background image

Capacity Control System 

consists of a multiple-step

water temperature controller, electric cylinder bank
unloader(s) and liquid line solenoid 

  A hot gas

bypass arrangement on  the  final step of unloading is
factory supplied for models 

 60 Hz and 30GT0 15

50 Hz. Factory-installed stubs are provided  to  facilitate

field installation of hot gas bypass for all other units.

MULTIPLE-STEP CONTROLLER consists of load

switches actuated by pressures developed 

 

sensing bulb located in the nozzle of the return water
line of the chilled water system.

To remove the sensing bulb, loosen the setscrew at the

top of well and pull the bulb out. Before replacing the
bulb, half fill the well with heat conductive 

(multi-service grease for high or low humiditv conditions

can be used). Then insert the 

 entirely 

 the well

and tighten the  setscrew. Be 

 

 

 collar is in the

well recess.

The controller is factory set to control from 

return

water temperature through a cooling range of IO F

 The sequence switches are factory calibrated and

sealed and should not require any field changes. Table 5
shows the 

 

temperature steps for the 

 and

3-step controllers.

The return water 

 at 

 the last step of

capacity unloads is 

 by the leaving water tem-

perature design set point on the adjustable dial (Fig. 12).
Example: design set point is at 44   (6.7 C). On   reduc-
tion in load, the capacity of the unit is reduced to zero
when 

 water temperature drops to 44 F 

 C).

Any alteration of factory settings, except design set
point, without Carrier authorization, may void

Carrier Warranty.

Design  Set Point Adjustment 

 When unit is ready for

operation. 

 small screwdriver in adjusting slot

(Fig. 12) and rotate to turn diaf (the 

 be turned by

hand if desired).

fable 5 

 Capacity Control Steps

*Return chilled water temperature.

 hot gas bypass.

 set point.

Rotate until the design set point for the installation

appears 

 under the pointer. Insert a thermometer

in the 

return 

chilled water connection and allow the unit

to run through a cycle. At the instant the last step of
capacity 

 

 no. 1 opens), read the 

ture. If it is not 

 same as the dial reading, the variation

can be compensated by shifting the control point slightly.

Do not force the dial past the stop. This could cause
loss of the control point and damage 

 instrument.

HOT GAS BYPASS VALVE  is  factory-installed on
Models 

 50 Hz and 

 Hz. It modu-

lates flow of hot gas into refrigerant circuit in response to
variations from preset suction pressure. 

sudden de-

crease in suction pressure causes valve to admit  more hot
gas to restore the preset pressure level. The hut gas enters
the refrigerant circuit through the connecting tube

between the thermal expansion 

 the cooler. With

hot gas 

 the 

 unit operates down to a lower

load condition; the result is less frequent off-on cycling
of the chiller.

The bypass valve is factory set to begin opening when

suction pressure drops to 

 62 psig (427 

 This

pressure corresponds to a chilled water controller 
point of approximately 

 F (6.7 C). If the chilled water

set point is lower than 44F (6.7 

 it is necessary to

decrease the bypass valve setting for proper operation.
Conversely, for chilled water set points above 44F

 the bypass valve setting must be increased. A

change in condensing temperature also requires a change
in bypass valve set  point,  As condensing temperature
decreases, decrease the bypass valve ser point until it
opens at desired conditions.

OPERATION

Refer to Control Circuit diagram on the unit, or in the

Wiring Diagrams publication.

Timer Functions (See 

Fig. 13)

1. Switch A 

 A-A    and A-A2) provides  Time

 function. Start 

 

 is delayed

approximately 5.5 minutes after shutoff. The 
mum rime between starts of compressor is 8 minutes.

2. Switch B (contacts 

 and B-B2) starts compressor.

3. Switch D (contacts D-Dl) bypasses the low-pressure

switch (LPS) for 2.5 minutes at start-up for winter
start control.

 

 

 

 

(BLACK DENOTES CLOSED CONTACTS)

TIMER POSITION DURING

  O f f

UNIT

   
I

  S E C  

A-AI 

 COMPRESSOR STARTS

 

 

  S E C  

 

 

 

 SEC

 

D-02 

150 SEC 

- - - - l - 5 . 5  

Fig. 13 

 Timer Cycle

Fig.   2 

 Set Point Adjustment

Summary of Contents for 30GT 015

Page 1: ...quipment Rigging Preferred method is with spreader bars from above the unit Use Z in 50 mm 0 D pipe or hooks in lifting holes Rig with 4 cables and spreader bars Al1 panels must be in place when riggi...

Page 2: ...see clearance dimensions in Fig 5 6 7 For multiple units allow 8ft separation between units for airflow and service Mounting Unit When unit is in proper location use of mounting holes in base rails is...

Page 3: ...beginning of next chilling season refill cooler and add recommended inhibitor Power Supply Electrical characteristics of avail able power supply must agree with unit nameplate rating Supply voltage mu...

Page 4: ...lled water line to prevent unit from running when water is not circulating through the cooler This switch no HR8 1 LG005 is available as an accessory from Service Parts Center or equivalent can be fie...

Page 5: ...OPER WT Ib AT SUPPORT POINTS 6OHz 1 2 3 4 Tot 0 1 5 5 1 0 3 7 6 4 3 4 3 2 0 1 6 4 0 015C 5 3 9 3 9 7 4 5 8 3 3 8 1 7 3 2 0 2 0 574 1 4 2 3 4 7 4 3 5 0 1821 02OC 6 1 3 451 5 0 7 3 7 4 1945 50 Hz 4 3 9...

Page 6: ...G T O P V I E W AIRFLOW IHRU 5 4 MIN CLEARANCE FOR C O O L E R R E M O V A L WATER OUTLET 2 FPT c OF COOLER NOZZLE5 WAltK UKAIN 4 6 5 8 C23881 7 IO L324 71 J lo 7 13 16 6 5 8 4 SIDE VIEW wing 30GT015...

Page 7: ...0GT030 2 2 6 8 1 0 2 9 30GT030C 2 4 7 4 1 1 2 2 50 HZ NOTE C INDICATES COPPER COIL 1 cl3153 4 3 3 c i APPROX OPER WT Ib AT SU PPORT POINTS HINGED ACCESS b 1 c e i C2353 9 l 4 I 119 11 END VIEW 3 4 DIA...

Page 8: ...I A UPPLY JR TOP VIEW AIRFLOW THRW t 122353 f 7 4 MIN CLEARANCE FOR COOLER REMOVAL a WATER OUTlET 1 8 0 H 1 I I I 1 880 MTG H O L E S i kl Q 7 IO __ f8121 2 7 1S l6 6 S S 8 IO 7 13 1Ei S I D E V I E W...

Page 9: ...CATES COPPER COIL CONTROL BOX 22 23 7 8 D I A FIELD CONTROL CIRCUIT HIRING 63 5 92 13 2 l 2 3 5 B FIELD MAIN PC WER SUPPLY APPROX OPER WT lb AT SUPPORT POINTS HINGED ACCESS DOOR HATER I N L E T 2 l 2...

Page 10: ...OP VIEW IRFLOW THRU ONDENSER FAN No aB 28451 9 4 MIN CLEARANCE FOR COOLER REMOVAL i_ 12584lt 8 5 3 4 4 f1693 6 5 8 t OF COOLER DRAIN El6991 4 2 1 s El1 C44241 14 6 l 8 S I D E V I E W dimensional Draw...

Page 11: ...plied to unit terminals is not below or above listed minimum and maximum timits TAll fans are protected by a single circuit breaker the IRA for the starting compressor plus the total RLA for all runni...

Page 12: ...ment or other equipment to which the chiller supplies liquid Con sult the manufacturer s instructions If used pump auxiliary contactor and flow switch interlocks must be properly installed see Fig 8 T...

Page 13: ...gle switch to START Be sure all safety devices are satisfied Check to see that the leaving chilled water tempera ture agrees with the dial setting on the temperature controller If it is not the same a...

Page 14: ...n moderately without torquing all the flange bolts in the sequence shown Step 2 Repeat Step 1 tightening the bolts to the specified torque JcJ Fig 11 Tightening Sequence Cooler Head Bolts ik l Line So...

Page 15: ...mpressor stops and the liquid line solenoid valve de energizes Manual reset is required to restart The chilled water circulating pump continues to operate during lockout period WINTER SHUTDOWN At the...

Page 16: ...n and allow the unit to run through a cycle At the instant the last step of capacity unloads switch no 1 opens read the tempera ture If it is not the same as the dial reading the variation can be comp...

Page 17: ...gh pressure switch HPS open low water temperature cutout LWTC RESTART The unit recycles and restarts automati cally under Time Guard control when power is restored or when SW is closed or when contact...

Page 18: ...U U05 in 0 I3 mm d Tube ID before rolling use Elliott tube gage 0 549 ip 13 9 mm e S of twice the wall thickness S9 s of b minus d 0 004 in 0 10 mm f Tube ID after rolling g t d e OS in f4 2 mm NOTE...

Page 19: ...l valve 3 Miswired solenoid 4 Weak broken or wrong valve body spring COMPRESSOR WILL NOT LOAD 1 Miswired solenoid 2 Defective capacity control valve 3 Plugged strainer high side 4 Stuck or damaged unl...

Page 20: ...s the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 2 I PC111 Catalog No 533 034 Printed in U S A Form 30GT ISI Pg 17 8 88...

Reviews: