17
ENG
ir33+ VCC
+040000058 - rel. 1.2 - 15.02.2018
In this case, the fan outputs are activated based on the following logic:
ON
OFF
St
t
rd/2
VCC
ON
OFF
rd/2
AUX
Fig. 3.i
Key:
St = Set point
rd = Diff erential
Sv = Virtual probe
CMP = Compressor output
AUX = Auxiliary output
3.1.12 Pump
down
The pump down function can be activated when parameter
H1 = 5
and
c7 ≥ 7
. The AUX relay is thus used to
control the pump down valve. Digital input DI1 must be confi gured as a low pressure switch
A4 = 8
, otherwise
pump down will be performed by time if
c10 = 1
.
To start the pump down function, compressor control must fi rst stop. The pump down function can then start.
Pump down can be started immediately by setting
cct = 0
.
If
c10 = 1
and no pressure switch is confi gured
(A4 = 8),
the pump down ends after the time set for
c7
.
Compressor restart can be delayed for the time set for
c8
.
Code Parameter
UOM
Dis.
Def. Max Min
c7
Maximum pump down time (PD): 0 = Pump down disabled
Sec
C
0
900
0
c8
Compressor start delay after opening PD valve
Sec
C
5
60
0
c9
Autostart in pump down: 0 = Disabled -
1 = Pump down whenever closing pump down valve and following low
pressure switch activation with no cooling demand
-
C
1
1
0
c10
Pump down by time or pressure: 0 = pressure; 1 = time
-
C
0
1
0
A4
Digital input 1 confi guration (DI1): 8 = low pressure switch
min
C
0
1
0
H1
AUX1 output confi guration
0: normally energised alarm
1: normally de-energised alarm
2: auxiliary
3: light
4: auxiliary evaporator defrost
5: pump down valve
6: condenser fan
7: delayed compressor
8: auxiliary with deactivation when OFF
9: light with deactivation when OFF
10: no function
11: reverse with neutral zone
12: second compressor step
13: no function
14: condensate drain heater
-
C
10
14
0
Tab. 3.k