background image

6

Table 2—Accessory Usage

Accessory

REQUIRED FOR LOW---AMBI-

ENT APPLICATIONS

(Below 55

°

F

)

REQUIRED FOR LONG LINE

APPLICATIONS* (Over 80 Ft.)

REQUIRED FOR SEA

COAST APPLICATIONS

(Within 2 miles)

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes

{

No

No

Accumulator

No

No

No

Compressor Start Assist Capacitor

and Relay

Yes

Yes

No

Motor Master

®

Control

or

Low---ambient Pressure Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

Liquid Line Solenoid Valve

No

See Long---Line Application

Guideline

No

Ball Bearing Fan Motor

Yes

}

No

No

* For Tubing Set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (250 ft. Total Equivalent Length), refer to the Longline

Guideline --- Air Conditioners and Heat Pumps using Puron

}

Required for low---ambient controller (full modulation feature) and Motor Master

control only.

INSTALL LIQUID---LINE FILTER DRIER INDOOR

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
To avoid performance loss and compressor failure, installation

of filter drier in liquid line is required.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To avoid filter drier damage while brazing, filter drier must

be wrapped in a heat---sinking material such as a wet

cloth.

Refer to Fig. 5 and install filter drier as follows:

1. Braze 5--in. liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5” liquid tube. Flow arrow

must point towards indoor coil.

4. Connect and braze liquid refrigerant tube to the filter drier.

A05178

Fig. 5 ---

Liquid Line Filter Drier

REFRIGERANT TUBING CONNECTION OUTDOOR

Connect vapor tube to fitting on outdoor unit vapor service
valves (see Table 1.) Connect and braze the 3/8” coupling

(provided with the filter drier) to the liquid service valve and
connect and braze the liquid tubing to the other end of this

coupling. Use refrigerant grade tubing.

SWEAT CONNECTION

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To avoid valve damage while brazing, service valves

must be wrapped in a heat--sinking material such as a

wet cloth.

Service valves are closed from factory and ready for brazing.
After wrapping service valve with a wet cloth, braze sweat

connections using industry accepted methods and materials.
Consult local code requirements. Refrigerant tubing and indoor

coil are now ready for leak testing. This check should include all

field and factory joints.

EVACUATE REFRIGERANT TUBING AND INDOOR COIL

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To avoid compressor damage, never use the system

compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the

recommended deep vacuum method of 500 microns. The
alternate triple evacuation method may be used if the procedure

outlined below is followed. Always break a vacuum with dry

nitrogen.

24AC

A

Summary of Contents for 24ACA

Page 1: ...2 INSTALLATION 3 9 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Make Piping Connections 4 7...

Page 2: ...rate at higher pressures than standard R 22 systems To avoid damage to the unit or possible personal injury do not use R 22 service equipment or components on Puron equipment INSTALLATION RECOMMENDATI...

Page 3: ...ufacturer specifications STEP 3 Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 30 in clearance to service end of unit a...

Page 4: ...placing TXV on R 22 Indoor Coil 1 Pump system down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabinet 3 Remove TXV support clamp using a 5 16 in nut d...

Page 5: ...nd condition Rated tubing diameters shown in Table 1 recommended up to 80 ft See Product Data for acceptable alternates vapor diameters and associated capacity losses For tubing requirements beyond 80...

Page 6: ...the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 liquid tube Flow arrow must point towards indoor coil 4 Connect and braze liquid refrigerant tube to the filter dri...

Page 7: ...utdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close attention to feeder tubes making sure wire ties on feeder tubes are secure and...

Page 8: ...ine Section Residential Split System Air Conditioners and Heat Pumps Using Puronr Refrigerant STEP 9 Install Electrical Accessories Refer to the individual instructions packaged with kits or accessori...

Page 9: ...cial charging requirements EXAMPLE To calculate additional charge required for a 25 ft line set 25 ft 15 ft 10 ft X 0 6 oz ft 6 oz of additional charge COOLING ONLY PROCEDURE This system requires char...

Page 10: ...ons On On On Off Off Off No 230V power to unit Check 230V disconnect circuit breaker Check 230V L1 L2 wire connections On On On On Off Off Contactor open Check Contactor and replace if necessary Check...

Page 11: ...8 76 74 72 70 68 266 80 78 76 74 72 70 274 82 80 78 76 74 72 283 84 82 80 78 76 74 291 86 84 82 80 78 76 299 88 86 84 82 80 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96...

Page 12: ...s S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S...

Reviews: