background image

10

TechAssist

Diagnostics---at---a---Glance

This system is equipped with a system diagnostics tool called the TechAssist

t

. Follow Table 3 to identify and correct problems in system

operation.

Table 3—

TechAssist

t

Diagnostics---at---a---Glance

LED

Description

ON

OFF

Y

Thermostat cooling call

Yes

No

. . . . . . . . . . .

. . . . . . . . .

. . . . . . . .

HPS

High Pressure Switch

Closed

Open

. . . . . . . .

. . . . . . . . . . .

. . . . .

LPS

Low Pressure Switch

Closed

Open

. . . . . . . . .

. . . . . . . . . . . .

. . . . .

230V

AC Line Power Available

Yes

No

. . . . . . . .

. . . . . . . . .

. . . . . . . .

Contactor

Contactor Energized

Yes

No

. . .

. . . . . . . . . . .

. . . . . . . .

Compressor Compressor Running

Yes

No

.

. . . . . . . . . . .

. . . . . . . .

Y

HPS

LPS

230V Contactor Compressor

CONTROL

POWER

Note: --- Follow arrows to first unlit LED in control (green) ladder or power (amber) ladder to determine problem area.

*** --- For contactor LED to be On, all control LEDs (green) as well as 230V LED (amber) must already be on, and contactor must operate . . . . .

properly

Control Ladder

Power ladder

Indication

Possible Cause & Quick

Trouble---Shooting

Green LEDs

Amber LEDs

Y

HPS LPS 230V Contac-

tor

Compressor

Off

Off

Off

Off

Off

Off

--- No 230V power to unit

--- No thermostat call

--- Check 230V disconnect/ circuit breaker

--- Check 230V L1 & L2 wire connections

On

Off

Off

--- ---

Off

Off

--- HPS Switch Open

--- Check pressures

--- Check HPS wire connections

On

On

Off

--- ---

Off

Off

--- LPS Switch Open

--- Check pressures

--- Check LPS wire connections

On

On

On

Off

Off

Off

--- No 230V power to unit

--- Check 230V disconnect / circuit breaker

--- Check 230V L1 & L2 wire connections

On

On

On

On

Off

Off

--- Contactor open ***

--- Check Contactor and replace if necessary

--- Check contactor wire connections

On

On

On

On

On

Off

--- Compressor not running*

--- Check for compressor protector trip, capacitor

fault, faulty connections or compressor fault.

SEE BELOW.

On

On

On

On

On

On

--- Compressor running

--- OK

Off

Off

Off

On

Off

Off

--- No thermostat call, standby --- OK

Off

Off

Off

On

On

Off

--- Contactor stuck closed,

compressor tripped

--- Check Contactor and replace if necessary

--- Check wire connections for shorts

Off

Off

Off

On

On

On

--- Contactor stuck closed,

compressor running

--- Check Contactor and replace if necessary

--- Check wire connections for shorts

*Compressor not running: If all LEDs are on except the Compressor, this indicates that power is applied to the compressor but it is not running. Check the

following sequence:

1) Check all compressor wire connections

2) Check run capacitor and replace if necessary

3) Try starting compressor

4) If compressor LED does not come on, then leave unit in standby for up to four hours to allow thermal protector to reset, and all pressures to equalize

5) Try starting the compressor again

6) If compressor LED comes on, then turns off quickly, investigate starting issues such as low line voltage

7) If compressor LED never comes on, compressor may be faulty.

24AC

A

Summary of Contents for 24ACA

Page 1: ...2 INSTALLATION 3 9 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Make Piping Connections 4 7...

Page 2: ...rate at higher pressures than standard R 22 systems To avoid damage to the unit or possible personal injury do not use R 22 service equipment or components on Puron equipment INSTALLATION RECOMMENDATI...

Page 3: ...ufacturer specifications STEP 3 Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 30 in clearance to service end of unit a...

Page 4: ...placing TXV on R 22 Indoor Coil 1 Pump system down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabinet 3 Remove TXV support clamp using a 5 16 in nut d...

Page 5: ...nd condition Rated tubing diameters shown in Table 1 recommended up to 80 ft See Product Data for acceptable alternates vapor diameters and associated capacity losses For tubing requirements beyond 80...

Page 6: ...the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 liquid tube Flow arrow must point towards indoor coil 4 Connect and braze liquid refrigerant tube to the filter dri...

Page 7: ...utdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close attention to feeder tubes making sure wire ties on feeder tubes are secure and...

Page 8: ...ine Section Residential Split System Air Conditioners and Heat Pumps Using Puronr Refrigerant STEP 9 Install Electrical Accessories Refer to the individual instructions packaged with kits or accessori...

Page 9: ...cial charging requirements EXAMPLE To calculate additional charge required for a 25 ft line set 25 ft 15 ft 10 ft X 0 6 oz ft 6 oz of additional charge COOLING ONLY PROCEDURE This system requires char...

Page 10: ...ons On On On Off Off Off No 230V power to unit Check 230V disconnect circuit breaker Check 230V L1 L2 wire connections On On On On Off Off Contactor open Check Contactor and replace if necessary Check...

Page 11: ...8 76 74 72 70 68 266 80 78 76 74 72 70 274 82 80 78 76 74 72 283 84 82 80 78 76 74 291 86 84 82 80 78 76 299 88 86 84 82 80 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96...

Page 12: ...s S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S...

Reviews: