ENG
Fig.5.h
Ref.
Description
T
temperature
t
time
Sr
intake probe (air on)
Ref.
Description
Sv
Virtual probe
Sm
Outlet probe (air off)
Shared network solenoid
If using solenoid valves, on Master controllers only the solenoid output (DOA) can be configured as a
network solenoid output. The function is useful for multiplexed showcases: the network solenoid valve is
only connected to the Master controller, which opens when at least one of the Slaves is in cooling request.
Code Description
Def Min Max UOM User
User
terminal
DOA
Assign solenoid/comp. digital output
0 = not set
3 = digital output 3 (NO3)
1 = digital output 1 (NO1)
4 = digital output 4 (NO4)
2 = digital output 2 (NO2)
3
0
4
-
S
NO
r7
Master solenoid valve configuration
0/1 = local valve/network valve (connected to Master)
0
0
1
-
S
NO
If configured as the network solenoid, the valve is:
l
open: if at least one of the controllers requires cooling;
l
closed: if there is no control request or if at least one of the controllers has a serious valve alarm (low
superheat, low suction temperature, high evaporation pressure), when suitably configured. See
parameters P10 and PM5.
Code Description
Def Min Max UOM User
User
terminal
P10
Enable close solenoid valve for low superheat (LowSH) and/or
low suction temp. (LSA)
1 = closing enabled
0
0
1
-
M
NO
PM5
MOP: close solenoid valve
0/1 = No/Yes
0
0
1
-
S
NO
54
| 5. Functions
0300086EN rel. 1.0 – 04.09.2018