background image

Due to the high pressure of nitrogen, it should never be used
without a pressure regulator on the tank.

Assuming that a system is pressurized with either all refrigerant or
a mixture of nitrogen and refrigerant, leaks in the system can be
found with a leak detector which detects extremely small refrig-
erant leaks.

If system has been operating for some time, make first check for
a leak visually. Since refrigerant carries a small quantity of oil,
traces of oil at any joint or connection is an indication that
refrigerant is leaking at that point.

A simple and inexpensive method of testing for leaks is to use soap
bubbles. Any solution of water and soap may be used. Soap
solution is applied to all joints and connections in system. A small
pinhole leak is located by tracing bubbles in soap solution around
leak.

Use electronic leak detector to check for leaks. This unquestion-
ably is the most efficient and easiest method for checking leaks.
There are various types of electronic leak detectors. Electronic leak
detectors must be suitable for R134A application. Check with the
manufacturer of the equipment for suitability. Generally speaking,
they are all portable, most are lightweight, and consist of a box
with several switches and a probe or sniffer. Detector is turned on
and probe is passed around all fittings and connections in system.
Leak is detected by either the movement of a pointer on detector
dial, a buzzing sound, or a light.

In all instances when a leak is found, system charge must be bled
down and leak repaired before final charging and operation. After
leak testing or leak is repaired, evacuate system reclaiming
refrigerant and recharge with correct refrigerant charge.

Step 3—Brazing

When brazing is required in the refrigeration system, certain basics
should be remembered. The following are a few of the basic rules.

1. Clean joints make the best joints. To clean:

a. Remove all oxidation from surfaces to a shiny finish before

brazing.

b. Remove all flux residue with brush and water while

material is still hot.

2. Use "sil-fos" or "phos-copper" for copper-to-copper only. No

flux is required.

3. Silver solder is used on copper-to-brass, copper-to-steel, or

copper-to-copper. Flux is required when using silver solder.

4. Fluxes should be used carefully. Avoid excessive application

and do not allow fluxes to enter into the system.

5. Brazing temperature of copper is proper when it is heated to a

dull red color.

This section on brazing is not intended to teach a technician how
to braze. There are books and classes which teach and refine
brazing techniques. The basic points above are listed only as a
reminder.

Step 4—Service Valves

Service valves provide a means for holding original factory charge
in outdoor unit prior to hookup to indoor coil. They also contain
gage ports for measuring system pressures, and provide shut-off
convenience for certain types of repairs. (See Fig. 17.)

Fig. 16—Leak Detector

A88401

Fig. 17—Service Valve

A91435

FIELD SIDE

STAINLESS

STEEL

STEM

SERVICE

PORT

ENTRANCE

BACK

SEAT

POSITION

FRONT

SEAT

POSITION

FORGED BACK SEATING VALVE

12

Summary of Contents for 38TN

Page 1: ...te ELECTRICAL 4 Aluminum Wire Contactor Capacitor PTC Devices Cycle Protector Crankcase Heater Time Delay Relay TDR Pressure Switches Fan Motor Compressor Plug Low Voltage Terminals MILLENNIUM SCROLL...

Page 2: ...truction Dimensions MODEL UNIT SIZE A B C D E F G H J K L M 38TN 024 21 32 11 3 16 23 3 4 24 1 2 42 23 11 16 24 7 16 23 5 8 19 11 16 11 7 8 6 11 16 030 21 32 11 13 16 29 3 4 30 1 2 42 29 11 16 30 7 16...

Page 3: ...bserved when handling refrigerants Wear safety glasses and gloves to prevent personal injury During normal system operation some components are hot and can cause burns Rotating fan blades can cause pe...

Page 4: ...NNEL SHOULD PERFORM ELECTRICAL TROUBLESHOOTING Troubleshooting chart for the 38TN Air Conditioner units is provided at the back of this manual It will enable the service technician to use a systematic...

Page 5: ...connect leads and apply low voltage power to contactor coil This may be done by leaving high voltage power to outdoor unit off and turning thermostat to cooling Check voltage at coil with voltmeter Re...

Page 6: ...is called a positive temperature coefficient PTC or thermistor See Fig 7 It is a resistor wired in parallel with the run capacitor As current flows through the PTC at start up it heats up As PTC heats...

Page 7: ...er has power Do not touch heater Carefully feel area around crankcase heater If warm crankcase heater is probably functioning Do not rely on this method as absolute evidence heater is functioning If c...

Page 8: ...the same manner as low pressure switch Observe all safety precautions Step 9 Fan Motor Fan motor rotates the fan blade that either draws or blows air through outdoor coil to perform heat exchange Moto...

Page 9: ...amped on compressor nameplate If compressor draws locked rotor amps and all other external sources of problems have been eliminated compressor must be replaced Because compressor is a sealed unit it i...

Page 10: ...a compressor fails to start or run 3 tests can help determine the problem First all possible external causes should be eliminated such as overloads improper voltage pres sure equalization defective ca...

Page 11: ...with refrigerant Indoor piston or TXV must be cleaned or replaced Remove and discard liquid line strainer and filter drier After system is reassembled install liquid and suction line R134A filter drie...

Page 12: ...light In all instances when a leak is found system charge must be bled down and leak repaired before final charging and operation After leak testing or leak is repaired evacuate system reclaiming refr...

Page 13: ...seat suction valve NOTE All outdoor unit coils will hold only factory supplied amount of refrigerant Excess refrigerant such as in long line applications may cause unit to relieve pressure through int...

Page 14: ...in suction gas returning to compressor The accumulator stores liquid and allows it to boil off into a vapor so it can be safely returned to compressor Since a compressor is designed to pump refrigera...

Page 15: ...ng is the process of charging refrigerant in a system until the temperature superheat of the suction gas entering the compressor reaches a prescribed value Small variations of charge affect suction ga...

Page 16: ...top cover See Remove Top Cover in Cabinet section of the manual Table 1 Superheat Charging Table OUTDOOR TEMP F INDOOR COIL ENTERING AIR TEMP F WB 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14...

Page 17: ...erating cycle trouble shoot to find the cause and correct REFRIGERANT CIRCUIT 1 Check the refrigerant charge using the superheat or subcooling method whichever is applicable and if low on charge check...

Page 18: ...T LOSS OF CHARGE CONTACTOR OR COIL DEFECTIVE LOOSE ELECTRICAL CONNECTION CONTACTOR CLOSED COMPRESSOR POWER SUPPLY OPEN LOOSE LEADS AT COMPRESSOR FAULTY START GEAR 1 PH OPEN SHORTED OR GROUNDED COMPRES...

Page 19: ...19...

Page 20: ...46231 33058c Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 1 2 Tab 3a 5a 1a PC 101 Catalog No 5...

Reviews: