).

Fig. 12—Fan Position

A94066

INVIROFLOW TOP

A

Fig. 13—Compressor Plug

A94011

LEAD 1
BLK

LEAD 2
YEL

LEAD 3
BLUE

C

S

R

CARLYLE

C

S

R

8

Summary of Contents for 38TN

Page 1: ...te ELECTRICAL 4 Aluminum Wire Contactor Capacitor PTC Devices Cycle Protector Crankcase Heater Time Delay Relay TDR Pressure Switches Fan Motor Compressor Plug Low Voltage Terminals MILLENNIUM SCROLL...

Page 2: ...truction Dimensions MODEL UNIT SIZE A B C D E F G H J K L M 38TN 024 21 32 11 3 16 23 3 4 24 1 2 42 23 11 16 24 7 16 23 5 8 19 11 16 11 7 8 6 11 16 030 21 32 11 13 16 29 3 4 30 1 2 42 29 11 16 30 7 16...

Page 3: ...bserved when handling refrigerants Wear safety glasses and gloves to prevent personal injury During normal system operation some components are hot and can cause burns Rotating fan blades can cause pe...

Page 4: ...NNEL SHOULD PERFORM ELECTRICAL TROUBLESHOOTING Troubleshooting chart for the 38TN Air Conditioner units is provided at the back of this manual It will enable the service technician to use a systematic...

Page 5: ...connect leads and apply low voltage power to contactor coil This may be done by leaving high voltage power to outdoor unit off and turning thermostat to cooling Check voltage at coil with voltmeter Re...

Page 6: ...is called a positive temperature coefficient PTC or thermistor See Fig 7 It is a resistor wired in parallel with the run capacitor As current flows through the PTC at start up it heats up As PTC heats...

Page 7: ...er has power Do not touch heater Carefully feel area around crankcase heater If warm crankcase heater is probably functioning Do not rely on this method as absolute evidence heater is functioning If c...

Page 8: ...the same manner as low pressure switch Observe all safety precautions Step 9 Fan Motor Fan motor rotates the fan blade that either draws or blows air through outdoor coil to perform heat exchange Moto...

Page 9: ...amped on compressor nameplate If compressor draws locked rotor amps and all other external sources of problems have been eliminated compressor must be replaced Because compressor is a sealed unit it i...

Page 10: ...a compressor fails to start or run 3 tests can help determine the problem First all possible external causes should be eliminated such as overloads improper voltage pres sure equalization defective ca...

Page 11: ...with refrigerant Indoor piston or TXV must be cleaned or replaced Remove and discard liquid line strainer and filter drier After system is reassembled install liquid and suction line R134A filter drie...

Page 12: ...light In all instances when a leak is found system charge must be bled down and leak repaired before final charging and operation After leak testing or leak is repaired evacuate system reclaiming refr...

Page 13: ...seat suction valve NOTE All outdoor unit coils will hold only factory supplied amount of refrigerant Excess refrigerant such as in long line applications may cause unit to relieve pressure through int...

Page 14: ...in suction gas returning to compressor The accumulator stores liquid and allows it to boil off into a vapor so it can be safely returned to compressor Since a compressor is designed to pump refrigera...

Page 15: ...ng is the process of charging refrigerant in a system until the temperature superheat of the suction gas entering the compressor reaches a prescribed value Small variations of charge affect suction ga...

Page 16: ...top cover See Remove Top Cover in Cabinet section of the manual Table 1 Superheat Charging Table OUTDOOR TEMP F INDOOR COIL ENTERING AIR TEMP F WB 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14...

Page 17: ...erating cycle trouble shoot to find the cause and correct REFRIGERANT CIRCUIT 1 Check the refrigerant charge using the superheat or subcooling method whichever is applicable and if low on charge check...

Page 18: ...T LOSS OF CHARGE CONTACTOR OR COIL DEFECTIVE LOOSE ELECTRICAL CONNECTION CONTACTOR CLOSED COMPRESSOR POWER SUPPLY OPEN LOOSE LEADS AT COMPRESSOR FAULTY START GEAR 1 PH OPEN SHORTED OR GROUNDED COMPRES...

Page 19: ...19...

Page 20: ...46231 33058c Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 1 2 Tab 3a 5a 1a PC 101 Catalog No 5...

Reviews: