Operation and maintenance instructions
Series PRE proportional pressure regulator
IO-Link version
5000030186
Ver. 03
27
In the case of psi, having a resolution of 0.1 psi/bit, the pressure target has to be multiplied by
a factor of 10, i.e. if a target of 50 psi is desired, the pressure target sent by the master must
contain the value 500.
13.2.
Acyclic data
The data exchanged on request are all useful parameters to know the status of the pressure
regulator and to parameterize it.
The protocol provides a set of predefined parameters, some are mandatory, others are optional,
and manufacturers can to define others.
The parameters can be divided as follows:
▪
Device identification parameters
Address
Parameter
Access
(RO, WO o RW)
Dimension
(byte)
Description
0x0010
(16)
Vendor Name
RO
Max 64
Manufacturer name
0x0011
(17)
Vendor Text
Additional information of
manufacturer
0x0012
(18)
Product Name
Product name
0x0013
(19)
Product ID
Product ID
0x0014
(20)
Product Text
Product description
0x0015
(21)
Serial Number
Device serial number
0x0016
(22)
Hardware Version
Device hardware version
0x0017
(23)
Firmware Version
Device firmware version
0x0018
(24)
Application Specific Tag
RW
Da 16 a 32
Parameter available to
the user