background image

38TN

Air Conditioner with R134A Refrigerant

Application Guideline

and Service Manual

SAFETY CONSIDERATIONS

Service and repair of these units should be attempted only by
trained service technicians familiar with Carrier standard service
instruction and training material.

All equipment should be installed in accordance with accepted
practices and unit Installation Instructions, and in compliance with
all national and local codes.
Power should be turned off when servicing or repairing electrical
components. Extreme caution should be observed when trouble-
shooting electrical components with power on. Observe all warn-
ing notices posted on equipment and in instructions or manuals.

Refrigeration system contains refrigerant under pressure. Extreme
caution should be observed when handling refrigerants. Wear
safety glasses and gloves to prevent personal injury. During
normal system operation, some components are hot and can cause
burns. Rotating fan blades can cause personal injury. Appropriate
safety considerations are posted throughout this manual where
potentially dangerous techniques are addressed.

INTRODUCTION

This Application Guideline and Service Manual provides the
required system information necessary to install equipment in
low-ambient conditions, and service, repair, and maintain the
family of 38TN Air Conditioners with nominal capacities ranging
from 24,000 to 48,000 Btu’s. These air conditioners use R134A
refrigerant and operate at lower pressures than standard R22
systems.

TABLE OF CONTENTS

Page

SECTION 1—INSTALLATION GUIDELINE ......................1

SECTION 2—LOW-AMBIENT GUIDELINE ......................1

Applicable Systems

Field-Installed Accessories

Accessory Information

SECTION 3—SERVICE MANUAL ........................................3
UNIT IDENTIFICATION .........................................................3

Product Number Stamped on Unit Rating Plate

Serial Number Identification

CABINET ....................................................................................3

Remove Top Cover

Remove Fan Motor Assembly

Information Plate

ELECTRICAL ............................................................................4

Aluminum Wire

Contactor

Capacitor

PTC Devices

Cycle Protector

Crankcase Heater

Time-Delay Relay (TDR)

Pressure Switches

Fan Motor

Compressor Plug

Low-Voltage Terminals

MILLENNIUM SCROLL COMPRESSOR ............................9

Mechanical Failures

Electrical Failures

System Clean-Up After Burnout

Compressor Removal and Replacement

REFRIGERATION SYSTEM ................................................11

Refrigeration Cycle

Leak Detection

Brazing

Service Valves

AccuRater® (Bypass Type) Components

Thermostatic Expansion Valve (TXV)

Coil Removal

Accumulator

Contaminant Removal

R134A Refrigerant System Charging

Checking Charge

Care and Maintenance

TROUBLESHOOTING CHART ...........................................18

SECTION 1—INSTALLATION GUIDELINE

Specifications for this unit in the RNC market require the outdoor
section, indoor section, refrigerant tubing sets, metering device,
and filter drier listed in Product Data Digest (PDD.) There can be
no deviation.

Specifications for this unit in the AOR market require change-out
of the total system, including the outdoor section, indoor section,
refrigerant tubing sets, metering device, and filter drier listed in
PDD. There can be no deviation.

The system can be applied in low-ambient conditions when
installed following the guidelines in Section 2 of this manual.

For long-line applications over 50 ft, consult the 38TN (R134A)
Residential Application Bulletin available from your local dis-
tributor. The R134A long-line application differs from R22 long-
line application.

SECTION 2—LOW-AMBIENT GUIDELINE

This guideline is for 38TN split-system products only. For
applications involving standard R22 single-speed products, refer to
Low-Ambient Guideline Residential Split-System Application
Bulletin.

This guideline explains the system changes and accessories re-
quired for any 38TN application having operating requirements
below 55°F outdoor ambient temperatures.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

1

2

Tab

3a 5a 1a

PC 101

Catalog No. 513-829

Printed in U.S.A.

Form 38TN-1XA

Pg 1

3-94

Replaces: New

Summary of Contents for 38TN

Page 1: ...te ELECTRICAL 4 Aluminum Wire Contactor Capacitor PTC Devices Cycle Protector Crankcase Heater Time Delay Relay TDR Pressure Switches Fan Motor Compressor Plug Low Voltage Terminals MILLENNIUM SCROLL...

Page 2: ...truction Dimensions MODEL UNIT SIZE A B C D E F G H J K L M 38TN 024 21 32 11 3 16 23 3 4 24 1 2 42 23 11 16 24 7 16 23 5 8 19 11 16 11 7 8 6 11 16 030 21 32 11 13 16 29 3 4 30 1 2 42 29 11 16 30 7 16...

Page 3: ...bserved when handling refrigerants Wear safety glasses and gloves to prevent personal injury During normal system operation some components are hot and can cause burns Rotating fan blades can cause pe...

Page 4: ...NNEL SHOULD PERFORM ELECTRICAL TROUBLESHOOTING Troubleshooting chart for the 38TN Air Conditioner units is provided at the back of this manual It will enable the service technician to use a systematic...

Page 5: ...connect leads and apply low voltage power to contactor coil This may be done by leaving high voltage power to outdoor unit off and turning thermostat to cooling Check voltage at coil with voltmeter Re...

Page 6: ...is called a positive temperature coefficient PTC or thermistor See Fig 7 It is a resistor wired in parallel with the run capacitor As current flows through the PTC at start up it heats up As PTC heats...

Page 7: ...er has power Do not touch heater Carefully feel area around crankcase heater If warm crankcase heater is probably functioning Do not rely on this method as absolute evidence heater is functioning If c...

Page 8: ...the same manner as low pressure switch Observe all safety precautions Step 9 Fan Motor Fan motor rotates the fan blade that either draws or blows air through outdoor coil to perform heat exchange Moto...

Page 9: ...amped on compressor nameplate If compressor draws locked rotor amps and all other external sources of problems have been eliminated compressor must be replaced Because compressor is a sealed unit it i...

Page 10: ...a compressor fails to start or run 3 tests can help determine the problem First all possible external causes should be eliminated such as overloads improper voltage pres sure equalization defective ca...

Page 11: ...with refrigerant Indoor piston or TXV must be cleaned or replaced Remove and discard liquid line strainer and filter drier After system is reassembled install liquid and suction line R134A filter drie...

Page 12: ...light In all instances when a leak is found system charge must be bled down and leak repaired before final charging and operation After leak testing or leak is repaired evacuate system reclaiming refr...

Page 13: ...seat suction valve NOTE All outdoor unit coils will hold only factory supplied amount of refrigerant Excess refrigerant such as in long line applications may cause unit to relieve pressure through int...

Page 14: ...in suction gas returning to compressor The accumulator stores liquid and allows it to boil off into a vapor so it can be safely returned to compressor Since a compressor is designed to pump refrigera...

Page 15: ...ng is the process of charging refrigerant in a system until the temperature superheat of the suction gas entering the compressor reaches a prescribed value Small variations of charge affect suction ga...

Page 16: ...top cover See Remove Top Cover in Cabinet section of the manual Table 1 Superheat Charging Table OUTDOOR TEMP F INDOOR COIL ENTERING AIR TEMP F WB 50 52 54 56 58 60 62 64 66 68 70 72 74 76 55 9 12 14...

Page 17: ...erating cycle trouble shoot to find the cause and correct REFRIGERANT CIRCUIT 1 Check the refrigerant charge using the superheat or subcooling method whichever is applicable and if low on charge check...

Page 18: ...T LOSS OF CHARGE CONTACTOR OR COIL DEFECTIVE LOOSE ELECTRICAL CONNECTION CONTACTOR CLOSED COMPRESSOR POWER SUPPLY OPEN LOOSE LEADS AT COMPRESSOR FAULTY START GEAR 1 PH OPEN SHORTED OR GROUNDED COMPRES...

Page 19: ...19...

Page 20: ...46231 33058c Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 1 2 Tab 3a 5a 1a PC 101 Catalog No 5...

Reviews: