smartphone, with BLE connection, using the specific function on the alarm page ("Service" level access is
required).
Note:
deletion of the alarm log is irreversible.
8.3 Display
alarm log
The alarm log can only be viewed via the supervisor or APP with BLE connection.
8.4 Alarm table
Display
code
Description
Display
icon
flashing
Alarm
relay
Buzzer Reset
Compressor Defrost
Evaporator
fans
Continuous
cycle
Signalled
to LAN
Network
solenoid
valve
rE
Control probe
ON
ON
automatic
duty setting
(c4)
unchanged unchanged unchanged YES
NO
E1
Probe S1
OFF
OFF
automatic
duty setting
(c4)
unchanged unchanged unchanged YES
NO
E2
Probe S2
OFF
OFF
automatic
unchanged
unchanged unchanged unchanged YES
NO
E3
Probe S3
OFF
OFF
automatic
unchanged
unchanged unchanged unchanged YES
NO
E4
Probe S4
OFF
OFF
automatic
unchanged
unchanged unchanged unchanged YES
NO
E5
Probe S5
OFF
OFF
automatic
unchanged
unchanged unchanged unchanged YES
NO
E6
Probe S6
OFF
OFF
automatic
unchanged
unchanged unchanged unchanged YES
NO
E11
Serial probe S11
not updated
OFF
OFF
automatic
duty setting
(c4)
unchanged unchanged unchanged YES
NO
E12
Serial probe S12
not updated
OFF
OFF
automatic
duty setting
(c4)
unchanged unchanged unchanged YES
NO
E13
Serial probe S13
not updated
OFF
OFF
automatic
duty setting
(c4)
unchanged unchanged unchanged YES
NO
E14
Serial probe S14
not updated
OFF
OFF
automatic
duty setting
(c4)
unchanged unchanged unchanged YES
NO
LO
Low temperature
ON
ON
automatic
unchanged
unchanged unchanged unchanged YES
NO
HI
High temperature
ON
ON
automatic
unchanged
unchanged unchanged unchanged YES
NO
LO2
Low temperature
ON
ON
automatic
unchanged
unchanged unchanged unchanged YES
NO
HI2
High temperature
ON
ON
automatic
unchanged
unchanged unchanged unchanged YES
NO
IA
Immediate
alarm
from
external
contact
ON
ON
automatic
duty setting
(A6)
unchanged unchanged unchanged YES
NO
dA
Delayed
alarm
from
external
contact
ON
ON
automatic
duty setting
(A6) if A7≠0
unchanged unchanged unchanged YES
NO
dor
Door open for too
long
ON
ON
automatic
unchanged
unchanged unchanged unchanged YES
NO
Etc
Real time clock not
updated
OFF
OFF
automatic
unchanged
unchanged unchanged unchanged YES
NO
LSH
Low superheat
OFF
OFF
automatic
OFF
unchanged unchanged unchanged YES
YES
LSA
Low
suction
temperature
OFF
OFF
automatic/manual
OFF
(paragraph
6.10)
unchanged unchanged unchanged YES
YES
MOP
Maximum
evaporation
pressure
OFF
OFF
automatic
OFF
unchanged unchanged unchanged YES
YES
LOP
Low
evaporation
temperature
OFF
OFF
automatic
unchanged
unchanged unchanged unchanged YES
YES
bLo
Valve blocked
OFF
OFF
manual/disabled
when P14=0
unchanged
unchanged unchanged unchanged YES
NO
Edc
Communication
ON
ON
automatic
unchanged
unchanged unchanged unchanged YES
NO
100