background image

4

Installing TXV in Place of Piston

1. Pump system down to 2 psig and recover refrigerant.
2. Remove hex nut from piston body. Use backup wrench on

fan coils.

3. Remove and discard factory--installed piston. Be sure

Teflon seal is in place.

4. Reinstall hex nut. Finger tighten nut plus 1/2 turn.

NOTE

: If the piston is not removed from the body, TXV will not

function properly.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To prevent damage to the unit, use a brazing shield

and wrap TXV with wet cloth or use heat sink

material.

5. Install TXV on indoor coil liquid line. Sweat swivel

adapter to inlet of indoor coil and attach to TXV outlet.
Use backup wrench to avoid damage to tubing or valve.

Sweat inlet of TXV, marked “IN” to liquid line. Avoid
excessive heat which could damage valve.

6. Install vapor elbow with equalizer adapter to suction tube

of line set and suction connection to indoor coil. Adapter
has a 1/4--in. male connector for attaching equalizer tube.

7. Connect equalizer tube of TXV to 1/4--in. equalizer fitting

on vapor line adapter.

8. Attach TXV bulb to horizontal section of suction line

using clamps provided. Insulate bulb with field--supplied
insulation tape. See Fig. 4 for correct positioning of

sensing bulb.

9. Proceed with remainder of unit installation.

2 O’CLOCK

10 O’CLOCK

SENSING BULB

STRAP

SUCTION TUBE

8 O’CLOCK

4 O’CLOCK

IN. OD & SMALLER

LARGER THAN 7/8 IN. OD

7/8

A81032

Fig. 4 ---

Position of Sensing Bulb

Replacing TXV on R---22 Indoor Coil

1. Pump system down to 2 psig and recover refrigerant.
2. Remove coil access panel and fitting panel from front of

cabinet.

3. Remove TXV support clamp using a 5/16--in. nut driver.

Save the clamp.

4. Remove R--22 TXV using a backup wrench on flare

connections to prevent damage to tubing.

5. Using wire cutters, cut equalizer tube off flush with vapor

tube inside cabinet.

6. Remove bulb from vapor tube inside cabinet.
7. Braze equalizer stub--tube closed. Use protective barrier as

necessary to prevent damage to drain pan.

IMPORTANT

: Route the equalizer tube of Puron TXV through

suction line connection opening in fitting panel prior to replacing
fitting panel around tubing.

8. Install TXV with 3/8--in. copper tubing through small hole

in service panel. Use wrench and backup wrench, to avoid
damage to tubing or valve, to attach TXV to distributor.

9. Reinstall TXV support clamp (removed in item 3).

10. Attach TXV bulb to vapor tube inside cabinet, in same

location as original was when removed, using supplied
bulb clamps (nylon or copper). See Fig. 4 for correct
positioning of sensing bulb.

11. Route equalizer tube through suction connection opening

(large hole) in fitting panel and install fitting panel in

place.

12. Sweat inlet of TXV, marked “IN” to liquid line. Avoid

excessive heat which could damage valve.

13. Install vapor elbow with equalizer adapter to vapor line of

line set and vapor connection to indoor coil. Adapter has

a 1/4--in. male connector for attaching equalizer tube.

14. Connect equalizer tube of TXV to 1/4--in. equalizer fitting

on vapor line adapter. Use backup wrench to prevent
damage to equalizer fitting.

15. Proceed with remainder of unit installation.

24AC

A

Summary of Contents for 24ACA

Page 1: ...2 INSTALLATION 3 9 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Make Piping Connections 4 7...

Page 2: ...rate at higher pressures than standard R 22 systems To avoid damage to the unit or possible personal injury do not use R 22 service equipment or components on Puron equipment INSTALLATION RECOMMENDATI...

Page 3: ...ufacturer specifications STEP 3 Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 30 in clearance to service end of unit a...

Page 4: ...placing TXV on R 22 Indoor Coil 1 Pump system down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabinet 3 Remove TXV support clamp using a 5 16 in nut d...

Page 5: ...nd condition Rated tubing diameters shown in Table 1 recommended up to 80 ft See Product Data for acceptable alternates vapor diameters and associated capacity losses For tubing requirements beyond 80...

Page 6: ...the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 liquid tube Flow arrow must point towards indoor coil 4 Connect and braze liquid refrigerant tube to the filter dri...

Page 7: ...utdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close attention to feeder tubes making sure wire ties on feeder tubes are secure and...

Page 8: ...ine Section Residential Split System Air Conditioners and Heat Pumps Using Puronr Refrigerant STEP 9 Install Electrical Accessories Refer to the individual instructions packaged with kits or accessori...

Page 9: ...cial charging requirements EXAMPLE To calculate additional charge required for a 25 ft line set 25 ft 15 ft 10 ft X 0 6 oz ft 6 oz of additional charge COOLING ONLY PROCEDURE This system requires char...

Page 10: ...ons On On On Off Off Off No 230V power to unit Check 230V disconnect circuit breaker Check 230V L1 L2 wire connections On On On On Off Off Contactor open Check Contactor and replace if necessary Check...

Page 11: ...8 76 74 72 70 68 266 80 78 76 74 72 70 274 82 80 78 76 74 72 283 84 82 80 78 76 74 291 86 84 82 80 78 76 299 88 86 84 82 80 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96...

Page 12: ...s S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S...

Reviews: