background image

Leak Test and Dehydration 

 

All 30GT units are

shipped with complete operating charge of Refrigerant 22

(Table 1) and should  be  under sufficient pressure to

conduct leak test after installation. If there is no system

pressure, admit refrigerant until a pressure is observed
and then proceed to test for leaks. After leaks are re-
paired, the system must be dehydrated. For leak testing
and dehydration procedures, refer to Carrier Standard
Service Techniques Manual, Chapter I, Refrigerants,

Sections 6 and 7.

Refrigerant Charge 

When additional or complete

field charging is required, refer to Table I and use the

Liquid Charging Method. Refer to 

 Standard

Service Techniques Manual, Chapter 1, Refrigerants,
Section 8, for charging procedures.

Immediately ahead of the filter drier is a 

installed liquid shutoff charging valve, A 

 flare

connection is provided for 

 charging.

Never charge liquid into low-pressure side of system.

Do  not  overcharge. During charging or removal of

refrigerant, be sure water is continuously circulating
through the cooler to prevent freezing.

Control Power Circuit 

 

Switch 115-l-60 or

230-I-50 field disconnect to ON. The cooler heater is

factory wired into the control circuit.

IMPORTANT: The compressor crankcase heater

should be on as soon as auxiliary circuit is energized.

Allow crankcase heater to operate at least 24 hours
before starting unit, then close main power circuit

Actual Start-Up 

should be done only under super-

vision of a qualified refrigeration mechanic:

Open any compressor and system valves that were
closed during charging.
Turn control circuit toggle switch to START.
Be sure all safety devices are satisfied.
Check to see that the leaving chilled water tempera-
ture agrees with the dial setting on the temperature
controller. If it is not the same as the dial setting,
the variation  can  be compensated by shifting the
control point slightly to obtain the proper leaving
chilled water temperature.

SERVICE

Turn off all power to unit before proceeding,

I

Access for Servicing (See Fig. 9)

COMPRESSOR SECTION 

 The compressor com-

partment has 2 side doors and one front door for servic-
ing, providing access to compressor, all components of
the  refrigeration  system, electrical controls and control

box. After opening front door an inner cover must be
removed for access to control box.

The low water temperature cutout and water tempera-

ture control are located in the auxiliary control box
behind the side access door on the cooler side. Both can
be adjusted without removing auxiliary box cover.

CONDENSER SECTION 

 Condenser fan motors and

fans can be serviced by removal of outlet grilles or side

panels. If a fan motor is serviced, be sure the wire fan

guard is in place over each fan before starting unit.

See Fig, IO for proper fan adjustment. Tighten fan hub
securely on motor shaft with setscrew which bears against
the  key.  Be sure to replace Permagum and rubber cap
over end of motor shaft to protect against moisture
causing fan to rust on shaft.
COOLER SECTION 

 The cooler can be serviced

from the side or the end opposite the compressor com-
partment. To remove cooler tubes or entire cooler, see

Fig. 5, 6, 7 for minimum clearance required. Cooler

should be removed from end of unit.

LEFT FRONT VIEW, COMPRESSOR END

 END, LEFT FRONT ACCESS D O O R

COMPRESSOR END, CONTROLS PANEL REMOVED

Fig. 9 

 

 Unit with Access Panels Removed

 5,020 

Shown)

10

Summary of Contents for 30GT 015

Page 1: ...quipment Rigging Preferred method is with spreader bars from above the unit Use Z in 50 mm 0 D pipe or hooks in lifting holes Rig with 4 cables and spreader bars Al1 panels must be in place when riggi...

Page 2: ...see clearance dimensions in Fig 5 6 7 For multiple units allow 8ft separation between units for airflow and service Mounting Unit When unit is in proper location use of mounting holes in base rails is...

Page 3: ...beginning of next chilling season refill cooler and add recommended inhibitor Power Supply Electrical characteristics of avail able power supply must agree with unit nameplate rating Supply voltage mu...

Page 4: ...lled water line to prevent unit from running when water is not circulating through the cooler This switch no HR8 1 LG005 is available as an accessory from Service Parts Center or equivalent can be fie...

