PART 10
MAINTENANCE
CAUTION
It is important that all gas appliances to be serviced by a Camus trained service technician. It is in your own interest and that of
safety to ensure that all local codes, and all the “NOTES” and “WARNINGS” in this manual are complied with. To service or adjust
this appliance, it is imperative that the Camus trained service technician utilize a combustion analyzer to read CO
2,
CO and flue
pressure according to
Camus Hydronics
recommendation.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation, verify
proper operation after servicing.
Listed below are items that must be checked to ensure safe reliable operations. Verify proper operation after servicing.
10.1
EXAMINE THE VENTING SYSTEM
Examine the venting system at least once a year. Check more often in the first year to determine inspection interval. Check all joints
and pipe connections for tightness, corrosion or deterioration. Flush the condensate drain hose with water to clean. Clean screens in
the venting air intake system as required. Have the entire system, including the venting system, periodically inspected by a qualified
service agency.
10.2
VISUALLY CHECK MAIN BURNER FLAMES
At each start up after long shutdown periods or at least every six months. A burner view port is located on the burner mounting flange.
CAUTION
The area around the burner view port is hot and direct contact could result in burns.
Figure 46: Normal Burner Flame Profile (short dense and blue at full fire, infrared at low fire)
Normal Flame: A normal flame at 100% of burner input is blue, with slight yellow tips and a well-defined flame, no flame lifting
Yellow Tip: Yellow tipping can be caused by blockage or partial obstruction of air flow to the burner.
Yellow Flames: Yellow flames can be caused by blockage of primary air flow to the burner or excessive gas input. This condition
MUST
be corrected immediately
Lifting Flames: Lifting flames can be caused by over firing the burner, excessive primary air or high draft in excess of negative
0.15” w.c.
If improper flame is observed, examine the venting system; ensure proper gas supply and adequate supply of combustion and ventilation
air. Periodic visual check of pilot and burner flame is recommended to ensure trouble-free operation.
10.3
FLUE GAS PASSAGEWAYS CLEANING PROCEDURES
Any sign of soot around the flue pipe connections, burner or in the combustion chamber indicates a need for cleaning. The following
cleaning procedure must only be performed by a Camus trained service technician. Proper service is required to maintain safe operation.
Properly installed and adjusted units seldom need flue cleaning.
NOTE
All gaskets/sealant on disassembled components or jacket panels must be replaced with new gaskets/sealant on re-assembly.
Gasket and sealant kits are available from the factory.
CAUTION
When the vent system is disconnected for any reason it must be
reassembled and resealed according to vent manufacturer’s
instruction.
Summary of Contents for ADVANTUS AVH 1000
Page 2: ......
Page 3: ......
Page 38: ...31 Figure 23 Recommended Piping with Reverse Return and Variable Primary Flow...
Page 88: ...81 PART 12 EXPLODED VIEW Figure A...
Page 89: ...82 Figure B FAN BURNER ASSEMBLY AV500 600 some items may not be as shown...
Page 90: ...83 Figure C FAN BURNER ASSEMBLY AV800 4000 some items may not be as shown...
Page 91: ...84 Figure D Figure E...
Page 92: ...85 Figure F Figure G...
Page 93: ...86 Figure H CONTROL BOARD ASSEMBLY...
Page 100: ...93 PART 13 ELECTRICAL DIAGRAMS...
Page 101: ...94...
Page 102: ...95...