Carrier 30GT 015 Installation Instructions Manual Download Page 4

FIELD 

1. Main Power 

 Bring wires from the fused disconnect

switch through hole in bottom rail of unit to control
box (Fig. 5, 6, 7) and connect to terminals 

 , 

,

 on line side of terminal block 

 (see Fig. 8).

2. Control Power 

 Bring separate source power 

 

 or 230-l-50) into unit as shown in Fig. 

 This

supplies power for control circuit, compressor crank-
case heater and cooler heater. Connect incoming wires
to TB2 in unit 

  box 

 to 

 and L2 to 

Neutral side must be connected to terminal 

 In the

auxiliary power supply a field-supplied disconnect

with 7-amp circuit protection must be provided to

accommodate crankcase heater and cooler heater

cable.
To comply with NEC Article 

 the disconnect

must be located within sight from and readily acces-
sible from unit.

IMPORTANT: To ensure power  to  the heaters,
make sure auxiliary power to unit is always on
(except for servicing or prolonged shutdown).

A toggle switch (marked SW on the label diagram) allows
the control circuit to be manually disconnected when
necessary. This switch does not affect the crankcase
heater and cooler heater cable.

3. Control Circuit Interlocks 

 An accessory flow switch

may be 

 in the chilled water  line  to prevent

 from running when water is not circulating

through the cooler. This switch (no. 

 1 

 is

available as an accessory from Service Parts Center, or

equivalent can be field supplied. Also, it is recom-
mended that auxiliary contacts for the chilled water
pump starter be installed in the control circuit as
additional protection against unit operation when
pump is not running. These  items should be electrically

 in the control circuit, between terminals

 and 

 (for flow switch), and 

 and 

 (for

auxiliary contacts) on TB2. See Fig. 8 for field wiring.

Unbalanced 

 Supply Voltage 

 

Never

operate a motor where a phase imbalance in supply volt-
age  is  greater than 

 Use the following formula to

determine the 

 voltage  imbalance:

 Voltage Imbalance

  x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 

A

  c

AB = 243 volts

   236 volts

AC = 238 volts

M O T O R

__ .

243   236 •+ 238

 

.

Average 

 

3

 

  volts

Determine maximum deviation from average voltage:

 243   239 = 4 volts

(BC) 239   236 = 3 volts
(AC) 239   238 = 1 volt

Maximum  deviation is 4 volts. Determine 

 voltage

imbalance:

4

 

 Imbalance   

   

     

This 

 

 phase imbalance is satisfactory as it is

below the  maximum  allowable 

IMPORTANT: Contact your local electric  utility
company 

 if  the  supply 

 phase

imbalance is more than 

Summary of Contents for 30GT 015

Page 1: ...quipment Rigging Preferred method is with spreader bars from above the unit Use Z in 50 mm 0 D pipe or hooks in lifting holes Rig with 4 cables and spreader bars Al1 panels must be in place when riggi...

Page 2: ...see clearance dimensions in Fig 5 6 7 For multiple units allow 8ft separation between units for airflow and service Mounting Unit When unit is in proper location use of mounting holes in base rails is...

Page 3: ...beginning of next chilling season refill cooler and add recommended inhibitor Power Supply Electrical characteristics of avail able power supply must agree with unit nameplate rating Supply voltage mu...

Page 4: ...lled water line to prevent unit from running when water is not circulating through the cooler This switch no HR8 1 LG005 is available as an accessory from Service Parts Center or equivalent can be fie...

Page 5: ...OPER WT Ib AT SUPPORT POINTS 6OHz 1 2 3 4 Tot 0 1 5 5 1 0 3 7 6 4 3 4 3 2 0 1 6 4 0 015C 5 3 9 3 9 7 4 5 8 3 3 8 1 7 3 2 0 2 0 574 1 4 2 3 4 7 4 3 5 0 1821 02OC 6 1 3 451 5 0 7 3 7 4 1945 50 Hz 4 3 9...

Page 6: ...G T O P V I E W AIRFLOW IHRU 5 4 MIN CLEARANCE FOR C O O L E R R E M O V A L WATER OUTLET 2 FPT c OF COOLER NOZZLE5 WAltK UKAIN 4 6 5 8 C23881 7 IO L324 71 J lo 7 13 16 6 5 8 4 SIDE VIEW wing 30GT015...

Page 7: ...0GT030 2 2 6 8 1 0 2 9 30GT030C 2 4 7 4 1 1 2 2 50 HZ NOTE C INDICATES COPPER COIL 1 cl3153 4 3 3 c i APPROX OPER WT Ib AT SU PPORT POINTS HINGED ACCESS b 1 c e i C2353 9 l 4 I 119 11 END VIEW 3 4 DIA...

Page 8: ...I A UPPLY JR TOP VIEW AIRFLOW THRW t 122353 f 7 4 MIN CLEARANCE FOR COOLER REMOVAL a WATER OUTlET 1 8 0 H 1 I I I 1 880 MTG H O L E S i kl Q 7 IO __ f8121 2 7 1S l6 6 S S 8 IO 7 13 1Ei S I D E V I E W...

Page 9: ...CATES COPPER COIL CONTROL BOX 22 23 7 8 D I A FIELD CONTROL CIRCUIT HIRING 63 5 92 13 2 l 2 3 5 B FIELD MAIN PC WER SUPPLY APPROX OPER WT lb AT SUPPORT POINTS HINGED ACCESS DOOR HATER I N L E T 2 l 2...

Page 10: ...OP VIEW IRFLOW THRU ONDENSER FAN No aB 28451 9 4 MIN CLEARANCE FOR COOLER REMOVAL i_ 12584lt 8 5 3 4 4 f1693 6 5 8 t OF COOLER DRAIN El6991 4 2 1 s El1 C44241 14 6 l 8 S I D E V I E W dimensional Draw...

Page 11: ...plied to unit terminals is not below or above listed minimum and maximum timits TAll fans are protected by a single circuit breaker the IRA for the starting compressor plus the total RLA for all runni...

Page 12: ...ment or other equipment to which the chiller supplies liquid Con sult the manufacturer s instructions If used pump auxiliary contactor and flow switch interlocks must be properly installed see Fig 8 T...

Page 13: ...gle switch to START Be sure all safety devices are satisfied Check to see that the leaving chilled water tempera ture agrees with the dial setting on the temperature controller If it is not the same a...

Page 14: ...n moderately without torquing all the flange bolts in the sequence shown Step 2 Repeat Step 1 tightening the bolts to the specified torque JcJ Fig 11 Tightening Sequence Cooler Head Bolts ik l Line So...

Page 15: ...mpressor stops and the liquid line solenoid valve de energizes Manual reset is required to restart The chilled water circulating pump continues to operate during lockout period WINTER SHUTDOWN At the...

Page 16: ...n and allow the unit to run through a cycle At the instant the last step of capacity unloads switch no 1 opens read the tempera ture If it is not the same as the dial reading the variation can be comp...

Page 17: ...gh pressure switch HPS open low water temperature cutout LWTC RESTART The unit recycles and restarts automati cally under Time Guard control when power is restored or when SW is closed or when contact...

Page 18: ...U U05 in 0 I3 mm d Tube ID before rolling use Elliott tube gage 0 549 ip 13 9 mm e S of twice the wall thickness S9 s of b minus d 0 004 in 0 10 mm f Tube ID after rolling g t d e OS in f4 2 mm NOTE...

Page 19: ...l valve 3 Miswired solenoid 4 Weak broken or wrong valve body spring COMPRESSOR WILL NOT LOAD 1 Miswired solenoid 2 Defective capacity control valve 3 Plugged strainer high side 4 Stuck or damaged unl...

Page 20: ...s the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 2 I PC111 Catalog No 533 034 Printed in U S A Form 30GT ISI Pg 17 8 88...

Reviews: