Operation and maintenance instructions
Series PRE proportional pressure regulator
IO-Link version
5000030186
Ver. 03
35
16.
IO Device description (IODD)
IODD is a mandatory file for every device that contains all necessary information to establish the
communication and manage parameters and events of a specific device. The IODD of the Regulator
is available
http://catalogue.camozzi.com/Downloads.aspx?cat=182
17.
Troubleshooting and/or exceptional circumstances
UVIX
Code
Name
Description
IO-Link code
EXE
DEC
ERROR = The control operations are interrupted
E001
Alarm sensor
Communication error regarding pressure sensor,
the sensor doesn’t communicate in the right way
or
a diagnostic error is present
1800 6144
E002
E005
Alarm EEprom
Memory writing, reading or accessing error of
information that is essential to the process.
1802 6146
E006
E007
E009
Pressure out of range
The regulator is not able to reach the target
pressure.
1804 6148
E010
Fault up coil
Generic error during pilot valve power on, probably
caused by interrupted or short-circuited coil.
180D 6157
E011
Fault down coil
Generic error during pilot valve power off, probably
caused by interrupted or short-circuited coil.
180E
6158
WARNING = The control operations are not interrupted but performance is not guaranteed
A129
Undervoltage Power
Power supply is below the minimum value.
180C 6156
A130
Pressure out of range
The regulator is not able to reach the target
pressure.
1805 6149
A131
No activation valve
No activation valve error
1803 6147
A132 Data process not valid The connection with master is interrupted
180F
6159
A133
Warning EEprom
Memory writing, reading or accessing error of
information that is not essential to the process.
1806 6150
A134
A136
A141
IO-Link target out of
range
Target not valid
1807 6151