version of this signal is also provided (113).
Current Feedback (IFB, 102, filtered-112, Read-Only)
The
Current Feedback
is derived from two of the three incoming AC lines and is used by the
PI loop to regulate the amount of armature current in the motor. The signal is also used to
provide
IR Compensation
to the AFB signal in the Velocity Loop. A filtered version of this
signal is also provided (112).
Current Error (103, Read-Only)
The
Final Current Demand
and the
Current Feedback
sum together to form the
Current
Error
signal for the PI loop.
Current Proportional Gain (107)
The
Current
Proportional Gain
scales the output based upon the
Current Error
. Increasing
the gain improves the response of the drive but can also increase overshoot.
Current Integral Time (108)
The
Current Integral Time
adjustment eliminates steady-state error. Decreasing the integral
time improves the response of the drive. However, setting it too low can cause oscillation.
The adjustment is in seconds and corresponds to the amount of time that the signal would
take to integrate from 0 to maximum with 100%
Current
Error
.
Regen Mode (206, ICR)
When set to False, the
Regen Mode
parameter allows Elite Pro Regenerative models to
emulate a non-regen drive by clamping the negative portions of the Velocity Integral and
Current Integral signals. On non-regen drives, this parameter is ignored.
Open Loop Armature Select (104, ICR)
When set to True, the conduction angle sent to the trigger board can be manually controlled
by
Open Loop Armature Setpoint
. This diagnostic tool can be used to eliminate the Velocity
and Current Loops from the control. Care must be taken when using this mode because there
is no current limit protection. Remember to set this parameter back to False once diagnosis is
complete.
Open Loop Armature Setpoint (105)
When
Open Loop Armature Select
is True,
Open Loop Armature Setpoint
sets the
Conduction Angle
directly. The
Ramp Output
parameter writes to this parameter in the
factory preset configuration.
Conduction Angle (106, Read-Only)
Normally the
Conduction Angle
is the output of the Current Loop. However, if
Open Loop
Armature Select
is True, the
Conduction Angle
equals
Open Loop Armature Setpoint
.
This signal controls the SCRs in the armature bridge circuit.
Armature Amps (114, Read-Only)
Armature Amps
displays the actual motor current from the
Filtered Current Feedback
signal and the
Nameplate Motor Current
parameters.
Summary of Contents for Elite Pro EPN020-000
Page 10: ...10 Figure 4 ...
Page 80: ...80 Prints ...
Page 81: ...81 ...
Page 82: ...82 ...
Page 83: ...83 ...
Page 85: ...85 ...
Page 88: ...88 ...
Page 89: ...89 ...
Page 90: ...90 ...
Page 91: ...91 ...
Page 92: ...92 ...
Page 93: ...93 ...
Page 94: ...94 ...
Page 95: ...95 ...
Page 96: ...96 ...
Page 97: ...97 ...
Page 98: ...98 ...
Page 99: ...99 ...
Page 100: ...100 ...
Page 101: ...101 ...
Page 102: ...102 ...
Page 103: ...103 ...
Page 104: ...104 ...
Page 105: ......
Page 106: ...106 PRO SOFT ...
Page 107: ...107 WARE BLOCK DIAGRAM ...
Page 108: ...108 ...