49
6.2
CONFIGURE MENU
Figure 32: Configure Menu
6.2.1
SYSTEM IDENTIFICATION & ACCESS
Menu Group Selection
Parameter
Description
System Identification & Access
Product Type
Commercial Hydronic Boiler
OS number
Part Number of SOLA Controller
Software Version
Software version
Date Code:
Release date of software
Boiler Name
Advantus
Model Number
6.2.2
PUMP CONFIGURATION
Menu Group
Selection
Sub-Menu
Group Selection
Parameter
Selection
Description
Pump
Configuration
Central Heat
Pump
Pump Control
Auto
Assigns the method for SOLA to
control a Central Heating pump
(Default: Auto, Pump is activated
whenever a call for heat is
present)
ON
ON: Pump is constantly powered
Pump Output
Pump B
Specify pump contact
Over run time
1..5 min
Post pump time (Default: 1 min)
Use for local (Stand-alone)
demands
Use for Lead Lag Master
demands
Boiler Pump
Pump Control
Auto
Refer to above (Default)
ON
Refer to above
Pump Output
Pump A
Specify pump contact
Over run time
1..5 min
Post pump time (Default: 1 min)
Use for local (Stand-alone)
demands
Use for Lead Lag Master
demands
Pump
Configuration
DHW Pump
Pump Control
Auto
Refer to above (Default)
ON
ON: Pump is constantly powered
Pump Output
Pump B
Specify pump contact
Over run time
1..5 min
Post pump time (Default: 1 min)
Summary of Contents for ADVANTUS AVH 1000
Page 2: ......
Page 3: ......
Page 38: ...31 Figure 23 Recommended Piping with Reverse Return and Variable Primary Flow...
Page 88: ...81 PART 12 EXPLODED VIEW Figure A...
Page 89: ...82 Figure B FAN BURNER ASSEMBLY AV500 600 some items may not be as shown...
Page 90: ...83 Figure C FAN BURNER ASSEMBLY AV800 4000 some items may not be as shown...
Page 91: ...84 Figure D Figure E...
Page 92: ...85 Figure F Figure G...
Page 93: ...86 Figure H CONTROL BOARD ASSEMBLY...
Page 100: ...93 PART 13 ELECTRICAL DIAGRAMS...
Page 101: ...94...
Page 102: ...95...