background image

MN99102  042015

– 10 –

Model 99FRD, 102CRD & EZ-66 Oil Burners — Instruction Manual

3.  Prepare Burner 

(continued)

  Inspect the nozzle adapter before replacing the nozzle. If the 

threads have been damaged or show score marks, replace 
the nozzle line/adapter assembly.

4.  Replace the retention ring assembly by slipping one of the riveted arms 

through the gap between the electrode tips. Align this arm straight up, 
with the ring clamp firmly against the nozzle adapter shoulder (see 
Figure 10). Then tighten the clamping screw.

5.  Reposition and check the electrode settings. Position the electrodes as 

shown in Figure 10. These settings are critical in ensuring a reliable 
ignition. Once the electrodes are set, check all clamps to be sure they 
are securely tightened.

6.  Insert the combustion head/nozzle assembly in the burner.

Check zero position 

(99FRD only)

1.  See Figures 11, 12 and 13. Loosen the oil line thumb nut and adjusting 

slide locking screw. Use a 

B\cx

" Allen wrench to rotate the adjusting 

screw until the lead edge of the slide aligns to “0” on the scale. The 
retention ring should be flush, or nearly flush, with the edge of the 
throttling ring.

2.  If the retention ring is not close to flush with the throttle ring, make 

sure the air tube is completely inserted into the housing collar and the 
retention ring clamp is firmly against the nozzle adapter shoulder.

Set initial burner air settings

Combustion head
1.  The combustion head adjusting slide controls the spacing between the 

retention ring and throttle ring (or air cone), regulating how much air 
passes around the retention ring.

2.  Loosen the oil line thumb nut and adjusting slide locking screw. Use a 

B\cx

" Allen wrench to rotate the adjusting screw until the lead edge of 

the slide aligns to the number given in Table 3, page 11. Lock in place 
by first tightening the oil line thumbnut, then tightening the locking 
screw.

Air shutter
1.  The air shutter is fixed for all 99FRD, EZ-66 and 102CRD burners. See 

page 7 for the correct air shutter type. (Some 102CRD burners may 
be equipped with 3-slot air shutters.)

Air band
1.  The air band is marked in percent opening. Loosen the air band locking 

screw and move the air band until the pointer lines up with the percent 
opening given in Table 3, page 11.

Final adjustments
1.  The burner is now adjusted to the approximate air settings for the firing 

rate chosen. When you check combustion with instruments during start-
up or servicing, you may have to adjust the head slightly to achieve the 
desired efficiency. See “Adjust burner using test instruments,” page 22. 
( Note that pressure overfire will reduce air flow, requiring more air 
opening.)

Figure 11  Check zero position — 99FRD only

Figure 10  Combustion head/nozzle/electrode settings

Figure 12  Combustion head and air band adjutsments

Summary of Contents for 102CRD

Page 1: ...formation regarding operation of this burner The burner Instruction Manual is intended only for your service technician The burner and heat exchanger must be inspected and started at least annually by...

Page 2: ...pliance per this manual and the appliance instructions see User s information To keep this manual at or near the burner appliance for ready ac cess by the user and service technician To contact the se...

Page 3: ...ng GPH 0 50 to 3 00 2 00 to 3 50 3 00 to 4 50 Delavan Hollow 60 A Delavan Solid 60 B Hollow 70 A Solid 70 B Hago Hollow 60 H Solid 80 B Hollow 70 H Hago Semi solid 45 SS Monarch Hollow 60 NS Semi soli...

Page 4: ...ning sizes are always given in free area This means after deduction for louver obstruction If you can t find the louver reduction for the grilles used assume free area is 20 of total for wood louvers...

Page 5: ...sary clearances to combustible construction including the correct design of thimbles and insulation where penetrating combustible walls Illustrations A to F in Figure 1 show different chamber configur...

Page 6: ...a diameter at least as larger as the minimum width listed For steel cylinder chambers increase this dimension by from 1 to 4 inches 4 Wing walls are not recommended Corbels can be beneficial to heat...

Page 7: ...t flange if needed 7 The end of the air tube should be flush or almost flush with the inside of the combustion chamber wall 8 Verify the air tube is level and inserted the correct depth Adjust if nece...

Page 8: ...s are intended only for negative overfire pressure For pressur ized firing you must obtain a burner with a welded flange designed for use with the specific appliance Failure to comply could result in...

Page 9: ...ng from the housing Replace the gasket if not in good condition 9 Inspect the ignitor contact clips Clean or replace if necessary to ensure reliable contact with the electrodes Install nozzle check el...

Page 10: ...retention ring clamp is firmly against the nozzle adapter shoulder Set initial burner air settings Combustion head 1 The combustion head adjusting slide controls the spacing between the retention ring...

Page 11: ...15 20 0 20 0 20 0 1 25 1 70 2 2 15 2 60 4 0 4 75 2 3 20 2 3 65 5 5 4 5 80 3 25 3 70 5 10 5 100 4 5 70 4 100 6 45 6 100 6 100 5 100 8 65 7 100 6 7 100 9 100 8 100 11 100 10 102CRD 2 air cone B style a...

Page 12: ...d installed and that the fuel flow is unob structed the oil tank is clean and only 1 or 2 heating oil are supplied Failure to supply a reliable oil flow could result in loss of heat and potential seve...

Page 13: ...lation air openings and vent system o Fuel supply line in good condition and sized designed correctly o Oil tank has oil and oil line valves are open o Wiring installed per burner appliance instructio...

Page 14: ...ents a Check smoke It should be zero on the Bacharach scale b Set the appliance flue damper or barometric draft regulator so the draft or pressure in the vent complies with the appliance manufacturer...

Page 15: ...manual with the user Verify the user is aware of all procedures specified in the manuals Verify user will not store or use combustible liquids or materials or contaminants in the vicinity of the burn...

Page 16: ...21998S 102CRD 7 C Air Tube Combustion Head Assy 22004S 102CRD 9 C Air Tube Combustion Head Assy 21915S 102CRD 11 C Air Tube Combustion Head Assy 4 41000S 110V Ignitor 41000S0CAS 110V Ignitor on Basepl...

Page 17: ...arts continued ITEM PART NO DESCRIPTION 99FRD 100CRD 102CRD 17 70200S Universal Primary w Display 70200 48245S Model 48245 Primary w Smart Ignition 4020002S Model 40200 Primary 30 15 30 5020002S Model...

Page 18: ...time you replace a component or disassemble any part of the burner for service maintenance perform a complete operational test after reassembly to verify the burner operates correctly Failure to veri...

Page 19: ...MN99102 042015 19 Model 99FRD 102CRD EZ 66 Oil Burners Instruction Manual...

Page 20: ...ttempt to use gasoline as a fuel for this burner as it is more combustible and could result in a serious explosion Never attempt to burn refuse or use any fuel other than 1 or 2 heating oil ASTM D396...

Reviews: