ir33+ VCC
+040000058 - rel. 1.2 - 15.02.2018
User
Par.
Description
Def.
Min
Max
UOM
Type Carel
SPV
ModBus® R/W
dEF
C
d0
"Type of defrost
0 = heater by temperature
1 = hot gas by temperature
2 = heater by time (Ed1, Ed2 not shown)
3 = hot gas by time (Ed1, Ed2 not shown)
4 = heater by time with temperature control
(Ed1, Ed2 not shown)"
1
0
4
-
I
39
139
R/W
F
dI
"Maximum time between consecutive defrosts
0 = defrost not performed"
8
0
250
hour/
min
I
40
140
R/W
F
dt1
End defrost temperature probe 2
4
-50
200
°C/°F
A
23
23
R/W
F
dt2
End defrost temperature probe 3 (aux evaporator)
4
-50
200
°C/°F
A
24
24
R/W
F
dt3
End defrost temperature probe 4
4
-50
200
°C/°F
A
38
38
R/W
F
dP1
Maximum defrost duration
30
1
250
min/s
I
41
141
R/W
F
dP2
Maximum aux evaporator defrost duration
30
1
250
min/s
I
42
142
R/W
C
d3
Defrost activation delay
0
0
250
min
I
43
143
R/W
C
d4
Defrost at start-up: 0/1=disabled/enabled
0
0
1
-
D
48
48
R/W
C
d5
Defrost delay at start-up (if d4=1) or from dI
0
0
250
min
I
44
144
R/W
C
d6
"Terminal display during defrost
0 = Temperature alternating with dEF
1 = Display disabled - 2 = dEF"
1
0
2
-
I
45
145
R/W
F
dd
Dripping time after defrost (fans off )
2
0
15
min
I
46
146
R/W
F
d8
High temperature alarm bypass time after defrost
(and door open)
1
0
250
hour/
min
I
47
147
R/W
C
d8d
Alarm bypass time after door open
0
0
250
min
I
141
241
R/W
C
d9
"Defrost priority over compressor protectors
0/1 = yes/no"
0
0
1
-
D
49
49
R/W
F
d/1
Display defrost probe 1
0
0
0
°C/°F
A
1
1
R
F
d/2
Display defrost probe 2
0
0
0
°C/°F
A
2
2
R
C
dC
"Time base for defrost
0 = dI in hours, dP 1 and dP2 in minutes
1 = dI in minutes, dP1 and dP2 in seconds"
0
0
1
-
D
50
50
R/W
C
dC1
Time base for c6 and d8: 0/1 = hours/minutes
0
0
1
-
D
69
69
R/W
C
d10
Defrost time in “Running time” mode
0 = function disabled"
0
0
250
hour/
min
I
48
148
R/W
C
d11
Running time defrost temperature threshold
1
-20
20
°C/°F
A
25
25
R/W
C
d20
"Time base for defrost time in “Running time”
(d10)
0 = d10 in hours - 1 = d10 in minutes"
0
0
1
-
D
80
80
R/W
C
d12
"Advanced defrosts d12 - Skip defrost - Automatic
variation of dI: 0 - Disabled - Disabled
1 - Disabled - Enabled
2 - Enabled - Disabled
3 - Enabled - Enabled"
0
0
3
-
I
49
149
R/W
C
dn
Nominal defrost duration
65
1
100
-
I
50
150
R/W
C
dH
Proportional factor for variation of dI
50
0
100
-
I
51
151
R/W
C
dH1
Defrost valve delay (related to drain heater)
180
0
999
s
I
155
255
R/W
C
dH2
Post dripping drain
180
0
999
s
I
156
256
R/W
ALM
C
A0
Alarm and fan diff erential
2
0,1
20
°C/°F
A
26
26
R/W
C
A1
"Alarm thresholds (AL, AH) relative to set point or
absolute: 0/1=relative/absolute"
1
0
1
-
D
51
51
R/W
F
AL
"Low temperature alarm threshold
If A1= 0, AL=0: alarm disabled
If A1= 1, AL=-50: alarm disabled"
-26
-50
200
°C/°F
A
27
27
R/W
F
AH
"High temperature alarm threshold
If A1= 0, AL=0: alarm disabled
If A1= 1, AL=200: alarm disabled"
-14
-50
200
°C/°F
A
28
28
R/W
F
Ad
High and low temperature alarm delay
120
0
250
min
I
52
152
R/W