background image

230 volts X 1000 ohms/volt = 230,000 ohms minimum.

SHORT CIRCUIT

To determine if any wires within windings have broken through
their insulation and made contact with other wires, thereby
shorting all or part of the winding(s), be sure the following
conditions are met.

1. Correct motor winding resistances must be known before

testing, either from previous readings or from manufacturer’s
specifications.

2. Temperature of windings must be as specified, usually about

70° F.

3. Resistance measuring instrument must have an accuracy

within

±

5-10 percent. This requires an accurate ohmmeter

such as a Wheatstone bridge or null balance-type instrument.

4. Motor must be dry or free from direct contact with liquid

refrigerant.

MAKE THIS CRITICAL TEST

(Not advisable unless above conditions are met.)

1. Be sure all power is off.

2. Discharge all capacitors.

3. Remove wires from terminals C, S, and R.

4. Place instrument probes together and determine probe and

lead wire resistance.

5. Check resistance readings from C-R, C-S, and R-S.

6. Subtract instrument probe and lead resistance from each

reading.

If any reading is within

±

20 percent of known resistance, motor is

probably normal. Usually a considerable difference in reading is
noted if a turn-to-turn short is present.

Step 3—System Clean-Up After Burnout

Turn off all power to unit before proceeding. Wear safety
glasses and gloves when handling refrigerants. Acids formed
as a result of motor burnout can cause burns.

NOTE:

To analyze level of suspected contamination from com-

pressor burnout, use RCD test kit. (See your distributor/branch.)

Some compressor electrical failures can cause motor to burn.
When this occurs, byproducts of burn, which include sludge,
carbon and acids, contaminate system. If burnout is severe enough,
system must be cleaned before replacement compressor is in-
stalled. The 2 types of motor burnout are classified as mild or
severe.

In mild burnout, there is little or no detectable odor. Compressor
oil is clear or slightly discolored. An acid test of compressor oil
will be negative. This type of failure is treated the same as
mechanical failure. Liquid line strainer should be removed and
liquid line filter drier installed.

In a severe burnout, there is a strong, pungent, rotten egg odor.
Compressor oil is very dark. Evidence of burning may be present
in tubing connected to compressor. An acid test of compressor oil
will be positive. Complete system must be reverse flushed with
refrigerant. Indoor piston or TXV must be cleaned or replaced.
Remove and discard liquid line strainer and filter drier. After
system is reassembled, install liquid and suction line R134A filter
driers. Run system for 2 hrs. Discard both driers and install new
R134A liquid line drier only.

Step 4—Compressor Removal and Replacement

Once it is determined that compressor has failed and the reason
established, compressor must be replaced.

Wear safety glasses and gloves when handling refrigerants
and when using brazing torch.

1. Shut off all power to unit.

2. Remove and recover all refrigerant from system until pressure

gages read 0 psi. Use all service ports.

3. Disconnect electrical leads from compressor. Disconnect or

remove crankcase heater and remove compressor holddown
bolts.

4. Cut compressor from system with tubing cutters. Do not use

brazing torch for compressor removal. Oil vapor may ignite
when compressor is disconnected.

5. Scratch matching marks on stubs in old compressor. Make

corresponding marks on replacement compressor.

6. Use torch to remove stubs from old compressor and to reinstall

them in replacement compressor.

7. Use copper couplings to tie compressor back into system.

8. Evacuate system, recharge, check for normal system opera-

tion.

Do not leave system open to atmosphere for a prolonged
period. Product damage could occur. R134A refrigerant is
highly susceptible to moisture absorption.

REFRIGERATION SYSTEM

Step 1—Refrigeration Cycle

In a refrigerant system, refrigerant moves heat from 1 place to
another. It is useful to understand flow of refrigerant in a system.
In a straight cooling system, compressed hot gas leaves compres-
sor and enters condensing coil. As gas passes through condenser
coil, it rejects heat and condenses into liquid. The liquid leaves
condensing unit through liquid line and enters metering device at
indoor coil. As it passes through metering device, it becomes a
gas-liquid mixture. As it passes through indoor coil, it absorbs heat
and refrigerant and is again compressed to a hot gas, and cycle
repeats.

Step 2—Leak Detection

Always wear safety glasses and gloves when handling refrig-
erants.

New installations should be checked for leaks prior to complete
charging.

If a system has lost all or most of its charge, system must be
pressurized again to approximately 150 lb minimum. This can be
done by adding refrigerant using normal charging procedures or by
pressurizing system with nitrogen (less expensive than refrigerant).
Nitrogen also leaks faster than R134A and is not absorbed by
refrigeration oil. Nitrogen cannot, however, be detected by a leak
detector. (See Fig. 16.)

11

Summary of Contents for 38TN

Page 1: ...te ELECTRICAL 4 Aluminum Wire Contactor Capacitor PTC Devices Cycle Protector Crankcase Heater Time Delay Relay TDR Pressure Switches Fan Motor Compressor Plug Low Voltage Terminals MILLENNIUM SCROLL...

Page 2: ...truction Dimensions MODEL UNIT SIZE A B C D E F G H J K L M 38TN 024 21 32 11 3 16 23 3 4 24 1 2 42 23 11 16 24 7 16 23 5 8 19 11 16 11 7 8 6 11 16 030 21 32 11 13 16 29 3 4 30 1 2 42 29 11 16 30 7 16...

Page 3: ...bserved when handling refrigerants Wear safety glasses and gloves to prevent personal injury During normal system operation some components are hot and can cause burns Rotating fan blades can cause pe...

Page 4: ...NNEL SHOULD PERFORM ELECTRICAL TROUBLESHOOTING Troubleshooting chart for the 38TN Air Conditioner units is provided at the back of this manual It will enable the service technician to use a systematic...

Page 5: ...connect leads and apply low voltage power to contactor coil This may be done by leaving high voltage power to outdoor unit off and turning thermostat to cooling Check voltage at coil with voltmeter Re...

Page 6: ...is called a positive temperature coefficient PTC or thermistor See Fig 7 It is a resistor wired in parallel with the run capacitor As current flows through the PTC at start up it heats up As PTC heats...

Page 7: ...er has power Do not touch heater Carefully feel area around crankcase heater If warm crankcase heater is probably functioning Do not rely on this method as absolute evidence heater is functioning If c...

Page 8: ...the same manner as low pressure switch Observe all safety precautions Step 9 Fan Motor Fan motor rotates the fan blade that either draws or blows air through outdoor coil to perform heat exchange Moto...

Page 9: ...amped on compressor nameplate If compressor draws locked rotor amps and all other external sources of problems have been eliminated compressor must be replaced Because compressor is a sealed unit it i...

Page 10: ...a compressor fails to start or run 3 tests can help determine the problem First all possible external causes should be eliminated such as overloads improper voltage pres sure equalization defective ca...

Page 11: ...with refrigerant Indoor piston or TXV must be cleaned or replaced Remove and discard liquid line strainer and filter drier After system is reassembled install liquid and suction line R134A filter drie...

Page 12: ...light In all instances when a leak is found system charge must be bled down and leak repaired before final charging and operation After leak testing or leak is repaired evacuate system reclaiming refr...

Page 13: ...seat suction valve NOTE All outdoor unit coils will hold only factory supplied amount of refrigerant Excess refrigerant such as in long line applications may cause unit to relieve pressure through int...

Page 14: ...in suction gas returning to compressor The accumulator stores liquid and allows it to boil off into a vapor so it can be safely returned to compressor Since a compressor is designed to pump refrigera...

Page 15: ...ng is the process of charging refrigerant in a system until the temperature superheat of the suction gas entering the compressor reaches a prescribed value Small variations of charge affect suction ga...

Page 16: ...top cover See Remove Top Cover in Cabinet section of the manual Table 1 Superheat Charging Table OUTDOOR TEMP F INDOOR COIL ENTERING AIR TEMP F WB 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14...

Page 17: ...erating cycle trouble shoot to find the cause and correct REFRIGERANT CIRCUIT 1 Check the refrigerant charge using the superheat or subcooling method whichever is applicable and if low on charge check...

Page 18: ...T LOSS OF CHARGE CONTACTOR OR COIL DEFECTIVE LOOSE ELECTRICAL CONNECTION CONTACTOR CLOSED COMPRESSOR POWER SUPPLY OPEN LOOSE LEADS AT COMPRESSOR FAULTY START GEAR 1 PH OPEN SHORTED OR GROUNDED COMPRES...

Page 19: ...19...

Page 20: ...46231 33058c Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 1 2 Tab 3a 5a 1a PC 101 Catalog No 5...

Reviews: