background image

 

 

1 2 2 . 2 3  

   

D I A .   H O L E

D I A .  

 

 

 

  L 2 2 . 2 1  

  C I A .  

F I E L D  

 

F A C T O R Y  

  I S   I N   A C C O R O A N C E  

W I T H  

N A T I O N A L  

E L E C T R I C A L   C O D E

I N   E   C . ,    

  A N Y  

 

  O R   A D D I T I O N S   M U S T   B E  

C O M P L I A N C E   W I T H   A L L   A P P L I C A B L E   C O D E S .

2 .  

  S E P A R A T E   S O U R C E  

 

 

 

 

 

  J S E D   3  

 

 

 

      O

F

 

 

 

 

 

  T O  

 

7 .  

 

 

 

  T H E   U N I T

C O N T R O L  

 

 

 

 

 

3 .   A L L  

 

 

 

 

 

 

  3 6 3   V A

 

 

 

 

 

 

 

 

LEGEND:

 

 

 

 

 

 

 

 

  S T A R T E R

 

 

START-UP

5.

Initial Check

 Do not attempt to start the liquid

chiller, even momentarily, until the following steps have
been completed.

1. Check all auxiliary components such as chilled Iiquid

circulating pump, air handling equipment, or other
equipment to which the chiller supplies liquid. Con-

sult the manufacturer’s instructions. If used, pump

auxiliary 

contactor 

and flow switch interlocks must

be properly installed (see Fig. 8, Typical Wiring
Schematic).

7.
8.

9.

10.

11.

2. Check chilled water safety thermostat. See Safety

Thermostat (page 12) for adjustment.

3. Backseat 

(open) compressor  suction  and discharge

shutoff valves. Close valves one turn to allow pres-
sure to reach test gages.

4. Open liquid line valve.

5. Fill chilled liquid circuit with clean water (with rec-

ommended inhibitor added) to be cooled. Bleed all

air out of high points of system.

12.

13.

Fig. 8 

 Wiring Schematic

Set temperature controller (see Multiple-Step

Controller).
Check tightness of all electrical connections.
Compressor oil should be visible in sightglass (see Oil
Charge).

Be sure there are no refrigerant leaks (see Leak Test

and Dehydration).

Be sure unit is fully charged with refrigerant (see
Refrigerant Charge).
Electrical power source must agree with nameplate
rating.
Crankcase heater must  be  firmly locked into com-
pressor crankcase. 

Be 

sure crankcase is warm (heater

should be on for 24 hours before starting compressor).
Be sure compressor floats freely on the mounting
springs. See Compressor Mounting section and Fig. 3
for  loosening compressor bolts.

9

Summary of Contents for 30GT 015

Page 1: ...quipment Rigging Preferred method is with spreader bars from above the unit Use Z in 50 mm 0 D pipe or hooks in lifting holes Rig with 4 cables and spreader bars Al1 panels must be in place when riggi...

Page 2: ...see clearance dimensions in Fig 5 6 7 For multiple units allow 8ft separation between units for airflow and service Mounting Unit When unit is in proper location use of mounting holes in base rails is...

Page 3: ...beginning of next chilling season refill cooler and add recommended inhibitor Power Supply Electrical characteristics of avail able power supply must agree with unit nameplate rating Supply voltage mu...

Page 4: ...lled water line to prevent unit from running when water is not circulating through the cooler This switch no HR8 1 LG005 is available as an accessory from Service Parts Center or equivalent can be fie...

Page 5: ...OPER WT Ib AT SUPPORT POINTS 6OHz 1 2 3 4 Tot 0 1 5 5 1 0 3 7 6 4 3 4 3 2 0 1 6 4 0 015C 5 3 9 3 9 7 4 5 8 3 3 8 1 7 3 2 0 2 0 574 1 4 2 3 4 7 4 3 5 0 1821 02OC 6 1 3 451 5 0 7 3 7 4 1945 50 Hz 4 3 9...

Page 6: ...G T O P V I E W AIRFLOW IHRU 5 4 MIN CLEARANCE FOR C O O L E R R E M O V A L WATER OUTLET 2 FPT c OF COOLER NOZZLE5 WAltK UKAIN 4 6 5 8 C23881 7 IO L324 71 J lo 7 13 16 6 5 8 4 SIDE VIEW wing 30GT015...

Page 7: ...0GT030 2 2 6 8 1 0 2 9 30GT030C 2 4 7 4 1 1 2 2 50 HZ NOTE C INDICATES COPPER COIL 1 cl3153 4 3 3 c i APPROX OPER WT Ib AT SU PPORT POINTS HINGED ACCESS b 1 c e i C2353 9 l 4 I 119 11 END VIEW 3 4 DIA...

Page 8: ...I A UPPLY JR TOP VIEW AIRFLOW THRW t 122353 f 7 4 MIN CLEARANCE FOR COOLER REMOVAL a WATER OUTlET 1 8 0 H 1 I I I 1 880 MTG H O L E S i kl Q 7 IO __ f8121 2 7 1S l6 6 S S 8 IO 7 13 1Ei S I D E V I E W...

Page 9: ...CATES COPPER COIL CONTROL BOX 22 23 7 8 D I A FIELD CONTROL CIRCUIT HIRING 63 5 92 13 2 l 2 3 5 B FIELD MAIN PC WER SUPPLY APPROX OPER WT lb AT SUPPORT POINTS HINGED ACCESS DOOR HATER I N L E T 2 l 2...

Page 10: ...OP VIEW IRFLOW THRU ONDENSER FAN No aB 28451 9 4 MIN CLEARANCE FOR COOLER REMOVAL i_ 12584lt 8 5 3 4 4 f1693 6 5 8 t OF COOLER DRAIN El6991 4 2 1 s El1 C44241 14 6 l 8 S I D E V I E W dimensional Draw...

Page 11: ...plied to unit terminals is not below or above listed minimum and maximum timits TAll fans are protected by a single circuit breaker the IRA for the starting compressor plus the total RLA for all runni...

Page 12: ...ment or other equipment to which the chiller supplies liquid Con sult the manufacturer s instructions If used pump auxiliary contactor and flow switch interlocks must be properly installed see Fig 8 T...

Page 13: ...gle switch to START Be sure all safety devices are satisfied Check to see that the leaving chilled water tempera ture agrees with the dial setting on the temperature controller If it is not the same a...

Page 14: ...n moderately without torquing all the flange bolts in the sequence shown Step 2 Repeat Step 1 tightening the bolts to the specified torque JcJ Fig 11 Tightening Sequence Cooler Head Bolts ik l Line So...

Page 15: ...mpressor stops and the liquid line solenoid valve de energizes Manual reset is required to restart The chilled water circulating pump continues to operate during lockout period WINTER SHUTDOWN At the...

Page 16: ...n and allow the unit to run through a cycle At the instant the last step of capacity unloads switch no 1 opens read the tempera ture If it is not the same as the dial reading the variation can be comp...

Page 17: ...gh pressure switch HPS open low water temperature cutout LWTC RESTART The unit recycles and restarts automati cally under Time Guard control when power is restored or when SW is closed or when contact...

Page 18: ...U U05 in 0 I3 mm d Tube ID before rolling use Elliott tube gage 0 549 ip 13 9 mm e S of twice the wall thickness S9 s of b minus d 0 004 in 0 10 mm f Tube ID after rolling g t d e OS in f4 2 mm NOTE...

Page 19: ...l valve 3 Miswired solenoid 4 Weak broken or wrong valve body spring COMPRESSOR WILL NOT LOAD 1 Miswired solenoid 2 Defective capacity control valve 3 Plugged strainer high side 4 Stuck or damaged unl...

Page 20: ...s the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 2 I PC111 Catalog No 533 034 Printed in U S A Form 30GT ISI Pg 17 8 88...

Reviews: