22
ENG
ir33+ VCC
+040000058 - rel. 1.2 - 15.02.2018
4. PARAMETER
TABLE
For a detailed explanation of these parameters, see the standard ir33+ user manual.
The rows of the table in grey correspond to masked parameters.
User
Par.
Description
Def.
Min
Max
UOM
Type Carel
SPV
ModBus® R/W
Pro
C
/2
Probe measurement stability
4
1
15
-
I
17
117
R/W
C
/3
Probe display stability
Value
Display
delay. (s)
Value
Display
delay. (s)
0
disabled
8
50
1
5
9
60
2
10
10
75
3
15
11
90
4
20
12
105
5
25
13
120
6
30
14
150
7
40
15
180
0
0
15
-
I
18
118
R/W
C
/4
"Virtual probe composition
0 = Control probe S1 - 100 = Probe S2"
0
0
100
-
I
19
119
R/W
C
/5
Temperature unit of measure: 0 = °C; 1 = °F
0
0
1
-
D
43
43
R/W
C
/6
Display decimal point: 0/1=no/yes
0
0
1
-
D
44
44
R/W
C
/tI
Display on user terminal
1 - Virtual probe
2 - Probe 1
3 - Probe 2
4 - Probe 3
5 - Probe 4
6 - Reserved
7 - Set point
1
1
7
-
I
20
120
R/W
C
/tE
Reading on remote display
0 - Not fi tted
1 - Virtual probe
2 - Probe 1
4 - Probe 3
5 - Probe 4
6 - Reserved
0
0
6
-
I
21
121
R/W
C
/P
"Type of probe
0 = NTC Standard Range -50T90°C
1 = NTC Enhanced Range -40T150°C
2 = PTC Standard Range -50T150°C"
0
0
2
-
I
22
122
R/W
C
/A2
"Probe 2 confi guration (S2)
0 - Absent
1 - Product (display only)
2 - Defrost
3 - Condenser
4 - Frost"
2
0
4
-
I
23
123
R/W
C
/A3
"Probe 3 confi guration (S3/ DI1)
0 - Digital input 1
1 - Product (display only)
2 - Defrost
3 - Condenser
4 - Frost"
0
0
4
-
I
24
124
R/W
C
/A4
"Probe 4 confi guration (S4/ DI2)
0 Digital input 2
1 Product (display only)
2 Defrost
3 Condenser
4 Frost"
0
0
4
-
I
25
125
R/W