ENG
Code
Description
Def Min Max
UOM User
User
terminal
0 = function disabled
rHt
Manual anti-sweat heater activation period
0 = function disabled
5
0
180
min
S
NO
CLt
Max time for Clean status
0
0
999
min
U
NO
Stt
Maximum time for Standby status
0
0
240
min
S
NO
H14
Time light stays on after closing the door
0
0
240
min
U
NO
dbS
Safety timeout for double thermostat function
0
0
240
min
M
NO
db1
Double thermostat function logic
0/1: AND logic/OR logic
0
0
1
-
M
NO
rSu
Suction valve closing delay in normal control mode
0
0
999
s
S
NO
Defrost
d0
Type of defrost
0 = heater by temperature
1 = reserved
2 = heater by time
3 = reserved
4 = heater by time with temperature control
0
0
4
-
S
YES
d2
End defrost synchronised by Master
0/1 = not synchronised/synchronised
1
0
1
-
S
NO
d3
Send network start defrost command (for Master)
0/1: yes/no
Ignore network start defrost command (for Slave)
0/1: no/yes
0
0
1
-
S
NO
dI
Maximum interval between consecutive defrosts
8
0
240
hours
S
YES
dt1
End defrost temperature (read by Sd)
8
-50
50
°C/°F
S
YES
dt2
End defrost temperature (read by Sd2)
8
-50
50
°C/°F
S
NO
dP1
Maximum defrost duration
45
1
240
min
S
YES
dP2
Max secondary evap. defrost duration
45
1
240
min
S
NO
d4
Defrost on power-up (Master = network defrost; Slave = local defrost)
0/1 = No/Yes
0
0
1
-
S
NO
d5
Defrost delay on power-up or (for Slave) after control from Master
0 = delay disabled
0
0
240
min
S
NO
d6
Display on terminals during defrost
0 = temperature alternating with ‘dEF’
1 = freeze display
2 = ‘dEF’
1
0
2
-
U
NO
dd
Dripping time after defrost (fans off)
0 = no dripping
2
0
15
min
S
NO
d7
Skip defrost
0/1 = disabled/enabled
0
0
1
-
S
NO
d8
Bypass high temperature alarm time after defrost
30
1
240
min
S
NO
d9
Defrost priority over compressor protection times
0/1 = protection times observed/protection times not observed
1
0
1
-
M
NO
d10
Defrost time in Running time mode
0 = function disabled
0
0
240
min
S
NO
d11
Defrost temperature threshold in Running time mode
-30 -50
50
°C/°F
S
NO
d12
Pressure probe alarm management during defrost
probe error
supervisor update
0
disabled
enabled
1
enabled
enabled
2
disabled
disabled
3
enabled
disabled
0
0
3
-
M
NO
dH1
Pump down phase duration
0 = pump down disabled
0
0
999
s
M
NO
dS1
Compressor off time in sequential stop defrost mode
0 = function disabled
0
0
45
min
M
NO
88
| 6. Parameter table
0300086EN rel. 1.0 – 04.09.2018