background image

4. Scratch matching marks on tubing stubs and old accumulator.

Scratch matching marks on new accumulator. Unbraze stubs
from old accumulator and braze into new accumulator.

5. Thoroughly rinse any flux residue from joints and paint with

corrosion-resistant coating such as zinc-rich paint.

6. Reinstall accumulator into system with copper slip couplings.

7. Evacuate and charge system.

Pour and measure oil quantity (if any) from old accumulator. If
more than 20 percent of oil charge is trapped in accumulator, add
oil to compressor to make up for this loss.

Step 9—Contaminant Removal

Proper evacuation of a unit will remove non-condensibles and
assure a tight, dry system before charging. The 2 methods used to
evacuate a system are the deep vacuum method and the triple
evacuation method.

DEEP VACUUM METHOD — The deep vacuum method re-
quires a vacuum pump capable of pulling a vacuum of 1000
microns and a vacuum gage capable of accurately measuring this
vacuum depth. The deep vacuum method is the most positive way
of assuring a system is free of air and liquid water.

TRIPLE EVACUATION METHOD — The triple evacuation
method can be used where the vacuum pump is capable of
pumping down to only 28 in. of mercury vacuum, and the system
does not contain any liquid water. The procedure is as follows.

1. Pump the system down to 28 in. of mercury vacuum and allow

pump to continue to operate for additional 15 minutes.

2. Close the service valves and shut off the vacuum pump.

3. Connect a refrigerant cylinder to the system and open until

system pressure is 2 psig.

4. Close the service valve and allow system to stand for 1 hr,

during which time the dry refrigerant will be able to diffuse
throughout the system, absorbing moisture.

5. Repeat procedure 3 times. System will then be free of any

contaminants and water vapor.

Step 10—R134A Refrigerant System Charging

NOTE:

Consult unit information plate for superheat charging

table and unit rating plate for TXV subcooling temperature.

For all approved combinations, system must be charged correctly
for normal system operation and reliable operation of components.
Always wear safety glasses and gloves when handling refrigerants.

If system has lost all charge, weigh in charge using dial-a-charge
or digital scale designed for R134A refrigerant.

System charge should be fine tuned by using the superheat or
subcooling method, whichever is appropriate. These methods are
covered later in this manual.

Step 11—Checking Charge

Superheat charging is the process of charging refrigerant in a
system until the temperature (superheat) of the suction gas entering
the compressor reaches a prescribed value. Small variations of
charge affect suction gas superheat temperatures greatly. There-
fore, this method of charging is very accurate. This method can be
used only on split-system condensing units with fixed restrictor-
type metering devices such as AccuRater. For units using a TXV,
the subcooling method must be used. To charge by superheat, a
service technician will need an accurate superheat thermocouple or
thermistor-type thermometer, a sling psychrometer, and a gage
manifold. Do not use mercury or small dial type thermometers as
they are not adequate for this type of measurement. Then use one
of the following procedures.

SUPERHEAT CHARGING METHOD

1. Operate a unit a minimum of 10 minutes before checking

charge.

2. Measure vapor pressure by attaching a gage to vapor valve

service port.

3. Measure vapor line temperature by attaching a service ther-

mometer to unit vapor line near vapor valve. Insulate ther-
mometer for accurate readings.

4. Measure outdoor air dry-bulb temperature with a second

thermometer.

5. Measure indoor air (entering indoor coil) wet-bulb tempera-

ture with a sling psychrometer.

6. Locate outdoor temperature and evaporator entering air wet-

bulb temperature in Table 1. At this intersection note the
superheat.

7. Locate superheat temperature located in previous step and

vapor pressure in Table 2. At this intersection note vapor line
temperature.

8. If unit has a higher vapor line temperature than charted

temperature, add refrigerant until charted temperature is
reached.

9. If unit has a lower vapor line temperature than charted

temperature, bleed refrigerant until charted temperature is
reached.

10. If outdoor air temperature or pressure at vapor valve changes,

charge to new vapor line temperature indicated on chart.

This procedure compensates for slight variations of indoor airflow.

SUBCOOLING CHARGING METHOD

1. Operate unit a minimum of 15 minutes before checking

charge.

2. Measure liquid service valve pressure by attaching an accurate

gage to the service port.

3. Measure the liquid line temperature by attaching an accurate

thermistor-type or electronic thermometer to the liquid line
near the outdoor coil.

