SECTION 8. PROCESSING AND PROGRAM CONTROL EXAMPLES
8-4
PROGRAM
*
Table 1 Program
01:
10.0
Execution Interval (seconds)
01:
Pulse (P3)
1:
1
Reps
2:
1
Pulse Input Channel
3:
2
Switch Closure
4:
10
Loc [ Precip_1 ]
5:
.254
Mult
6:
0
Offset
02:
Pulse (P3)
1:
1
Reps
2:
3
Pulse Channel 3
3:
2
Switch Closure
4:
11
Loc [ Precip_2 ]
5:
.254
Mult
6:
0
Offset
03:
If time is (P92)
1:
0
Minutes (Seconds --) into a
2:
60
Interval (same units as above)
3:
10
Set Output Flag High
04:
Real Time (P77)
1: 0110
Day,Hour/Minute
05:
Totalize (P72)
1:
2
Reps
2:
10
Loc [ Precip_1 ]
INPUT LOCATIONS
10 Precip_1
11 Precip_2
8.5 CONVERTING 0-360 WIND
DIRECTION OUTPUT TO 0-540 FOR
STRIP CHART
If 0-360 degree wind direction is output to a strip
chart the discontinuity at 0/360 will cause the pen
to jump back and forth full scale when the winds
are varying from the north. In the days of strip
charts this was solved with a 0-540 degree pot on
the wind vane (direction changes from 540 to 180
and from 0 to 360 so the pen only jumps once
when the wind is out of the north or south).
When faced with the necessity of strip chart
output, the following algorithm can be used to
change a 0-360 degree input to 0-540. (If you
have a 0-540 pot, it can be used with the
CR510 since the Wind Vector Instruction, 69,
will work with this output.)
To change 0-360 degrees to the 0-540 degrees,
360 degrees must sometimes be added to the
reading when it is in the range of 0 to 180. The
following algorithm does this by assuming that if
the previous reading was less than 270, the vane
has shifted through 180 degrees and does not
need to be altered. If the previous 0-540 reading
was greater than 270, 360 degrees is added.
This example is written as a subroutine which is
used to output an analog voltage to a strip
chart.
*
Table 3 Subroutines
01:
Beginning of Subroutine (P85)
1:
1
Subroutine 1
02:
IF (X<=>F) (P89)
1: 10
X Loc [ 0_540_WD ]
2:
3
>=
3: 270
F
4: 30
Then Do
03:
Do (P86)
1: 11
Set Flag 1 High
04:
Else (P94)
05:
Do (P86)
1: 21
Set Flag 1 Low
06:
End (P95)
07:
Z=X (P31)
1:
2
X Loc [ 0_360_WD ]
2: 10
Z Loc [ 0_540_WD ]
08:
IF (X<=>F) (P89)
1: 10
X Loc [ 0_540_WD ]
2:
4
<
3: 180
F
4: 30
Then Do
09:
If Flag/Port (P91)
1: 11
Do if Flag 1 is High
2: 30
Then Do
10:
Z=X+F (P34)
1: 10
X Loc [ 0_540_WD ]
2: 360
F
3: 10
Z Loc [ 0_540_WD ]
11:
Z=X (P31)
1: 10
X Loc [ 0_540_WD ]
2:
6
Z Loc [ 0_540_out ]
Summary of Contents for CR510
Page 2: ...This is a blank page ...
Page 4: ...This is a blank page ...
Page 10: ...This is a blank page ...
Page 44: ...SECTION 1 FUNCTIONAL MODES 1 14 This is a blank page ...
Page 56: ...SECTION 3 INSTRUCTION SET BASICS 3 8 ...
Page 104: ...SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES 8 8 This is a blank page ...
Page 128: ...SECTION 10 PROCESSING INSTRUCTIONS 10 8 This is a blank page ...
Page 144: ...SECTION 12 PROGRAM CONTROL INSTRUCTIONS 12 10 This is a blank page ...
Page 172: ...SECTION 14 INSTALLATION AND MAINTENANCE 14 10 This is a blank page ...
Page 176: ...APPENDIX A GLOSSARY A 4 This is a blank page ...
Page 184: ...This is a blank page ...
Page 188: ...APPENDIX D DATALOGGER INITIATED COMMUNICATIONS D 4 This is a blank page ...
Page 196: ...APPENDIX F MODBUS ON THE CR10 X AND CR510 F 4 This is a blank page ...
Page 197: ...APPENDIX G TD OPERATING SYSTEM ADDENDUM FOR CR510 CR10X AND CR23X MANUALS ...
Page 198: ...This is a blank page ...
Page 200: ...This is a blank page ...
Page 206: ...TABLE DATA ADDENDUM AD 6 This is a blank page ...
Page 222: ...TD ADDENDUM SECTION 1 FUNCTIONAL MODES AD 1 8 This is a blank page ...
Page 238: ...TD ADDENDUM SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES AD 8 10 This is a blank page ...
Page 240: ...This is a blank page ...