23
ENG
ir33+ VCC
+040000058 - rel. 1.2 - 15.02.2018
User
Par.
Description
Def.
Min
Max
UOM
Type Carel
SPV
ModBus® R/W
C
/c1
Probe 1 calibration
0
-20
20
°C/°F
A
11
11
R/W
C
/c2
Probe 2 calibration
0
-20
20
°C/°F
A
12
12
R/W
C
/c3
Probe 3 calibration
0
-20
20
°C/°F
A
13
13
R/W
C
/c4
Probe 4 calibration
0
-20
20
°C/°F
A
14
14
R/W
Ctl
F
St
Set point
-20
r1
r2
°C/°F
A
16
16
R/W
F
rd
Diff erential
1
0,1
20
°C/°F
A
17
17
R/W
C
rn
Neutral zone
4
0
60
°C/°F
A
34
34
R/W
C
rr
Reverse diff erential
2
0,1
20
°C/°F
A
35
35
R/W
C
r1
Minimum set point
-50
-50
r2
°C/°F
A
18
18
R/W
C
r2
Maximum set point
60
r1
200
°C/°F
A
19
19
R/W
C
r3
"Operating mode
0 = Direct with defrost control (cooling)
1 = Direct (cooling)
2 = Reverse (heating)"
0
0
1
-
I
27
127
R/W
C
r4
Automatic night-time set point variation
3
-20
20
°C/°F
A
20
20
R/W
C
r5
Enable temperature monitoring: 0/1=no/yes
0
0
1
-
D
45
45
R/W
F
rt
Duration of current max and min temperature
monitoring session
0
0
0
ore
I
28
128
R
F
rH
Maximum temperature read
0
0
0
°C/°F
A
21
21
R
F
rL
Minimum temperature read
0
0
0
°C/°F
A
22
22
R
CMP
C
c0
Compressor, fan and AUX start delay at power on
0
0
15
min
I
29
129
R/W
C
c1
Min. time between successive compressor starts
0
0
15
min
I
30
130
R/W
C
c2
Minimum compressor off time
0
0
15
min
I
31
131
R/W
C
c3
Minimum compressor on time
0
0
15
min
I
32
132
R/W
C
c4
Compressor running time with duty setting
0
0
100
min
I
33
133
R/W
C
cc
Continuous cycle duration
0
0
15
hour
I
34
134
R/W
C
c6
Low temp. alarm bypass time after continuous cycle
2
0
250
hour/
mi.
I
35
135
R/W
C
c7
"Maximum pump down time (PD)
0 = Pump down disabled"
0
0
900
s
I
36
136
R/W
C
c8
Compressor start delay after opening PD valve
5
0
60
s
I
37
137
R/W
C
c9
"Autostart in pump down
0 = Disabled; 1 = Pump down whenever closing
pump down valve & following low pressure
switch activation with no cooling demand"
0
0
1
-
D
46
46
R/W
C
c10
"Pump down by time or pressure
0/1= pressure/ time"
0
0
1
-
D
47
47
R/W
C
c11
Second compressor start delay
4
0
250
s
I
38
138
R/W
C
cPr
Proportional term of PI controller
2
0
800
Hz/°C
A
40
40
R/W
C
ctI
Integral time of PI controller
120
0
999
s
I
150
250
R/W
C
cdt
Derivative time for PID regulation
1
0
255
s
I
152
252
R/W
C
cSc
Soft start frequency
53
0
255
Hz
I
153
253
R/W
C
cMf
Compressor maximum regulation frequency
100
0
255
Hz
I
147
247
R/W
C
cmf
Compressor maximum regulation frequency
52
0
255
Hz
I
148
248
R/W
C
cdF
Compressor frequency for hot gas defrost
140
0
255
Hz
I
149
249
R/W
C
cct
Compressor cut-off time
1
0
255
min
I
151
251
R/W
C
cPd
Compressor pull down maximum time
1
0
240
hour
I
11
111
R/W
C
coA
"Enable the UCF alarm.
0: alarm disabled - 1: alarm enabled"
1
0
1
-
I
161
261
R/W
C
ctd
"Max. time delay for inverter serial commun. alarm
(COM). If ctd = 0 then the COM alarm is disabled"
15
0
60
s
I
162
262
R/W
C
cMI
Compressor turn off frequency (expr. in tens of Hz)
3
0
250
Hz x 10
I
163
263
R/W
C
cMA
Max. compressor rotation frequency (expressed
in tens of Hz)
15
0
250
Hz x 10
I
164
264
R/W
H
cUF
Hz to RPM conversion factor of VCC expressed
in tenths
300
0
999
0.1 Hz
I
158
258
R/W