INSTALLATION

Specifications for this unit in residential new construction market
require the outdoor unit, indoor unit, refrigerant tubing sets,

metering device, and filter drier listed in presale literature. There
can be no deviation. Consult the Application Guideline and

Service Manual – Air Conditioners and Heat Pumps Using

Puron

r

Refrigerant to obtain required unit changes for specific

applications and for R--22 retrofit.

STEP 1. —

Check Equipment and Job Site

UNPACK UNIT

Move to final location. Remove carton taking care not to damage

unit.

INSPECT EQUIPMENT

File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner

panel. It contains information needed to properly install unit.

Check rating plate to be sure unit matches job specifications.

STEP 2. —

Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts

provided in unit base pan. Refer to unit mounting pattern in Fig.
3 to determine base pan size and knockout hole location.
For hurricane tie downs -- contact your local distributor for
details and PE (Professional Certification), if required by local

authorities.
On rooftop applications, mount on level platform or frame. Place
unit above a load--bearing wall and isolate unit and tubing set

from structure. Arrange supporting members to adequately
support unit and minimize transmission of vibration to building.

Consult local codes governing rooftop applications.
Roof mounted units exposed to winds may require wind baffles.
Consult the Application Guideline and Service Manual --

Residential Split System Air Conditioners and Heat Pumps Using
Puron

r

Refrigerant for wind baffle construction.

NOTE

: Unit must be level to within

±

2

_

(

±

3/8 in./ft.) per

compressor manufacturer specifications.

STEP 3. —

Clearance Requirements

When installing, allow sufficient space for airflow clearance,

wiring, refrigerant piping, and service. Allow 30--in. clearance to
service end of unit and 48 in. above unit. For proper airflow, a

6--in. clearance on 1 side of unit and 12 in. on all remaining sides
must be maintained. Maintain a distance of 24 in. between units.

Position so water, snow, or ice from roof or eaves cannot fall

directly on unit.

3/8---in. Dia. Tiedown

Knockouts in Basepan

(2) Places

View From Top

UNIT BASE PAN

DIMENSIONS

TIEDOWN KNOCKOUT LOCATIONS

A

B

C

26 X 26

9–1/8

4–7/16

21–1/4

31–1/2 X 31–1/2

9–1/8

6–9/16

24–11/16

35 X 35

9–1/8

6–9/16

28–7/16

A05177

Fig. 3 ---

Tiedown Knockout Locations

On rooftop applications, locate unit at least 6 in. above roof

surface.

STEP 4. —

Operating Ambient

The minimum outdoor operating ambient in cooling mode is
55

_

F, and the maximum outdoor operating ambient in cooling

mode is 125

_

F.

STEP 5. —

Install TXV

NOTE

: Applies to non--TXV and R--22 TXV indoor units only.

If installing a rated and approved indoor coil without a factory
installed Puron

R

TXV, remove and replace the fixed orifice or

R--22 TXV expansion device with a hard shutoff Puron TXV.
The thermostatic expansion valve is specifically designed to

operate with Puron. Do not use an R--22 TXV. An existing R--22

TXV must be replaced with a factory--approved TXV specifically
designed for Puron. Refer to Product Data Sheet for the

appropriate TXV kit number.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To avoid improper performance and possible

equipment failure, all indoor coil units must be

installed with a hard shut off Puron

R

TXV metering

device.

IMPORTANT

: The TXV should be mounted as close to the

indoor coil as possible and in a vertical, upright position. Avoid
mounting the inlet tube vertically down. Valve is more
susceptible to malfunction due to debris if inlet tube is facing
down. A factory--approved filter drier must be installed in the
liquid line.

24AC

A

Summary of Contents for 24ACA

Page 1: ...2 INSTALLATION 3 9 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Make Piping Connections 4 7...

Page 2: ...rate at higher pressures than standard R 22 systems To avoid damage to the unit or possible personal injury do not use R 22 service equipment or components on Puron equipment INSTALLATION RECOMMENDATI...

Page 3: ...ufacturer specifications STEP 3 Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 30 in clearance to service end of unit a...

Page 4: ...placing TXV on R 22 Indoor Coil 1 Pump system down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabinet 3 Remove TXV support clamp using a 5 16 in nut d...

Page 5: ...nd condition Rated tubing diameters shown in Table 1 recommended up to 80 ft See Product Data for acceptable alternates vapor diameters and associated capacity losses For tubing requirements beyond 80...

Page 6: ...the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 liquid tube Flow arrow must point towards indoor coil 4 Connect and braze liquid refrigerant tube to the filter dri...

Page 7: ...utdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close attention to feeder tubes making sure wire ties on feeder tubes are secure and...

Page 8: ...ine Section Residential Split System Air Conditioners and Heat Pumps Using Puronr Refrigerant STEP 9 Install Electrical Accessories Refer to the individual instructions packaged with kits or accessori...

Page 9: ...cial charging requirements EXAMPLE To calculate additional charge required for a 25 ft line set 25 ft 15 ft 10 ft X 0 6 oz ft 6 oz of additional charge COOLING ONLY PROCEDURE This system requires char...

Page 10: ...ons On On On Off Off Off No 230V power to unit Check 230V disconnect circuit breaker Check 230V L1 L2 wire connections On On On On Off Off Contactor open Check Contactor and replace if necessary Check...

Page 11: ...8 76 74 72 70 68 266 80 78 76 74 72 70 274 82 80 78 76 74 72 283 84 82 80 78 76 74 291 86 84 82 80 78 76 299 88 86 84 82 80 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96...

Page 12: ...s S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S...