G38xx14 Configuration Software
Activation of master function
Selected Channel
status
Master
Channel
status
Master
channel type
before master
activated before
master
activated
switches
on
switches
off
Normal channel
0
1
1
tx
Note
1
Flip-flop/Real
time
0
1 1 0
Note
II
Timer On-delay
0
0 timer ->1
1
0
Note
III
Timer Off-delay
0
1 timer ->0
1
0
Note
III
Timer
Recycler toggles
1 toggles
0
Blank
channel 0
1 1 0
Note I:
When the master function deactivates, the status on the channel will reflect trans-
mission on the channel.
Note II:
Activation of a master channel can override a toggle on a Real time channel which
should have been caused by the clock.
Note III:
The On-delay channel does not activate until the master has been activated for
the On-delay period. The Off-delay timer will maintain the pulse until the Off-delay
has elapsed from the point of time when the master function is deactivated.
Roller blind functions
Roller blind up/down control
Operation:
Two interconnected channels for Up/Down control. A short transmission pulse on Up chan-
nel will cause the two outputs to switch on in “Up” direction for the defined time. A trans-
mission pulse longer than 1 sec causes the output to be manually controlled and will keep
the “Up” direction on, until transmission is released. If a Down-pulse is issued while running
in “Up” direction, the direction will change. Activating both up and down simultaneously will
be ignored. (Up and Down operations are similar to each other). To ensure safe operation of
the Up-Down control, the receiver G3430 4249 must be used.
Parameters:
Roll time 0 to 255 secs.
Reverse
delay
Delay before the roller blind changes direction for protection of motor and contacts.
The entered value cannot be lower than 500 ms. The min. allowable value can be seen
from the technical specifications of the motor.
Adjustment of tilting blinds
The function of adjustment of tilting blinds changes as follows:
Pulse < 5 s:
The motor runs for the duration of the pulse.
Pulse > 5 s:
The motor runs until stopped by a limit switch, unless a new short pulse is
given, the roll direction is changed or the motor is stopped by the roll time
control.
Setting of priority channels
Assignment of an address or flag by which the up-direction or the down-direction is given
priority. A priority signal blocks all other control signals for the motor. The selected channel
must transmit a continuous signal for the duration of the priority.