Type HF alarms
The type HF HACCP alarm is generated following a power failure for an extended time (> 1 minute), if
when power returns the temperature read by probe set for parameter AA exceeds the AH high
temperature threshold. HFn indicates the number of type HF alarms activated.
Par.
Description
Def.
Min
Max
UOM User
User terminal
HFn (*)
Number of type HF alarms
0
0
15
-
S
NO
Fig.8.d
Ref.
Description
S
Measurement probe
St
Set point
AH
Low temperature alarm threshold
Ref.
Description
ALARM Type HA HACCP alarm
t
Time
(*) parameters visible to supervision or in the APPLICA app.
ENG
0300086EN rel. 1.0 – 04.09.2018
8. Alarms and signals |
105