Code
Description
Def Min Max
UOM User
User
terminal
DOG
Assign defrost digital output - see DOA
1
0
4
-
S
NO
DOH
Assign auxiliary evaporator defrost digital output - see DOA
0
0
4
-
S
NO
DOI
Assign evaporator fan digital output - see DOA
2
0
4
-
M
NO
DOo
Assign timed digital output - see DOA
0
0
4
-
M
NO
DOP
Assign drain heater digital output - see DOA
0
0
4
-
M
NO
DOQ
Assign anti-sweat heater digital output - see DOA
0
0
4
-
S
NO
rOA
Solenoid/compressor digital output logic
0/1 = direct/reverse
0
0
1
-
M
NO
rOb
Alarm digital output logic - see rOA
0
0
1
-
M
NO
rOc
Auxiliary digital output logic - see rOA
0
0
1
-
M
NO
rOd
Auxiliary serving the Master on the Slaves digital output logic - see rOA
0
0
1
-
M
NO
rOE
Light digital output logic - see rOA
0
0
1
-
S
NO
rOF
Light serving the Master on the Slaves digital output logic - see rOA
0
0
1
-
S
NO
rOG
Defrost digital output logic - see rOA
0
0
1
-
S
NO
rOH
Auxiliary evaporator defrost digital output logic - see rOA
0
0
1
-
S
NO
rOI
Evaporator fan digital output logic - see rOA
0
0
1
-
S
NO
rOo
Timed digital output logic - see rOA
0
0
1
-
M
NO
rOP
Drain heater digital output logic - see rOA
0
0
1
-
M
NO
H9
Output switched with time bands
0 = Light
1 = AUX
0
0
1
-
S
NO
Analogue outputs
NO
/AA
Assign analogue output for modulating fans
0 = not configured
1 = analogue output 1 (Y1)
2 = analogue output 2 (Y2)
0
0
2
-
M
NO
/Ab
Assign analogue output for modulating valve - see /AA
0
0
2
-
M
NO
/Ac
Assign analogue output for modulating anti-sweat heaters - see /AA
0
0
2
-
M
NO
Control
ON
ON/OFF control
0/1: OFF/ON
0
0
1
-
S
YES
/4
Virtual probe composition
0 = Air off probe Sm
100 = Air on probe Sr
0
0
100
%
S
NO
r1
Minimum set point
-50 -50
r2
°C/°F
M
NO
r2
Maximum set point
50
r1
50
°C/°F
M
NO
r4
Automatic night set point variation
0
-50
50
°C/°F
S
NO
r6
Probe for night-time control
0/1 = virtual probe Sv/air on probe Sr
0
0
1
-
S
NO
ro
Control offset with probe error
0
0
20
°C/°F
S
NO
r7
Master solenoid valve configuration
0/1 = local valve/network valve (connected to Master)
0
0
1
-
S
NO
St
Set point
50
r1
r2
°C/°F
U
YES
St2
Air on probe set point with double thermostat
50
r1
r2
°C/°F
S
NO
rd
Differential
2
0.1
20
°C/°F
U
YES
rd2
Set point St2 differential with double thermostat
0.0 = function disabled
0
0
20
°C/°F
S
NO
rHS
Virtual probe composition for glass temp. probe estimate
0 = Air off probe Sm
100 = Air on probe Sr
20
0
100
%
S
NO
rHA
Coeff. A for glass temp. probe estimate
2
-20
20
°C/°F
S
NO
rHb
Coeff. B for glass temp. probe estimate
22
0
100
-
S
NO
rHo
Offset for anti-sweat modulation
2
-20
20
°C/°F
S
NO
rHd
Differential for anti-sweat heater modulation
0
0
20
°C/°F
S
NO
rHu
Manual anti-sweat heater activation percentage (of period ‘rHt’)
70
0
100
%
S
NO
ENG
0300086EN rel. 1.0 – 04.09.2018
6. Parameter table |
87