Page 5: ...OPER WT Ib AT SUPPORT POINTS 6OHz 1 2 3 4 Tot 0 1 5 5 1 0 3 7 6 4 3 4 3 2 0 1 6 4 0 015C 5 3 9 3 9 7 4 5 8 3 3 8 1 7 3 2 0 2 0 574 1 4 2 3 4 7 4 3 5 0 1821 02OC 6 1 3 451 5 0 7 3 7 4 1945 50 Hz 4 3 9...

Page 6: ...G T O P V I E W AIRFLOW IHRU 5 4 MIN CLEARANCE FOR C O O L E R R E M O V A L WATER OUTLET 2 FPT c OF COOLER NOZZLE5 WAltK UKAIN 4 6 5 8 C23881 7 IO L324 71 J lo 7 13 16 6 5 8 4 SIDE VIEW wing 30GT015...

Page 7: ...0GT030 2 2 6 8 1 0 2 9 30GT030C 2 4 7 4 1 1 2 2 50 HZ NOTE C INDICATES COPPER COIL 1 cl3153 4 3 3 c i APPROX OPER WT Ib AT SU PPORT POINTS HINGED ACCESS b 1 c e i C2353 9 l 4 I 119 11 END VIEW 3 4 DIA...

Page 8: ...I A UPPLY JR TOP VIEW AIRFLOW THRW t 122353 f 7 4 MIN CLEARANCE FOR COOLER REMOVAL a WATER OUTlET 1 8 0 H 1 I I I 1 880 MTG H O L E S i kl Q 7 IO __ f8121 2 7 1S l6 6 S S 8 IO 7 13 1Ei S I D E V I E W...

Page 9: ...CATES COPPER COIL CONTROL BOX 22 23 7 8 D I A FIELD CONTROL CIRCUIT HIRING 63 5 92 13 2 l 2 3 5 B FIELD MAIN PC WER SUPPLY APPROX OPER WT lb AT SUPPORT POINTS HINGED ACCESS DOOR HATER I N L E T 2 l 2...

Page 10: ...OP VIEW IRFLOW THRU ONDENSER FAN No aB 28451 9 4 MIN CLEARANCE FOR COOLER REMOVAL i_ 12584lt 8 5 3 4 4 f1693 6 5 8 t OF COOLER DRAIN El6991 4 2 1 s El1 C44241 14 6 l 8 S I D E V I E W dimensional Draw...

Page 11: ...plied to unit terminals is not below or above listed minimum and maximum timits TAll fans are protected by a single circuit breaker the IRA for the starting compressor plus the total RLA for all runni...

Page 12: ...ment or other equipment to which the chiller supplies liquid Con sult the manufacturer s instructions If used pump auxiliary contactor and flow switch interlocks must be properly installed see Fig 8 T...

Page 13: ...gle switch to START Be sure all safety devices are satisfied Check to see that the leaving chilled water tempera ture agrees with the dial setting on the temperature controller If it is not the same a...

Page 14: ...n moderately without torquing all the flange bolts in the sequence shown Step 2 Repeat Step 1 tightening the bolts to the specified torque JcJ Fig 11 Tightening Sequence Cooler Head Bolts ik l Line So...

Page 15: ...mpressor stops and the liquid line solenoid valve de energizes Manual reset is required to restart The chilled water circulating pump continues to operate during lockout period WINTER SHUTDOWN At the...

Page 16: ...n and allow the unit to run through a cycle At the instant the last step of capacity unloads switch no 1 opens read the tempera ture If it is not the same as the dial reading the variation can be comp...

Page 17: ...gh pressure switch HPS open low water temperature cutout LWTC RESTART The unit recycles and restarts automati cally under Time Guard control when power is restored or when SW is closed or when contact...

Page 18: ...U U05 in 0 I3 mm d Tube ID before rolling use Elliott tube gage 0 549 ip 13 9 mm e S of twice the wall thickness S9 s of b minus d 0 004 in 0 10 mm f Tube ID after rolling g t d e OS in f4 2 mm NOTE...

Page 19: ...l valve 3 Miswired solenoid 4 Weak broken or wrong valve body spring COMPRESSOR WILL NOT LOAD 1 Miswired solenoid 2 Defective capacity control valve 3 Plugged strainer high side 4 Stuck or damaged unl...

Page 20: ...s the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 2 I PC111 Catalog No 533 034 Printed in U S A Form 30GT ISI Pg 17 8 88...

Reviews: