G38xx14 Configuration Software
Function Code 03: Read Multiple Registers
Register
Address
Register 16 bit
Dec Hex
Hi
Lo
0 0
B8..B1
A8..A1
Digital
1 1 D C
Digital
. . . .
.
6 6 N M
Digital
7 7 P O
Digital
Reads Dupline transmitters (DI).
Reading of 1 to 8 registers possible.
If an attempt is made to read from a start-address and the number of registers exceeds
the allowed register range, no answer will be made, as this is interpreted as an illegal
function
256 100 A1 0 0..255
Analink
257 101 A2 0 0..255
Analink
258 102 A3 0 0..255
Analink
. . . 0 0..255
Analink
382 17E P7 0 0..255
Analink
383 17F P8 0 0..255
Analink
Analog value only valid if channel is defined as an Analink sensor.
Reading of 1 to 8 registers possible
512 200 0 0..99 0..99 0..99 0..99 Counter
514 202 1 0..99 0..99 0..99 0..99 Counter
516 204 2 0..99 0..99 0..99 0..99 Counter
0..99 0..99 0..99 0..99 Counter
764 2FC 126 0..99 0..99 0..99 0..99 Counter
766 2FE
127 0..99 0..99 0..99 0..99 Counter
Counter value only valid if Counters are selected.
Reading of 1 to 8 registers allowed.
The response time for a Counter value may go up to 132 ms, to ensure data integrity
between all digits.
Dec Hex Mux Hi
Lo
Value
784 310 0
HI
LO
CD-0
Input
Table
785 311 1
HI
LO
CD-1
Input
Table
786 312 2
HI
LO
CD-2
Input
Table
787 313 3
HI
LO
CD-3
Input
Table
. . . . .
.
Input
Table
798 31E E
HI
LO
CD-E
Input
Table
799 31F F
HI
LO
CD-F
Input
Table
800 320 0
HI
LO
EF-0
Input
Table
815 32F F
HI
LO
EF-F
Input
Table
816 330 0
HI
LO
GH-0
Input
Table
831 33F F
HI
LO
GH-F
Input
Table
832 340 0
HI
LO
IJ-0
Input
Table
847 34F F
HI
LO
IJ-F
Input
Table
848 350 0
HI
LO
KL-0
Input
Table
863 35F F
Hi
LO
KL-F
Input
Table
864 360 0
HI
LO
MN-0
Input
Table
879 36F F
HI
LO
MN-F
Input
Table
880 370 0
HI
LO
OP-0
Input
Table
895 37F F
HI
LO
OP-F
Input
Table
1000 1000 B8-B1 A8-A1
Digital
1001 1001
D
C
Digital
.
.
Digital
4103 1007
P
O
Digital
4880 1310 0
HI
LO
CD-0
Output
Table
4881 1311 1
HI
LO
CD-1
Output
Table
4882 1312 2
HI
LO
CD-2
Output
Table
4883 1313 3
HI
LO
CD-3
Output
Table
. . . . .
.
Output
Table
4894 131
E
E HI LO
CD-E
Output
Table
4895 131F F
HI
LO
CD-F
Output
Table
4896 1320 0
HI
LO
EF-0
Output
Table
4911 132F F
HI
LO
EF-F
Output
Table
4912 1330 0
HI
LO
GH-0
Output
Table
4927 133F F
HI
LO
GH-F
Output
Table
4928 1340 0
HI
LO
IJ-0
Output
Table
4943 134F F
HI
LO
IJ-F
Output
Table
4944 1350 0
HI
LO
KL-0
Output
Table
4959 135F F
Hi
LO
KL-F
Output
Table
4960 1360 0
HI
LO
MN-0
Output
Table
4975 136F F
HI
LO
MN-F
Output
Table
4976 1370 0
HI
LO
OP-0
Output
Table
4991 137F F
HI
LO
OP-F
Output
Table
Multiplexed analog Read Input Table (AI)
Registers 0300H to 037FH BCD-VALUES
Resisters 0400H to 047FH BINARY-VALUES
Multiplexed analog values only valid if Multiplexer is selected
Reading of 1 to 8 registers possible
Dupline group AB holds the actual Mux-address on the 4 most significant bits. The
remaining bits holds the digital transmit information from channel A5..B8
Reads Dupline Receivers (DO).
Reading of 1 to 8 registers possible.
If an attempt is made to read from a start-address and the number of registers exceeds the
allowed register range, no answer will be made, as this is interpreted as an illegal function
Multiplexed analog Read Output Table (AO)
Registers 1310H to 137FH BCD-VALUES
Resisters 1400H to 147FH BINARY-VALUES
Multiplexed analog values only valid if Multiplexer is selected
Reading of 1 to 8 registers possible
2000 Carlo Gavazzi Industri A/S. All rights reserved.
32