4. Refer to unit rating plate to find required subcooling tempera-

ture for unit. Find the point at which the required subcooling
temperature intersects the measured liquid service valve
pressure on Table 3.

5. To obtain the required subcooling temperature at a specific

liquid line pressure, add refrigerant if liquid line temperature

Fig. 20—Accumulator

A88410

430

°

 FUSE

ELEMENT

15

Summary of Contents for 38TN

Page 1: ...te ELECTRICAL 4 Aluminum Wire Contactor Capacitor PTC Devices Cycle Protector Crankcase Heater Time Delay Relay TDR Pressure Switches Fan Motor Compressor Plug Low Voltage Terminals MILLENNIUM SCROLL...

Page 2: ...truction Dimensions MODEL UNIT SIZE A B C D E F G H J K L M 38TN 024 21 32 11 3 16 23 3 4 24 1 2 42 23 11 16 24 7 16 23 5 8 19 11 16 11 7 8 6 11 16 030 21 32 11 13 16 29 3 4 30 1 2 42 29 11 16 30 7 16...

Page 3: ...bserved when handling refrigerants Wear safety glasses and gloves to prevent personal injury During normal system operation some components are hot and can cause burns Rotating fan blades can cause pe...

Page 4: ...NNEL SHOULD PERFORM ELECTRICAL TROUBLESHOOTING Troubleshooting chart for the 38TN Air Conditioner units is provided at the back of this manual It will enable the service technician to use a systematic...

Page 5: ...connect leads and apply low voltage power to contactor coil This may be done by leaving high voltage power to outdoor unit off and turning thermostat to cooling Check voltage at coil with voltmeter Re...

Page 6: ...is called a positive temperature coefficient PTC or thermistor See Fig 7 It is a resistor wired in parallel with the run capacitor As current flows through the PTC at start up it heats up As PTC heats...

Page 7: ...er has power Do not touch heater Carefully feel area around crankcase heater If warm crankcase heater is probably functioning Do not rely on this method as absolute evidence heater is functioning If c...

Page 8: ...the same manner as low pressure switch Observe all safety precautions Step 9 Fan Motor Fan motor rotates the fan blade that either draws or blows air through outdoor coil to perform heat exchange Moto...

Page 9: ...amped on compressor nameplate If compressor draws locked rotor amps and all other external sources of problems have been eliminated compressor must be replaced Because compressor is a sealed unit it i...

Page 10: ...a compressor fails to start or run 3 tests can help determine the problem First all possible external causes should be eliminated such as overloads improper voltage pres sure equalization defective ca...

Page 11: ...with refrigerant Indoor piston or TXV must be cleaned or replaced Remove and discard liquid line strainer and filter drier After system is reassembled install liquid and suction line R134A filter drie...

Page 12: ...light In all instances when a leak is found system charge must be bled down and leak repaired before final charging and operation After leak testing or leak is repaired evacuate system reclaiming refr...

Page 13: ...seat suction valve NOTE All outdoor unit coils will hold only factory supplied amount of refrigerant Excess refrigerant such as in long line applications may cause unit to relieve pressure through int...

Page 14: ...in suction gas returning to compressor The accumulator stores liquid and allows it to boil off into a vapor so it can be safely returned to compressor Since a compressor is designed to pump refrigera...

Page 15: ...ng is the process of charging refrigerant in a system until the temperature superheat of the suction gas entering the compressor reaches a prescribed value Small variations of charge affect suction ga...

Page 16: ...top cover See Remove Top Cover in Cabinet section of the manual Table 1 Superheat Charging Table OUTDOOR TEMP F INDOOR COIL ENTERING AIR TEMP F WB 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14...

Page 17: ...erating cycle trouble shoot to find the cause and correct REFRIGERANT CIRCUIT 1 Check the refrigerant charge using the superheat or subcooling method whichever is applicable and if low on charge check...

Page 18: ...T LOSS OF CHARGE CONTACTOR OR COIL DEFECTIVE LOOSE ELECTRICAL CONNECTION CONTACTOR CLOSED COMPRESSOR POWER SUPPLY OPEN LOOSE LEADS AT COMPRESSOR FAULTY START GEAR 1 PH OPEN SHORTED OR GROUNDED COMPRES...

Page 19: ...19...

Page 20: ...46231 33058c Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 1 2 Tab 3a 5a 1a PC 101 Catalog No 5...

Reviews: