SEQUENCE OF OPERATION FOR BLAZE 200 D/G TURBO

 

 

With “Selector Switch” in “ON” position and selector switch in “STAT ON” position and remote 
thermostat plugged into receptacle: 

1: Remote Thermostat senses a drop in temperature and the ignition control module is energized. 
2: The module performs a safe start check and the burner and spark generator start.  Burner lights, ignition 
stops, and flame current is sensed. 
 
For oil: the Genisys primary control contacts close, the burner motor and ignitor are     
energized after a 15 second delay.  The primary control energizes the pump solenoid valve and flame is 
established.  The cad cell senses flame and the burner continues to fire.    
 
3: Fan switch heats up to factory set point (110F) OR after Time Delay of 1 minute and circulating air 
blower starts. 
4: When the remote thermostat senses space temperature at set point, the burner shuts down. 
5: The circulating blower continues to operate until the air in the unit cools to the factory set point (80 ºF) 
then turns off.

  

 
With selector switch in “BYPASS” position: 

1: The module performs a safe start check and the burner and spark generator start. 
2: Burner lights, ignition stops, and flame current is sensed. 
3: Fan switch heats up to factory set point (110F) and circulating air blower starts. 
4: When the selector switch is placed to the off position the burner shuts down. 
5: The circulating blower continues to operate until the air in the unit cools to the factory set point (80F) 
then turns off.

  

 

OPERATING INSTRUCTIONS FOR BLAZE 200 D/G TURBO  
 

STARTING HEATER

 

1.) 

ENSURE HEATER IS ON FLAT, LEVEL GROUND BEFORE STARTING, CANOPY AND FAN GUARDS   
MUST BE CLOSED.   

2.) 

MAKE SURE “SELECTOR SWITCH” IS IN “OFF” POSITION. 

3.) 

WIRE IN SUPPLY CORD TO 120V SUPPLY WITH GROUND.   

INSTALLATION 
12/3 AWG UPTO 50FT 
10/3 AWG BEYOND 50FT 
4.) 

TURN “SELECTOR SWITCH” TO “ON” POSITION. 

5.) 

FOR THERMOSTAT OPERATION FLIP SELECTOR SWITCH TO “STAT ON” POSITION.  IF YOU ARE NOT     

 

USING A THERMOSTAT FLIP SELECTOR SWITCH TO “BYPASS” POSITION. 

 

Please Note: When using a generator for electrical supply, make sure the generator is properly grounded and 
is running at a 60HZ frequency.  In the event that a generator is being used and the generator runs out of fuel, 
make sure the heater “SELECTOR SWITCH” is in the “OFF” position before restarting generator, failure to do 
so may damage heater. 

 
STOPPING HEATER 

 

1.)   Close main gas supply valve while heater is operating or if operating heater with oil skip to # 2.) 
2.)   Flip “SELECTOR SWITCH” to “OFF” position.

  

The supply fan will continue to operate until the heat exchanger 

has sufficiently cooled.  Do not disconnect main power until supply fan has stopped running and “SELECTOR 
SWITCH” is on “OFF” position.

 

3.)   Disconnect heater from gas supply OR disconnect fuel oil lines. 

 
 

Summary of Contents for ECOBlaze 200D Turbo

Page 1: ...P a g e 1 OIL NG LP FIRED SPACE HEATER BLAZE 200 D G TURBO WWW CAMPOEQUIPMENT COM REPORT 0367MH007S Installation Instructions Manual Maintenance Parts List CAUTION DO NOT TAMPER WITH HEATER OR ITS CON...

Page 2: ...CAMPO EQUIPMENT CO LTD ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com P a g e 2...

Page 3: ...TALL THE HEATER MUST HAVE THE TRAINING AND EXPERIENCE NECESSARY TO DO SO READ THIS MANUAL CAREFULLY FAILURE TO PROPERLY INSTALL AND SETUP THE HEATER COULD RESULT IN PROPERTY DAMAGE PERSONAL INJURY OR...

Page 4: ...UALIFIED PLUMBER AND GAS FITTER OF THE STATE OF MASSACHUSETTS THE INSTALLATION OF THIS HEATER FOR USE WITH A PROPANE TANK OR CYLINDER SHALL CONFORM WITH LOCAL CODES OR IN THE ABSENCE OF LOCAL CODES WI...

Page 5: ...OUT PUSH THE RED RESET BUTTON ONLY ONCE IF THE BURNER DOES NOT RE LIGHT DO NOT PUSH THE BUTTON A SECOND TIME OR EXCESS OIL WILL ACCUMULATE IN THE COMBUSTION CHAMBER CALL A QUALIFIED SERVICE PERSON INS...

Page 6: ...1 X 12 1 X 12 Gas Conversion Easy switch over Blue handle Ball Valve on Gas manifold Closed position Propane Open position Natural Gas N A Manifold pressure W C 3 5 NG or 3 5 LP Pressure to be set be...

Page 7: ...CONNECTION BETWEEN THE PROPANE SUPPLY CYLINDER S AND THE HEATER MUST BE DISCONNECTED AND THE CYLINDERS REMOVED FROM THE HEATER AND STORED IN ACCORDANCE WITH STANDARDS FOR THE STORAGE AND HANDLING OF...

Page 8: ...HE FUEL THE HEATER IS BURNING DO NOT OPERATE THE HEATER WITHOUT CONSULTING THE RATING PLATE HEATER CONVERSION MUST BE DONE BY A QUALIFIED TECHNICIAN AND RATING PLATE MUST REFLECT ANY CHANGE THIS UNIT...

Page 9: ...PPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE TEW 14GA WIRE OR ITS EQUIVALENT ELECTRICAL SYSTEM BLAZE 200 D G Volts Hertz Phase 120 60 1 Full Load Amps 9 Max fuse size in AM...

Page 10: ...CAMPO EQUIPMENT CO LTD ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com P a g e 10 Blaze 200D Turbo Schematic Beckett AFG Oil Burner...

Page 11: ...CAMPO EQUIPMENT CO LTD ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com P a g e 11 Blaze 200G Turbo Schematic Beckett CG4 Burner...

Page 12: ...switch heats up to factory set point 110F and circulating air blower starts 4 When the selector switch is placed to the off position the burner shuts down 5 The circulating blower continues to operate...

Page 13: ...BEFORE POWER SHUTDOWN 2 ALWAYS MAINTAIN ADEQUATE FUEL SUPPLY 3 IF GAS BURNER IS INSTALLED HEATER IS FOR USE WITH PROPANE OR NATURAL GAS ONLY SEE APPROVAL LABEL 4 DO NOT PLUG ANYTHING OTHER THAN THE T...

Page 14: ...feet BURNER END 3 feet DISCHARGE END 10 feet VENT CONNECTOR 3 feet COMBUSTIBLE FLOOR 6 feet FLUE PIPE CONNECTIONS VENT TO OUTDOORS FOR INSTALLATION ON NON COMBUSTIBLE FLOORS ONLY When the heater is c...

Page 15: ...ICIENT DISCHARGE AIR WILL CAUSE THE HEATER TO OVERHEAT BLAZE 200 D G TURBO MAINTENANCE INSTRUCTIONS WARNING EVERY CONSTRUCTION HEATER SHOULD BE INSPECTED BEFORE EACH USE AND AT LEAST ANNUALLY BY A QUA...

Page 16: ...frayed wires exposed FAN Check for dust or dirt build up on blades Run heater to check for fan vibration Replace fan blade if vibration is noticeable The flow of combustion and ventilation air must n...

Page 17: ...AFTER INSPECTION A COMPLETE COMBUSTION TEST MUST BE PEFORMED AFTER EACH ANNUAL SERVICE OF THE UNIT TO MAINTAIN OPTIMUM PERFORMANCE AND RELIABILITY WARNING TURN OFF THE FUEL SUPPLIES AND POWER BEFORE P...

Page 18: ...altitude and type of fuel used BECKETT CG4 THE BECKETT CG4 BURNER IS DESIGNED TO BE USED SOLELY WITH THE BECKETT 7590 GAS BURNER PRIMARY CONTROL AND THE 7474 GAS IGNITER 1 Loosen shutter and band and...

Page 19: ...e unit begins to produce smoke Increase air until no smoke is produced Check for excessive heat build up in the heat exchanger Insufficient air will cause flame impingement and reduced heat exchanger...

Page 20: ...mmended pump pressure 175 psi is recommended 3 Check nameplate for recommended air setting A 4 2 air setting is recommended 4 Install a pressure gauge in pump gauge port and start the burner Operate f...

Page 21: ...CAMPO EQUIPMENT CO LTD ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com P a g e 21 BECKETT AFG PARTS BREAKDOWN...

Page 22: ...CAMPO EQUIPMENT CO LTD ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com P a g e 22...

Page 23: ...EQUIPMENT CO LTD ECOBLAZE 6 Carson Court Brampton ON CANADA L6T 4P8 Tel 905 793 2525 Fax 905 793 8768 www campoequipment com P a g e 23 For replacement parts please contact Campo Equipment 1 866 323...

Reviews: