46
5)
The control will proceed into a Lockout 2 condition
6)
Press
[Verify]
>
[Begin]
>
[Yes]
7)
Press the reset button on the ignition control within the alotted time
Master Boiler
8)
Press
and
9)
Press
[Lead Lag Master Configuration]
10) Press
[Advanced Settings >]
11) Press the to arrive at
Outdoor Reset
12) Select
Enable: Enabled
13) Select
Maximum outdoor temperature
(WWSD)
14) Select
Minimum outdoor temperature
(Outdoor design)
15) Select
Low Water Temperature
(Min. water temp)
16) Select
Outdoor boost maximum off point
(Design max.)
17) Press
[Show Line]
to confirm reset curve
18) Press the to arrive at
Warm Weather Shutdown
19) Select
Enable = Shutdown after demand ends
Rotation schedule adjustment
Description
Electrical Connection(s)
Programming Instructions
Standard rotation
schedule is based on
equalizing run time on
a 1-hour schedule
To vary the rotation to a
fixed schedule based
on (hours, days)
1)
Press
and
2)
Press
[Lead Lag Master Configuration]
3)
Press
[Advanced Settings >]
4)
Press the to arrive at
Algorithms
5)
Select
Lead selection method: Sequence order
6)
Select
Lag selection method: Sequence order
7)
Select
Lead rotation time: (user defined)
Summary of Contents for ADVANTUS AVH 1000
Page 2: ......
Page 3: ......
Page 38: ...31 Figure 23 Recommended Piping with Reverse Return and Variable Primary Flow...
Page 88: ...81 PART 12 EXPLODED VIEW Figure A...
Page 89: ...82 Figure B FAN BURNER ASSEMBLY AV500 600 some items may not be as shown...
Page 90: ...83 Figure C FAN BURNER ASSEMBLY AV800 4000 some items may not be as shown...
Page 91: ...84 Figure D Figure E...
Page 92: ...85 Figure F Figure G...
Page 93: ...86 Figure H CONTROL BOARD ASSEMBLY...
Page 100: ...93 PART 13 ELECTRICAL DIAGRAMS...
Page 101: ...94...
Page 102: ...95...