16
www.camplux.com
Leak Testing
WARNING:
Never use an open flame to test for gas leaks, as property damage, personal injury, or death
could result.
The water heater and its gas connections must be leak tested at normal operating pressures before it is placed
in operation.
• Turn on the gas shut-off valve(s) to the water heater.
• Use a commercial leak detector or soapy water solution to test for leaks at all connections and fittings.
Bubbles indicate a gas leak that must be corrected.
All connections should also be leak tested after the water heater is placed in operation.
Pressure Testing the Gas Supply System
WARNING:
Install a gas pressure regulator, in the gas supply line, which does not exceed the maximum
supply pressure. DO NOT use an industrial type gas regulator.
The water heater must be isolated from the gas piping system by closing the manual gas shut-off valve during
any pressure testing of the gas supply piping at pressures equal to or less than 1/2 PSI (14’w.c.) .
High Altitude
Ratings of gas appliances are based on sea level operation and need not be changed for installations at
elevations up to 2,000 feet / 600 meter. Unit not recommended for elevations in excess of 2,000 feet / 600
meter.
DANGER:
Failure to install the vent adapter and properly vent the water heater to the outdoors as
outlined in the Venting section of this manual will result in unsafe operation of the water heater causing death,
serious injury, explosion, or fire. To avoid the risk of fire, explosion,or asphyxiation from carbon monoxide,
NEVER operate the water heater unless it is properly vented and has adequate air supply for proper operation
as outlined in the Venting section of this manual.
WARNING:
Use UL approved Category III Stainless Steel vent material only. No other vent material is
permitted. Owner must refer to vent manufacturer’s instructions and specifications.
WARNING:
Refer to pages 17-18 for clearances to combustible material.
Venting
The installation of venting must comply with national codes, local codes, and the vent manufacturer’s
instructions. Owner must refer to vent manufacturer’s instructions and specifications.
Please visit a local
hardware store or online marketplaces to purchase φ3” Category III Stainless Steel Venting for certified
installation.
The water heater must be vented to the outdoors as described in these instructions. DO NOT connect this
water heater to an existing Vent or Chimney, it must be vented separately from all other appliances.
All vent components (adapters, pipe, elbows, terminals, etc.) should be UL 1738 Certified Stainless Steel
Venting Material (e.g. AL29-4C).
The specified vent termination must be used. The termination should be a 90° elbow type with screen. (Refer to
page 18).