background image

Step 3—Capacitor

Capacitors can store electrical energy when power is off.
Electrical shock can result if you touch the capacitor termi-
nals and discharge the stored energy. Exercise extreme
caution when working near capacitors. With power off,
discharge stored energy by shorting across the capacitor
terminals with a 15,000-ohm, 2-watt resistor.

NOTE:

If bleed resistor is wired across start capacitor, it must be

disconnected to avoid erroneous readings when ohmmeter is
applied across capacitor. (See Fig. 6.)

Always check capacitors with power off. Attempting to
troubleshoot a capacitor with power on can be dangerous.
Defective capacitors may explode when power is applied.
Insulating fluid inside is combustible and may ignite, causing
burns.

Capacitors are used as a phase-shifting device to aid in starting
certain single-phase motors. Check capacitors as follows.

1. After power is off, discharge capacitors as outlined above.

Disconnect capacitor from circuit. Put ohmmeter on R X 10k
scale. Using ohmmeter, check each terminal to ground (use
capacitor case). Discard any capacitor which measures 1/2
scale deflection or less. Place ohmmeter leads across capacitor
and place on R X 10k scale. Meter should jump to a low
resistance value and slowly climb to higher value. Failure of
meter to do this indicates an open capacitor. If resistance stays
at 0 or a low value, capacitor is internally shorted.

2. Capacitance testers are available which will read value of

capacitor. If value is not within

±

10 percent value stated on

capacitor, it should be replaced. If capacitor is not open or
shorted, the capacitance value is calculated by measuring
voltage across capacitor and current it draws.

Exercise extreme caution when taking readings while power
is on. Electrical shock can cause personal injury or death.

Use following formula to calculate capacitance:

Capacitance (mfd) =

2650 X amps

volts

3. Remove any capacitor that shows signs of bulging, dents, or

leaking. Do not apply power to a defective capacitor as it may
explode.

Step 4—PTC Devices

Sometimes under adverse conditions, a standard run capacitor in a
system is inadequate to start compressor. In these instances, a start
assist device is used to provide an extra starting boost to compres-
sor motor. This device is called a positive temperature coefficient
(PTC) or thermistor. (See Fig. 7.) It is a resistor wired in parallel
with the run capacitor. As current flows through the PTC at
start-up, it heats up. As PTC heats up, its resistance increases
greatly until it effectively lowers the current through itself to an
extremely low value. This, in effect, removes the PTC from the
circuit.

After system shutdown, resistor cools and resistance value returns
to normal until next time system starts. Thermistor device is
adequate for most conditions, however, in systems where off cycle
is short, device cannot fully cool and becomes less effective as a
start device. It is an easy device to troubleshoot. Shut off all power
to system.

Check thermistor with ohmmeter as described below. Shut off all
power to unit. Remove PTC from unit. Wait at least 10 minutes for
PTC to cool to ambient temperature.

Measure resistance of PTC with ohmmeter as shown in Fig. 7.

The cold resistance (RT) of any PTC device should be approxi-
mately 100-180 percent of device ohm rating.

12.5-ohm PTC = 12.5-22.5 ohm resistance - beige color

If PTC resistance is appreciably less than rating or more than 200
percent higher than rating, device is defective.

Use of start capacitor and relay IS NOT RECOMMENDED on
units equipped with a Millennium scroll compressor.

Step 5—Cycle Protector

Solid-state cycle protector protects unit compressor by preventing
short cycling. After a system shutdown, cycle protector provides
for a 5

±

2-minute delay before compressor restarts. On normal

start-up, a 5-minute delay occurs before thermostat closes. After
thermostat closes, cycle protector device provides a 3-sec delay.
(See Fig. 8, 9, and 10.)

Cycle protector is simple to troubleshoot. Only a voltmeter capable
of reading 24v is needed. Device is in control circuit, therefore,
troubleshooting is safe with control power (24v) on and high-
voltage power off.

With high-voltage power off, attach voltmeter leads across T1 and
T3, and set thermostat so that Y terminal is energized. Make sure
all protective devices in series with Y terminal are closed.
Voltmeter should read 24v across T1 and T3. With 24v still
applied, move voltmeter lead from T1 terminal to T2 terminal
across T2 and T3. After 5

±

2 minutes, voltmeter should read 24v,

indicating control is functioning normally. If no time delay is
encountered or device never times out, change control.

Fig. 6—Capacitor

A94006

Fig. 7—PTC Device

A94007

12.5 OHM

(BEIGE COLOR)

12.5-22.5 OHMS

6

Summary of Contents for 38TN

Page 1: ...te ELECTRICAL 4 Aluminum Wire Contactor Capacitor PTC Devices Cycle Protector Crankcase Heater Time Delay Relay TDR Pressure Switches Fan Motor Compressor Plug Low Voltage Terminals MILLENNIUM SCROLL...

Page 2: ...truction Dimensions MODEL UNIT SIZE A B C D E F G H J K L M 38TN 024 21 32 11 3 16 23 3 4 24 1 2 42 23 11 16 24 7 16 23 5 8 19 11 16 11 7 8 6 11 16 030 21 32 11 13 16 29 3 4 30 1 2 42 29 11 16 30 7 16...

Page 3: ...bserved when handling refrigerants Wear safety glasses and gloves to prevent personal injury During normal system operation some components are hot and can cause burns Rotating fan blades can cause pe...

Page 4: ...NNEL SHOULD PERFORM ELECTRICAL TROUBLESHOOTING Troubleshooting chart for the 38TN Air Conditioner units is provided at the back of this manual It will enable the service technician to use a systematic...

Page 5: ...connect leads and apply low voltage power to contactor coil This may be done by leaving high voltage power to outdoor unit off and turning thermostat to cooling Check voltage at coil with voltmeter Re...

Page 6: ...is called a positive temperature coefficient PTC or thermistor See Fig 7 It is a resistor wired in parallel with the run capacitor As current flows through the PTC at start up it heats up As PTC heats...

Page 7: ...er has power Do not touch heater Carefully feel area around crankcase heater If warm crankcase heater is probably functioning Do not rely on this method as absolute evidence heater is functioning If c...

Page 8: ...the same manner as low pressure switch Observe all safety precautions Step 9 Fan Motor Fan motor rotates the fan blade that either draws or blows air through outdoor coil to perform heat exchange Moto...

Page 9: ...amped on compressor nameplate If compressor draws locked rotor amps and all other external sources of problems have been eliminated compressor must be replaced Because compressor is a sealed unit it i...

Page 10: ...a compressor fails to start or run 3 tests can help determine the problem First all possible external causes should be eliminated such as overloads improper voltage pres sure equalization defective ca...

Page 11: ...with refrigerant Indoor piston or TXV must be cleaned or replaced Remove and discard liquid line strainer and filter drier After system is reassembled install liquid and suction line R134A filter drie...

Page 12: ...light In all instances when a leak is found system charge must be bled down and leak repaired before final charging and operation After leak testing or leak is repaired evacuate system reclaiming refr...

Page 13: ...seat suction valve NOTE All outdoor unit coils will hold only factory supplied amount of refrigerant Excess refrigerant such as in long line applications may cause unit to relieve pressure through int...

Page 14: ...in suction gas returning to compressor The accumulator stores liquid and allows it to boil off into a vapor so it can be safely returned to compressor Since a compressor is designed to pump refrigera...

Page 15: ...ng is the process of charging refrigerant in a system until the temperature superheat of the suction gas entering the compressor reaches a prescribed value Small variations of charge affect suction ga...

Page 16: ...top cover See Remove Top Cover in Cabinet section of the manual Table 1 Superheat Charging Table OUTDOOR TEMP F INDOOR COIL ENTERING AIR TEMP F WB 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14...

Page 17: ...erating cycle trouble shoot to find the cause and correct REFRIGERANT CIRCUIT 1 Check the refrigerant charge using the superheat or subcooling method whichever is applicable and if low on charge check...

Page 18: ...T LOSS OF CHARGE CONTACTOR OR COIL DEFECTIVE LOOSE ELECTRICAL CONNECTION CONTACTOR CLOSED COMPRESSOR POWER SUPPLY OPEN LOOSE LEADS AT COMPRESSOR FAULTY START GEAR 1 PH OPEN SHORTED OR GROUNDED COMPRES...

Page 19: ...19...

Page 20: ...46231 33058c Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 1 2 Tab 3a 5a 1a PC 101 Catalog No 5...

Reviews: