SECTION 7. MEASUREMENT PROGRAMMING EXAMPLES
7-9
CR510
FIGURE 7.9-1. Wiring Diagram for Full Bridge Pressure Transducer
FIGURE 7.10-1. Lysimeter Weighing Mechanism
7.10 LYSIMETER - 6 WIRE FULL BRIDGE
When a long cable is required between a load cell
and the CR510, the resistance of the wire can
create a substantial error in the measurement if
the 4 wire full bridge (Instruction 6) is used to
excite and measure the load cell. This error arises
because the excitation voltage is lower at the load
cell than at the CR510 due to voltage drop in the
cable. The 6 wire full bridge (Instruction 9) avoids
this problem by measuring the excitation voltage at
the load cell. This example shows the errors one
would encounter if the actual excitation voltage
was not measured and shows the use of a 6 wire
full bridge to measure a load cell on a weighing
lysimeter (a container buried in the ground, filled
with plants and soil, used for measuring
evapotranspiration).
The lysimeter is 2 meters in diameter and 1.5
meters deep. The total weight of the lysimeter
with its container is approximately 8000 kg. The
lysimeter has a mechanically adjustable counter-
balance, and changes in weight are measured
with a 250 pound (113.6 kg) capacity Sensotec
Model 41 tension/compression load cell. The
load cell has a 4:1 mechanical advantage on the
lysimeter (i.e., a change of 4 kg in the mass of the
lysimeter will change the force on the load cell by
1 kg-force or 980 N).
The surface area of the lysimeter is 3.1416 m
2
or
31,416 cm
2
, so 1 cm of rainfall or evaporation
results in a 31.416 kg change in mass. The load
cell can measure
±
113.6 kg, a 227 kg range. This
represents a maximum change of 909 kg (28 cm of
water) in the lysimeter before the counterbalance
would have to be readjusted.
There is 1000 feet of 22 AWG cable between the
CR510 and the load cell. The output of the load cell
is directly proportional to the excitation voltage.
When Instruction 6 (4 wire half bridge) is used, the
assumption is that the voltage drop in the
connecting cable is negligible. The average
resistance of 22 AWG wire is 16.5 ohms per 1000
feet. Thus, the resistance in the excitation lead
going out to the load cell added to that in the lead
coming back to ground is 33 ohms. The resistance
Summary of Contents for CR510
Page 2: ...This is a blank page ...
Page 4: ...This is a blank page ...
Page 10: ...This is a blank page ...
Page 44: ...SECTION 1 FUNCTIONAL MODES 1 14 This is a blank page ...
Page 56: ...SECTION 3 INSTRUCTION SET BASICS 3 8 ...
Page 104: ...SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES 8 8 This is a blank page ...
Page 128: ...SECTION 10 PROCESSING INSTRUCTIONS 10 8 This is a blank page ...
Page 144: ...SECTION 12 PROGRAM CONTROL INSTRUCTIONS 12 10 This is a blank page ...
Page 172: ...SECTION 14 INSTALLATION AND MAINTENANCE 14 10 This is a blank page ...
Page 176: ...APPENDIX A GLOSSARY A 4 This is a blank page ...
Page 184: ...This is a blank page ...
Page 188: ...APPENDIX D DATALOGGER INITIATED COMMUNICATIONS D 4 This is a blank page ...
Page 196: ...APPENDIX F MODBUS ON THE CR10 X AND CR510 F 4 This is a blank page ...
Page 197: ...APPENDIX G TD OPERATING SYSTEM ADDENDUM FOR CR510 CR10X AND CR23X MANUALS ...
Page 198: ...This is a blank page ...
Page 200: ...This is a blank page ...
Page 206: ...TABLE DATA ADDENDUM AD 6 This is a blank page ...
Page 222: ...TD ADDENDUM SECTION 1 FUNCTIONAL MODES AD 1 8 This is a blank page ...
Page 238: ...TD ADDENDUM SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES AD 8 10 This is a blank page ...
Page 240: ...This is a blank page ...