background image

5

STEP 6. —

Make Piping Connections

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD

Failure to follow this warning could result in personal

injury or death.
Relieve pressure and recover all refrigerant before

system repair or final unit disposal to avoid personal

injury or death. Use all service ports and open all

flow--control devices, including solenoid valves.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To prevent improper performance and/or unit component

failures, do not leave system open to atmosphere any longer

than minimum required for installation. POE oil in

compressor is extremely susceptible to moisture absorption.

Always keep ends of tubing sealed during installation.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6 in. vertical

rise at service valve. Refrigerant tubing lengths up to 36 in.

may be buried without further special consideration. Do

not bury lines longer than 36 in.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To prevent damage to unit or service valves observe the

following:

S

Use a brazing shield.

S

Wrap service valves with wet cloth or use a heat sink

material.

Outdoor units may be connected to indoor section using

accessory tubing package or field--supplied refrigerant grade

tubing of correct size and condition. Rated tubing diameters
shown in Table 1 recommended up to 80 ft. See Product Data

for acceptable alternates vapor diameters and associated capacity
losses. For tubing requirements beyond 80 ft., substantial

capacity and performance losses can occur. Following the

recommendations in the Longline Guideline -- Residential
Split--System Air Conditioners and Heat Pumps Using Puron

r

Refrigerant will reduce these losses. Refer to Table 1 for field
tubing diameters. Refer to Table 2 for accessory requirements.
There are no buried--line applications greater than 36 in.
If refrigerant tubes or indoor coil are exposed to atmosphere, they

must be evacuated to 500 microns to eliminate contamination and

moisture in the system.

OUTDOOR UNIT CONNECTED TO FACTORY---AP-

PROVED INDOOR UNIT:

Outdoor unit contains correct system refrigerant charge for

operation with factory approved ARI rated indoor unit when
connected by 15 ft. of field--supplied or factory--accessory tubing,

and factory supplied filter drier. Check refrigerant charge for
maximum efficiency.

Table 1—Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)

UNIT SIZE

LIQUID

RATED VAPOR

(up to 80 ft. *)

Connection

Diameter

Tube

Diameter

Connection

Diameter

Tube

Diameter

018, 024

3/8

3/8

5/8

5/8

030, 036

3/8

3/8

3/4

3/4

042, 048

3/8

3/8

7/8

7/8

060

3/8

3/8

7/8

1---1/8

Notes:

1. Tube diameters are for total equivalent lengths up to 80 ft..

2. Do not apply capillary tube or fixed orifice indoor coils to these units.
* For Tubing Set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (250 ft.Total Equivalent Length), refer to the Longline Guideline--- Air

Conditioners and Heat Pumps using Puron.

24AC

A

Summary of Contents for 24ACA

Page 1: ...2 INSTALLATION 3 9 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Make Piping Connections 4 7...

Page 2: ...rate at higher pressures than standard R 22 systems To avoid damage to the unit or possible personal injury do not use R 22 service equipment or components on Puron equipment INSTALLATION RECOMMENDATI...

Page 3: ...ufacturer specifications STEP 3 Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 30 in clearance to service end of unit a...

Page 4: ...placing TXV on R 22 Indoor Coil 1 Pump system down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabinet 3 Remove TXV support clamp using a 5 16 in nut d...

Page 5: ...nd condition Rated tubing diameters shown in Table 1 recommended up to 80 ft See Product Data for acceptable alternates vapor diameters and associated capacity losses For tubing requirements beyond 80...

Page 6: ...the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 liquid tube Flow arrow must point towards indoor coil 4 Connect and braze liquid refrigerant tube to the filter dri...

Page 7: ...utdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close attention to feeder tubes making sure wire ties on feeder tubes are secure and...

Page 8: ...ine Section Residential Split System Air Conditioners and Heat Pumps Using Puronr Refrigerant STEP 9 Install Electrical Accessories Refer to the individual instructions packaged with kits or accessori...

Page 9: ...cial charging requirements EXAMPLE To calculate additional charge required for a 25 ft line set 25 ft 15 ft 10 ft X 0 6 oz ft 6 oz of additional charge COOLING ONLY PROCEDURE This system requires char...

Page 10: ...ons On On On Off Off Off No 230V power to unit Check 230V disconnect circuit breaker Check 230V L1 L2 wire connections On On On On Off Off Contactor open Check Contactor and replace if necessary Check...

Page 11: ...8 76 74 72 70 68 266 80 78 76 74 72 70 274 82 80 78 76 74 72 283 84 82 80 78 76 74 291 86 84 82 80 78 76 299 88 86 84 82 80 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96...

Page 12: ...s S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S...

Reviews: