43
DHW
Modulation: Boiler Inlet or DHW Sensor, Fixed Setpoint Operation (Standalone)
Description
Electrical Connection(s)
Programming Instructions
Boiler operates at a
fixed DHW setpoint
Modulates on boiler
inlet sensor (default)
Heat demand is
generated when inlet
temperature drops
below setpoint minus
on hysteresis.
For inlet sensor
operation constant
pumping is required
For DHW
sensor/Aquastat
operation intermittent
pumping is allowed
DHW Sensor/Stat, if required
1)
Place toggle switch to
LOCAL
2)
Press
and
Inlet Sensor operation
3)
Press
[DHW
– Domestic Hot Water Configuration]
4)
Select
Demand Switch: Modulation sensor only
5)
Select
Modulation sensor: Inlet Sensor
. Proceed to Step 17
DHW Sensor/Stat operation
6)
Press
[Sensor Configuration]
7)
Select
S6S7 (J9-1,3) Sensor (DHW)
:
10K NTC Single Non-Safety
8)
The control will proceed into a Lockout 2 condition
9)
Press
[Verify]
>
[Begin]
>
[Yes]
10) Press the reset button on the ignition control within the alotted time
DHW Sensor operation
11) Press
[DHW
– Domestic Hot Water Configuration]
12) Select
Demand Switch: Modulation sensor only
13) Select
Modulation sensor: DHW Sensor
. Proceed to Step 17
DHW Stat operation
14) Press
[DHW
– Domestic Hot Water Configuration]
15) Select
Demand Switch: DHW (S6) switch
16) Select
Modulation sensor: Inlet sensor
17) Enter desired
Setpoint
(Maximum setpoint is
Limited
to 140
o
F)
Summary of Contents for ADVANTUS AVH 1000
Page 2: ......
Page 3: ......
Page 38: ...31 Figure 23 Recommended Piping with Reverse Return and Variable Primary Flow...
Page 88: ...81 PART 12 EXPLODED VIEW Figure A...
Page 89: ...82 Figure B FAN BURNER ASSEMBLY AV500 600 some items may not be as shown...
Page 90: ...83 Figure C FAN BURNER ASSEMBLY AV800 4000 some items may not be as shown...
Page 91: ...84 Figure D Figure E...
Page 92: ...85 Figure F Figure G...
Page 93: ...86 Figure H CONTROL BOARD ASSEMBLY...
Page 100: ...93 PART 13 ELECTRICAL DIAGRAMS...
Page 101: ...94...
Page 102: ...95...