3.1.6 Pull
down
The controller activates an automatic pull down procedure whenever the refrigeration unit temperature
exceeds the high temperature threshold
AH
. The Pull Down procedure ends when the refrigeration unit
temperature reaches the set point
St
. The maximum Pull Down time is set for parameter
cPd
. During a Pull
Down cycle, defrost calls are ignored and remain in standby.
Code
Parameter
UOM
Dis.
Def.
Max
Min
AH
AL = Low temperature alarm threshold
°C/°F
C
-14
50.0
-50.0
cPd
Compressor maximum pull down time
h
C
1
240
0
Tab. 3.e
3.1.7 Evaporator
fan
The evaporator fan is managed based on parameters
F0/F1/F2/F3
, in the same way as for standard control.
The fan is also managed as standard with the defrost water drain heating function. During the dripping time
dd
and the post-dripping time
Fd
, the fan remains off .
Code
Parameter
UOM
Dis.
Def.
Max
Min
F0
Evaporator fan management
-
C
0
2
0
F1
Fan activation temperature (only if F0 = 1 or 2)
°C/°F
C
5
200
-50
F2
Evap. fans with compressor off 0 = see F0; 1 = Always off
-
C
1
1
0
F3
Evaporator fans during the defrost: 0/1=on/off
dd
Dripping time after defrost (fans off )
min
C
2
15
0
Fd
Post-dripping time after defrost (defrost water drain heating remains
active during this time/fans off with control active)
min.
C
3
15
0
Tab. 3.f
3.1.8 Continuous
cycle
When the continuous cycle is activated the compressor is started (if off , otherwise it stays on). In this case there
is no active temperature control. The compressor runs to the speed set for parameter
cMf
. The continuous
cycle remains active until reaching the low temperature alarm threshold (parameter
AL
) or when the set time
has elapsed (parameter cc).
3.1.9
Neutral zone and reverse mode
Compressor confi guration with neutral zone and AUX relay as heater in reverse mode.
The AUX relay must be confi gured as a heater by setting
H1=11
. The compressor starts working when
St +
rn/2 + rd
, as described in the following diagram. To activate the AUX heater
H1=11
, the compressor must be
off and the set point reached.
Note the following:
•
The compressor stops when T< St and the time set for
cct
has elapsed.
•
If
cct
is set to
0
, the compressor stops immediately when the temp. T reaches the set point
St
”.
•
If
cct
is set to
255
, the compressor
never
stops and the AUX heater is disabled.
ON
OFF
CMP
rr
rn/2
rn/2
AUX
rd
St
Fig. 3.f