background image

Compressor Protection

 BREAKER 

 Calibrated trip manual reset,

ambient compensated, magnetic breaker protects against

motor overload and locked rotor conditions.

 THERMOSTAT 

 On 

 compres-

sors, a sensor embedded in  motor  windings protects
against overtemperature. A sensor in the discharge gas of

 compressor reacts to excessively high  discharge  gas

temperature  and shuts  off the compressor.

 GUARD@ control protects compressor against

short cycling. See Sequence of Control (page 14).
CRANKCASE HEATER minimizes  a b s o r p t i o n   o f
liquid refrigerant by oil in crankcase during brief or
extended shutdown periods. Source  of 

 60 Hz, or

 

 Hz power is the auxiliary control power,

independent of the main unit power. This  assures  com-
pressor protection even when main unit power disconnect

switch is off.

IMPORTANT: Never open any switch or dis-
connect that de-energizes the crankcase heater unless
unit  is being serviced or is to be shut down for a
prolonged period. After a prolonged 

 on a

service job, energize the crankcase heater for 24
hours before starting the compressor.

Cooler 

 Protection

HEATER CABLE 

 A heater cable is helically wound

around the entire length of the cooler. A thermostat
energizes the cable whenever the ambient temperature is

35 F (1.7 C) or lower. The cable is between the cooler and
the insulation blanket around the cooler. The heater

cable and the insulation protect the cooler down to -20 F

(-29 

 ambient temperature.

Since the 115-l-60, or 230-I-50 auxiliary power source

for the heater cable is separate from main power source,
power to heater is assured even though the main unit
power may be off.

Do not disconnect heater cable power when servicing

compressor if ambient temperature is below 40 F

(4.4 C). If power to the heater cable is cut off, or if

unit is to be down for a prolonged period, drain
the 

SAFETY THERMOSTAT (Freezestat  or  Low Water
Temperature Cutout) 

 The sensing bulb is located in the

cooler nozzle at  the  chilled water end. To remove the
sensing bulb, loosen the setscrew at the top of well and
pull the bulb out.  Before  replacing the bulb, half fill the
well with heat conductive compound (multi-service
grease for high or low humidity conditions can be used).

Then insert the bulb entirely into the well and tighten the

setscrew. 

 

 the split 

 is in the well recess.

The thermostat is factory set to open at 36   2 F (2.2

 1.1 

 It opens and locks out the compressor safety

circuit. The compressor stops and the liquid line solenoid
valve de-energizes. Manual reset is required to restart.

The 

  water circulating pump continues to operate

during lockout period.

WINTER SHUTDOWN 

 At the end of the 

season, drain the water from the 

 (see drain loca-

tion in Fig. 5, 6, 7). Replace the drain plug and put 2
gallons (8 L) of ethylene glycol in the cooler to prevent

any residual water in the cooler from freezing. At the
beginning of the next cooling season, refill the cooler and

add the recommended inhibitor.

High-Pressure Switch 

has fixed, nonadjustable

settings. Switch is mounted on the compressor.

TO CHECK

Open the condenser fan circuit breaker. Head pressure

builds up until compressor shuts down. This should be at
the cutout pressure in Table  3. Close condenser fan circuit
breaker. After pressure drops to cut-in setting, reset
control circuit by opening, then closing the control cir-
cuit switch. After control circuit is reset, the Time Guard@
timer cycles and in approximately 5.5 minutes the com-

pressor restarts.

Low-Pressure Switch 

has fixed, nonadjustable

settings. 

Switch is mounted on the compressor.

TO CHECK

 close 

 shutoff valve and allow com-

pressor to pump 

 Do not allow 

 to pump

down below 2 

 (13.8 

 Compressor should shut

down when suction pressure 

 to cutout pressure in

Table 3, and should restart when pressure builds up to

cut-in pressure shown.

  3

 

 Switch Settings, 

psig 

HIGH PRESSURE

Winter Start Control

 Switch D in the 4-function

timer bypasses low-pressure switch for 

 2 minutes on

unit start-up.

Head Pressure Control 

reduces  condensing capacity

under low ambient temperature conditions.

FAN CYCLING 

 These 30GT units have standard pro-

vision for fully automatic intermediate-season head

pressure control through condenser fan cycling. Fan no. 2
is cycled by a  fan cycling pressure switch 

 which

responds to variation in discharge pressure. The pressure
sensor is located in the liquid line of the refrigerant circuit.

Fan no. 3 cycling is controlled by outdoor air temperature

through an air temperature switch (ATS) 
units only).

The ATS is located in the lower divider panel between

the compressor compartment and  condenser  section.

Through a hole in the 

 the sensing element is

exposed  to  air entering the no. 1 fan compartment. Fan

no. 1 is non-cycling. Table 4 shows the operating set-
tings of the fan cycling pressure switch and the air tem-
perature switch.

Table 4 

 Fan Cycling Controls

CONTROL BY

S W I T C H   O P E N S     S W I T C H   C L O S E S

 F (C)

7 0

3 (21 

1.7) 

8 0

  3 ( 2 7  

1.7)

Pressure,

osia 

1 6 0

1 0 (1103

 69) 2 6 0

 15 ( 1 7 9 3

 103)

NOTE: See Fig. 5, 6, 7 for fan arrangement.

1 2

Summary of Contents for 30GT 015

Page 1: ...quipment Rigging Preferred method is with spreader bars from above the unit Use Z in 50 mm 0 D pipe or hooks in lifting holes Rig with 4 cables and spreader bars Al1 panels must be in place when riggi...

Page 2: ...see clearance dimensions in Fig 5 6 7 For multiple units allow 8ft separation between units for airflow and service Mounting Unit When unit is in proper location use of mounting holes in base rails is...

Page 3: ...beginning of next chilling season refill cooler and add recommended inhibitor Power Supply Electrical characteristics of avail able power supply must agree with unit nameplate rating Supply voltage mu...

Page 4: ...lled water line to prevent unit from running when water is not circulating through the cooler This switch no HR8 1 LG005 is available as an accessory from Service Parts Center or equivalent can be fie...

Page 5: ...OPER WT Ib AT SUPPORT POINTS 6OHz 1 2 3 4 Tot 0 1 5 5 1 0 3 7 6 4 3 4 3 2 0 1 6 4 0 015C 5 3 9 3 9 7 4 5 8 3 3 8 1 7 3 2 0 2 0 574 1 4 2 3 4 7 4 3 5 0 1821 02OC 6 1 3 451 5 0 7 3 7 4 1945 50 Hz 4 3 9...

Page 6: ...G T O P V I E W AIRFLOW IHRU 5 4 MIN CLEARANCE FOR C O O L E R R E M O V A L WATER OUTLET 2 FPT c OF COOLER NOZZLE5 WAltK UKAIN 4 6 5 8 C23881 7 IO L324 71 J lo 7 13 16 6 5 8 4 SIDE VIEW wing 30GT015...

Page 7: ...0GT030 2 2 6 8 1 0 2 9 30GT030C 2 4 7 4 1 1 2 2 50 HZ NOTE C INDICATES COPPER COIL 1 cl3153 4 3 3 c i APPROX OPER WT Ib AT SU PPORT POINTS HINGED ACCESS b 1 c e i C2353 9 l 4 I 119 11 END VIEW 3 4 DIA...

Page 8: ...I A UPPLY JR TOP VIEW AIRFLOW THRW t 122353 f 7 4 MIN CLEARANCE FOR COOLER REMOVAL a WATER OUTlET 1 8 0 H 1 I I I 1 880 MTG H O L E S i kl Q 7 IO __ f8121 2 7 1S l6 6 S S 8 IO 7 13 1Ei S I D E V I E W...

Page 9: ...CATES COPPER COIL CONTROL BOX 22 23 7 8 D I A FIELD CONTROL CIRCUIT HIRING 63 5 92 13 2 l 2 3 5 B FIELD MAIN PC WER SUPPLY APPROX OPER WT lb AT SUPPORT POINTS HINGED ACCESS DOOR HATER I N L E T 2 l 2...

Page 10: ...OP VIEW IRFLOW THRU ONDENSER FAN No aB 28451 9 4 MIN CLEARANCE FOR COOLER REMOVAL i_ 12584lt 8 5 3 4 4 f1693 6 5 8 t OF COOLER DRAIN El6991 4 2 1 s El1 C44241 14 6 l 8 S I D E V I E W dimensional Draw...

Page 11: ...plied to unit terminals is not below or above listed minimum and maximum timits TAll fans are protected by a single circuit breaker the IRA for the starting compressor plus the total RLA for all runni...

Page 12: ...ment or other equipment to which the chiller supplies liquid Con sult the manufacturer s instructions If used pump auxiliary contactor and flow switch interlocks must be properly installed see Fig 8 T...

Page 13: ...gle switch to START Be sure all safety devices are satisfied Check to see that the leaving chilled water tempera ture agrees with the dial setting on the temperature controller If it is not the same a...

Page 14: ...n moderately without torquing all the flange bolts in the sequence shown Step 2 Repeat Step 1 tightening the bolts to the specified torque JcJ Fig 11 Tightening Sequence Cooler Head Bolts ik l Line So...

Page 15: ...mpressor stops and the liquid line solenoid valve de energizes Manual reset is required to restart The chilled water circulating pump continues to operate during lockout period WINTER SHUTDOWN At the...

Page 16: ...n and allow the unit to run through a cycle At the instant the last step of capacity unloads switch no 1 opens read the tempera ture If it is not the same as the dial reading the variation can be comp...

Page 17: ...gh pressure switch HPS open low water temperature cutout LWTC RESTART The unit recycles and restarts automati cally under Time Guard control when power is restored or when SW is closed or when contact...

Page 18: ...U U05 in 0 I3 mm d Tube ID before rolling use Elliott tube gage 0 549 ip 13 9 mm e S of twice the wall thickness S9 s of b minus d 0 004 in 0 10 mm f Tube ID after rolling g t d e OS in f4 2 mm NOTE...

Page 19: ...l valve 3 Miswired solenoid 4 Weak broken or wrong valve body spring COMPRESSOR WILL NOT LOAD 1 Miswired solenoid 2 Defective capacity control valve 3 Plugged strainer high side 4 Stuck or damaged unl...

Page 20: ...s the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 2 I PC111 Catalog No 533 034 Printed in U S A Form 30GT ISI Pg 17 8 88...

Reviews: